Plan Review Notes For Permit 07120585 |
Permit Number |
07120585 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-01-02 15:45:59 | ***DENIED*** | | | | 1) IT WOULD APPEAR THAT THE 7TH LEVEL IS CONSIDERED | | SUITE 800. PLEASE VERIFY AND ADD APPROPRIATE SUITE | | NUMBERS IN ALL SUBMITTED SHEET TITLE BLOCKS. | | | | 2) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | 3) PLEASE ADVISE MINIMUM INTERIOR FINISH CLASSIFICATION | | FOR WALLS AND CEILING IN TERMS OF CLASS A,B OR C. | | | | 4) PLEASE INDICATE RATING OF FIRE DOORS IN TERMS OF | | MINUTES. | | | | 5) NEW DUCT SMOKE DETECTOR INSTALLATIONS WHEN ACTIVATED | | SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH | | LOCAL REQUIREMENTS. FA0.1 NOTE 17 | | | | 6) AS ALREADY STATED ON PLANS, SEPARATE SHOP DRAWINGS | | AND PERMITS REQUIRED PRIOR TO FIRE SPRINKLER AND FIRE | | ALARM REMODEL. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|