Notes
Date Text
2007-12-30 15:57:52 
 *** DENIED REVIEW ***
  
 1) NOTE: PLEASE BE SURE THE BASE BUILDING ELECTRICAL
 ENGINEER OF RECORD SIGNS BLOCK STAMPS FOR REVIEW.
 PLEASE KNOW THIS BUILDING DOES NOT HAVE A CERTIFICATE
 OF OCCUPANCY AND UNTIL SUCH TIME THE BASE BUILDING
 ENGINEER OF RECORD IS RESPONSIBLE AND NEEDS TO BE MADE
 AWARE OF ANY BASE BUILDING DESIGNS/LOADS/ LIGHTING
 PERFORMANCE CALCULATIONS ETC.
 FS 471
  
 2) NOTE: PLEASE KNOW THE SUITE/UNIT NUMBER WHICH WAS
 PLACED ON PERMIT APPLICATION WAS SUITE #700. PLEASE
 VERIFY AND IF DETERMINED AS ACCURATE PLEASE PLACE ON
 TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002, FBC ADMIN 106.5,
 106.1.2
  
 3) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS AS NOTED STATE THESE ARE DONE FOR *SPACE
 BY SPACE* YET THE CALCULATIONS SHOW ONLY OFFICE AREA.
 THIS IS NOT POSSIBLE AS THERE ARE SEVERAL OTHER TYPES
 OF ROOMS WHICH ARE NOT OFFICE.
 PLEASE ADJUST CALCULATIONS.
 PLEASE ALSO SEE THE NUMBER OF FIXTURES ON PLANS NEED TO
 COORDINATE WITH THE TOTALS ON THE LIGHTING POWER
 CALCULATIONS.
 PLEASE SEE FOR EXAMPLE:
 THE NUMBER OF *A* FIXTURES DO NOT CORRELATE,
 THE *B*,*BE*,*C* AND *CE* ALSO NEED ADJUSTING.
  
 THESE WERE NOTED FOR A COUPLE OF EXAMPLES.
  
 4) NOTE: PLEASE BE SURE TO CORRELATE ROOM DESIGNATIONS
 FROM SHEET TO SHEET. PLEASE SEE FOR EXAMPLE:
 SHEET E2.1 AND 3.1 WHICH SHOWS ELECTRICAL ROOM AND DATA
 ROOM SWITCHED FROM SHEET 6.1.
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE BE SURE TO GO OVER ALL LOAD ON LIGHTING
 AND OTHER LOADS SHOWN ON PANELS.
 PLEASE SEE FOR EXAMPLE: THE LIGHTING LOAD SHOWN ON
 PANEL *H7A-7* IS SHOWN AS 1.1 KVA WHICH IS NOT POSSIBLE
 BASED ON THE AMOUNT OF FIXTURES SHOWN ON THIS CIRCUIT
 ON LIGHTING PLANS E2.1.
 PLEASE ADJUST ALL LOAD CALCULATIONS.
 NEC 220.
 FBC 106.3.5.1
  
 6) NOTE: PLEASE SEE PANEL *L7A* IS BEING SHOWN AS A
 250AMP MCB PANEL WITH FEED-THRU LUGS TO PANEL *L7B* YET
 *L7B* IS SHOWN ONLY RATED AT 225AMPS. THIS PLACES OVER
 CURRENT PROTECTION ON PANEL WHICH IS HIGHER THAN THE
 MAXIMUM RATING OF ITS LISTING.
 PLEASE ADJUST.
 ( CONDUCTORS ON RISER ARE SHOWN RATED AT THE 250AMPS)
 90.7, 110.3.
  
 7) NOTE: PLEASE SEE PANEL *L7A* AS THE LOAD
 CALCULATIONS SHOWS AND INDICATES LOADS FROM PANELS
 *L8A* AND *L8B*, YET THE RISER, PLANS AND PANELS DO NOT
 SHOW ANY *8TH* LEVEL PANELS.
 THIS APPEARS TO BE A MISPRINT BASED ON PANELS AND LOADS
 SHOWN.
 PLEASE COORDINATE.
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE SEE THE CODES LISTED ON SHEET E0.1 SHOW
 2006 NFPA-101 AND 2007 NFPA-72.
 PLEASE KNOW AS OF THIS DATE OF REVIEW THIS OFFICE KNOWS
 OF NO CHANGE TO THE LATEST STATE ADOPTION OF THESE
 CODES.
 PLEASE SEE THE FOLLOWING ARE THE CURRENT EDITIONS OF
 CODES STATED AND KNOWN TO THIS OFFICE.
 2003 NFPA-101
 2002 NFPA-72
 ** THIS WAS VERIFIED *ON-LINE* AT THE STATE WEBSITE AS
 OF THISREVIEW WHICH STILL SHOWS 2003 AND 2002
 EDITIONS.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE
 ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717