2007-12-30 15:57:52 | |
| *** DENIED REVIEW *** |
| |
| 1) NOTE: PLEASE BE SURE THE BASE BUILDING ELECTRICAL |
| ENGINEER OF RECORD SIGNS BLOCK STAMPS FOR REVIEW. |
| PLEASE KNOW THIS BUILDING DOES NOT HAVE A CERTIFICATE |
| OF OCCUPANCY AND UNTIL SUCH TIME THE BASE BUILDING |
| ENGINEER OF RECORD IS RESPONSIBLE AND NEEDS TO BE MADE |
| AWARE OF ANY BASE BUILDING DESIGNS/LOADS/ LIGHTING |
| PERFORMANCE CALCULATIONS ETC. |
| FS 471 |
| |
| 2) NOTE: PLEASE KNOW THE SUITE/UNIT NUMBER WHICH WAS |
| PLACED ON PERMIT APPLICATION WAS SUITE #700. PLEASE |
| VERIFY AND IF DETERMINED AS ACCURATE PLEASE PLACE ON |
| TITLE BLOCKS. |
| FAC 61G1-16.004, 61G15-23.002, FBC ADMIN 106.5, |
| 106.1.2 |
| |
| 3) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| CALCULATIONS AS NOTED STATE THESE ARE DONE FOR *SPACE |
| BY SPACE* YET THE CALCULATIONS SHOW ONLY OFFICE AREA. |
| THIS IS NOT POSSIBLE AS THERE ARE SEVERAL OTHER TYPES |
| OF ROOMS WHICH ARE NOT OFFICE. |
| PLEASE ADJUST CALCULATIONS. |
| PLEASE ALSO SEE THE NUMBER OF FIXTURES ON PLANS NEED TO |
| COORDINATE WITH THE TOTALS ON THE LIGHTING POWER |
| CALCULATIONS. |
| PLEASE SEE FOR EXAMPLE: |
| THE NUMBER OF *A* FIXTURES DO NOT CORRELATE, |
| THE *B*,*BE*,*C* AND *CE* ALSO NEED ADJUSTING. |
| |
| THESE WERE NOTED FOR A COUPLE OF EXAMPLES. |
| |
| 4) NOTE: PLEASE BE SURE TO CORRELATE ROOM DESIGNATIONS |
| FROM SHEET TO SHEET. PLEASE SEE FOR EXAMPLE: |
| SHEET E2.1 AND 3.1 WHICH SHOWS ELECTRICAL ROOM AND DATA |
| ROOM SWITCHED FROM SHEET 6.1. |
| FBC 106.1.2 FOR COORDINATION. |
| |
| 5) NOTE: PLEASE BE SURE TO GO OVER ALL LOAD ON LIGHTING |
| AND OTHER LOADS SHOWN ON PANELS. |
| PLEASE SEE FOR EXAMPLE: THE LIGHTING LOAD SHOWN ON |
| PANEL *H7A-7* IS SHOWN AS 1.1 KVA WHICH IS NOT POSSIBLE |
| BASED ON THE AMOUNT OF FIXTURES SHOWN ON THIS CIRCUIT |
| ON LIGHTING PLANS E2.1. |
| PLEASE ADJUST ALL LOAD CALCULATIONS. |
| NEC 220. |
| FBC 106.3.5.1 |
| |
| 6) NOTE: PLEASE SEE PANEL *L7A* IS BEING SHOWN AS A |
| 250AMP MCB PANEL WITH FEED-THRU LUGS TO PANEL *L7B* YET |
| *L7B* IS SHOWN ONLY RATED AT 225AMPS. THIS PLACES OVER |
| CURRENT PROTECTION ON PANEL WHICH IS HIGHER THAN THE |
| MAXIMUM RATING OF ITS LISTING. |
| PLEASE ADJUST. |
| ( CONDUCTORS ON RISER ARE SHOWN RATED AT THE 250AMPS) |
| 90.7, 110.3. |
| |
| 7) NOTE: PLEASE SEE PANEL *L7A* AS THE LOAD |
| CALCULATIONS SHOWS AND INDICATES LOADS FROM PANELS |
| *L8A* AND *L8B*, YET THE RISER, PLANS AND PANELS DO NOT |
| SHOW ANY *8TH* LEVEL PANELS. |
| THIS APPEARS TO BE A MISPRINT BASED ON PANELS AND LOADS |
| SHOWN. |
| PLEASE COORDINATE. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 8) NOTE: PLEASE SEE THE CODES LISTED ON SHEET E0.1 SHOW |
| 2006 NFPA-101 AND 2007 NFPA-72. |
| PLEASE KNOW AS OF THIS DATE OF REVIEW THIS OFFICE KNOWS |
| OF NO CHANGE TO THE LATEST STATE ADOPTION OF THESE |
| CODES. |
| PLEASE SEE THE FOLLOWING ARE THE CURRENT EDITIONS OF |
| CODES STATED AND KNOWN TO THIS OFFICE. |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| ** THIS WAS VERIFIED *ON-LINE* AT THE STATE WEBSITE AS |
| OF THISREVIEW WHICH STILL SHOWS 2003 AND 2002 |
| EDITIONS. |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE |
| ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |