Plan Review Notes
Plan Review Notes For Permit 07120574
Permit Number 07120574
Review Stop P
Sequence Number 2
Notes
Date Text
2008-04-25 09:43:06PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE RELOCATION OF THE WASHING MACHINE AND LAUNDRY TRAY
 IS CONSIDERED AS NEW WORK AND THE SUBMITTED REVISION
 SHEET E-1 IS NOT COMPLIANT PER THE FOLLOWING.
  
 1. THE WASHING MACHINE SHALL CONNECT TO A BRANCH DRAIN
 OR STACK A MINIMUM OF 3 INCHES. PER FBC-2004 PLUMBING
 SECTION 406.3. WASTE CONNECTION.
  
 2. THE CLEANOUT FOR THE WASHING MACHINE STACK SHALL BE
 3 INCH. PER FBC-2004 PLUMBING SECTION 708.7 MINIMUM
 SIZE.
  
 3. THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 CLEARLY INDICATED AS BEING 4' A.F.F. PER FBC-2004
 PLUMBING SECTION 708.9 ACCESS.
  
 4. NOTE: THE INDICATED RUBBER COUPLING IS NOT
 COMPLIANT AS A JOINT BETWEEN DIFFERENT MATERIALS.
 CLEARLY INDICATE THIS TYPE OF CONNECTION PER FBC-2004
 PLUMBING SECTION 705.16 JOINTS BETWEEN DIFFERENT
 MATERIALS.
 JOINTS BETWEEN DIFFERENT PIPING MATERIALS SHALL BE MADE
 WITH A MECHANICAL JOINT OF THE COMPRESSION OR
 MECHANICAL-SEALING TYPE CONFORMING TO ASTM C 1173, ASTM
 C 1460 OR ASTM C 1461. CONNECTORS AND ADAPTERS SHALL BE
 APPROVED FOR THE APPLICATION AND SUCH JOINTS SHALL HAVE
 AN ELASTOMERIC SEAL CONFORMING TO ASTM C 425, ASTM C
 443, ASTM C 564, ASTM C 1440, ASTM D 1869, ASTM F 477,
 CAN/CSA A257.3M OR CAN/CSA B602.
  
 5. THE VALUE FOR THE JOB SHALL BE INCREASED FOR THE
 PROPOSED NEW WORK AND THE DIFFERENCE PAID BEFORE THE
 NEXT REVISION BEING RESUBMITTED FOR PLAN REVIEW. PER
 (W.P.B. AS AMENDED) SECTION 108.3 BUILDING PERMIT
 VALUATION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]