2007-12-31 08:11:13 | |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| ALL COMMENTS RELATE TO SHEET E-1 , UNLESS OTHERWISE |
| NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED |
| FOR THE FEED FOR THE NEW PANEL. |
| |
| 2} THE ELECTRICAL NOTE ON E-1 INDICATES A NEW SERVICE |
| IS TO BE INSTALLED. IF SO PROVIDE A RISER DIAGRAM PER |
| 215.5. AND AIC RATING OF THE EQUIPMENT PER 110.9-10. |
| THE NOTE ON THE "PANEL/LOAD CALCULATION" INDICATES AN |
| EXISTING 150 AMP PANEL. PLEASE CORRELATE TO INDICATE |
| PROPOSED WORK. THERE IS NO MENTION OF ELECTRICAL WORK |
| ON THE APPLICATION. |
| |
| 3} THE LOCATION OF THE NEW WATER HEATER DOES NOT COMPLY |
| WITH THE CLEARANCE REQUIREMENTS OF 110.26 DUE TO THE |
| LOCATION OF THE WASHER UNDER IT. |
| |
| 4} THE BATH CIRCUIT IS REQUIRED TO BE A 20 AMP CIRCUIT |
| WITH #12 CONDUCTORS PER 210.11(C) (3), |
| |
| 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.LOCATE |
| SAME ON THE PLANS, INDICATE IF EXISTING OR NEW WORK. |
| |
| 6} NOTE #4 INDICATES ALL CONDUCTORS MUST BE #12. |
| CIRCUITS 22 AND 24 ARE LISTRD AS #15. CORRELATE SAME. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |