Plan Review Notes For Permit 07120574
Permit Number 07120574
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-08 16:43:492004 W/2007 REVISIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE DESIGN PARAMETERS ON SHEET 1.1 INCORRECTLY LIST
 THE BUILDING AS OPENED. THE BUILDING IS ENCLOSED.
 PLEASE CORRECT. SEE ASCE 7-02 FOR DEFINITIONS OF OPEN
 AND ENCLOSED STRUCTURES.
  
 3) SHOW COMPLIANCE WITH FBC EXISTING BUILDINGS SECTION
 604.4.3 FOR SMOKE ALARMS.
  
 4) ON SHEET 1.2, DETAIL D SPECIFIES (3) ANCHOR BOLTS
 AND A 12" X 12" BASE PLATE. HOWEVER DETAILS A, B AND C
 SPECIFY (4) ANCHOR BOLTS AND A 10" X 10" BASE PLATE.
 PLEASE CLARIFY. FBC 106.1.1* CITY AMENDMENTS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]