Notes |
Date |
Text |
2008-01-08 16:43:49 | 2004 W/2007 REVISIONS | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) THE DESIGN PARAMETERS ON SHEET 1.1 INCORRECTLY LIST | | THE BUILDING AS OPENED. THE BUILDING IS ENCLOSED. | | PLEASE CORRECT. SEE ASCE 7-02 FOR DEFINITIONS OF OPEN | | AND ENCLOSED STRUCTURES. | | | | 3) SHOW COMPLIANCE WITH FBC EXISTING BUILDINGS SECTION | | 604.4.3 FOR SMOKE ALARMS. | | | | 4) ON SHEET 1.2, DETAIL D SPECIFIES (3) ANCHOR BOLTS | | AND A 12" X 12" BASE PLATE. HOWEVER DETAILS A, B AND C | | SPECIFY (4) ANCHOR BOLTS AND A 10" X 10" BASE PLATE. | | PLEASE CLARIFY. FBC 106.1.1* CITY AMENDMENTS. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|