Date |
Text |
2008-02-04 16:34:11 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED 2ND TIME: |
| |
| NOTE: THERE IS A PLAN REVIEW COMMENT FROM THE PREVIOUS |
| REVIEW THAT STILL NEEDS TO BE ADDRESSED. |
| |
| 1. **RESPONSE NOTED, HOWEVER THE RESUBMITTED SANITARY |
| RISER DIAGRAM IS NOT COMPLIANT PER *905.3, REFERENCE |
| NOTE**SHEET A-3 PLUMBING PLAN AND SANITARY RISER |
| DIAGRAM: VENT REQUIRED FOR THE SHOWER PER THE |
| FOLLOWING. |
| |
| 901.2.1 VENTING REQUIRED. |
| EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN |
| ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| THIS CHAPTER. |
| |
| **NOTE: THE RESUBMITTED SANITARY RISER DIAGRAM IS |
| INDICATING A HORIZONTAL DRY VENT AND IS NOT COMPLIANT. |
| PER FBC, PLUMBING SECTION *905.3 VENT CONNECTION TO |
| DRAINAGE SYSTEM. |
| EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| PIPE. |
| |
| **THE INDICATED VENT ON THE DRAWINGS DOES NOT CONNECT |
| ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. |
| PLEASE REFERENCE FIGURE 905.3 VENT CONNECTIONS |
| INDICATING ACCEPTABLE AND UNACCEPTABLE VENT CONNECTIONS |
| ATTACHED TO THESE PLUMBING COMMENTS. |
| |
| 2. **OK, COMMENT ADDRESSED** |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |