Plan Review Notes
Plan Review Notes For Permit 07120567
Permit Number 07120567
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-01-25 10:40:55*****DENIED*****
  
  
 1.NO ELECTRICAL CONDUITS SHALL ENTER ANY OF THE
 REQUIRED EXIT STAIRTOWERS.PLEASE PROVIDE A NOTE ON
 THE PLANS THAT NO CONDUITS SHALL BE CHASED THROUGH ANY
 EXIT STAIRTOWER EITHER VERTICALLY OR HORIZONTALLY.
  
 2.ANY PROPOSED INSTALLATION OF EQUIPMENT SHALL NOT
 INTERFERE WITH ANY EXISTING FIRE PROTECTION SYSTEMS OR
 DEVICES.
  
 3.ANY EQUIPMENT INSTALLED ON THE ROOF SHALL NOT
 INTERFERE ANY STANDPIPE ROOF MANIFOLDS.
  
 4.ALL CONSTRUCTION, DEMOLITION, AND RENOVATION WORK
 TO COMPLY WITH NFPA 241.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW