2007-12-31 10:31:06****************PROVISO****************
 A} PROTECTION FOR THE DOCK HOSE BIBBS REQUIRED PER THE
 FOLLOWING.
 608.15.4.2 HOSE CONNECTIONS.
 SILLCOCKS, HOSE BIBBS, WALL HYDRANTS AND OTHER OPENINGS
 WITH A HOSE CONNECTION SHALL BE PROTECTED BY AN
 ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM BREAKER OR A
 PERMANENTLY ATTACHED HOSE CONNECTION VACUUM BREAKER.
  
 B} NOTE: THE INDICATED SLEEVE UNDER STREET BY OTHERS
 REQUIRES A "RIGHT OF WAY PERMIT". PLEASE CONTACT WINDEL
 G. PALMER, UTILITIES ENGINEER PROJECT COORDINATOR,
 ENGINEERING SERCICES DEPARTMENT. PHONE: (561) 494-1040
 EXT:1086, FOR INFORMATION ABOUT THIS PERMIT.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731