2008-02-06 07:36:282004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) THE DESIGN PRESSURES FOR THE CASEMENT WINDOWS
 (CIRCLED ON PAGE 4 OF NOA 05-1129.09 ARE FOR 3/16"
 ANNEALED GLASS) ARE + & - 40 PSF. THE PLANS SUBMITTED
 SPECIFY + 35 & - 47.2AS THE REQUIRED DESIGN PRESSURES
 FOR THESE WINDOWS. THE NEGATIVE PRESSURE OF THE
 SPECIFIED PRODUCT IS NOT ADEQUATE. PLEASE CORRECT. SEE
 FBC R301.2.1.
  
 2) SUBMIT 2 COPIES OF THE SCOPE OF WORK DOCUMENT OR
 LIST THE SCOPE OF WORK ON THE DRAWINGS.
  
 3) SHOW COMPLIANCE WITH FBC EXISTING BUILDING SECTION
 604.4.3 FOR SMOKE ALARMS.
  
 4) THE DRAWINGS SPECIFY THE 2004 FBC WITH 2006
 REVISIONS. THE CORRECT CODE FOR THIS PROJECT IS THE
 2004 FBC WITH 2007 REVISIONS. PLEASE CORRECT.
  
 5) ADDRESS COMMENTS OF OTHER TRADES.
  
  