Plan Review Notes
Plan Review Notes For Permit 07120532
Permit Number 07120532
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-23 14:57:21** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE
 STATED ON PLANS FOR MINIMUM DESIGN.
 2005 NFPA-70
 2002 NFPA-72
 ** FBC 2004 W/2007 REVISIONS (NOTED BY OTHER TRADES)
  
 2) NOTE: PLEASE SUBMIT A COMPLETE PLAN INCLUDING PANEL
 SCHEDULE, RISER, LOAD CALCULATIONS ETC FOR NEW SCOPE OF
 WORK.
 PLEASE INDICATE THE NEW DEDICATED CIRCUITS WHICH ARE
 REQUIRED PER 210.52, 210.11, 220.
 AS SCOPE OF WORK IS NOT SHOWN DETERMINATION OF MINIMUM
 ELECTRICAL CODE COMPLIANCE CAN BE DONE AT THIS TIME.
 2005 NEC.
 PLEASE SEE 210.70, LS 101 7.8 FOR CONTROLS OF NEW
 LIGHTING WHICH IS STATED ON SCOPE.
 PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS.
 PLEASE B SURE TO LIST ALL OVER CURRENT PROTECTION
 DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC
 408.4, 240.4, 310.16 ETC
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12
 AWG.
  
 4) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING
 DWELLING SLEEPING ROOMS PER FBC R313 AND NFPA-72
 11.5.1.1.1, 11.8.3
 PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING
 DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE
 CURRENT VERSION OF NFPA-72 11.5.1.1.1 AND 11.8.3 OR NEW
 TO BE INSTALLED.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECTS FOR A/C
 CONDENSING UNIT AND AH UNITPER 440.11.
 PLEASE ALSO SEE THE MISSING GFI PER 210.8, 210.63.
  
 7) NOTE: PLEASE SHOW LAYOUT OF NEW PROPOSED KITCHEN
 CABINETS SHOWING KITCHEN COUNTER SPACE GFI RECEPTACLES
 NEW MEETING CODE OR EXISTING MEETING MINIMUM CODE PER
 210.52B1, 210.52C1-5, 210.8A6.
  
 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED
 LIGHTING PER FBC 13-606.ABC.1.2.4
  
 9) NOTE: PLAN TITLE BLOCKS MENTIONS DESIGNER FOR
 RESIDENTIAL AND COMMERCIAL WORK. PLEASE SEE FLORIDA
 STATUTES 481.229 AS SCOPE OF WORK ON COMMERCIAL
 PROJECTS REQUIRE LICENSE UNDER ARCHITECTURAL
 REGULATIONS. PLEASE COMPLETE TITLE BLOCKS WITH REQUIRED
 LICENSING PER FAC 61G1-16.004, FS 481.219.
 PLANS WILL BE REQUIRED TO BE SIGNED, DATED AND SEALED
 BY ANY LICENSED DESIGNER OF RECORD. FS 481.221.
  
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]