2007-12-23 14:57:21 | ** DENIEDREVIEW ** |
| |
| |
| 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE |
| STATED ON PLANS FOR MINIMUM DESIGN. |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| ** FBC 2004 W/2007 REVISIONS (NOTED BY OTHER TRADES) |
| |
| 2) NOTE: PLEASE SUBMIT A COMPLETE PLAN INCLUDING PANEL |
| SCHEDULE, RISER, LOAD CALCULATIONS ETC FOR NEW SCOPE OF |
| WORK. |
| PLEASE INDICATE THE NEW DEDICATED CIRCUITS WHICH ARE |
| REQUIRED PER 210.52, 210.11, 220. |
| AS SCOPE OF WORK IS NOT SHOWN DETERMINATION OF MINIMUM |
| ELECTRICAL CODE COMPLIANCE CAN BE DONE AT THIS TIME. |
| 2005 NEC. |
| PLEASE SEE 210.70, LS 101 7.8 FOR CONTROLS OF NEW |
| LIGHTING WHICH IS STATED ON SCOPE. |
| PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS. |
| PLEASE B SURE TO LIST ALL OVER CURRENT PROTECTION |
| DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC |
| 408.4, 240.4, 310.16 ETC |
| FBC 106.3.5.4 |
| |
| 3) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED |
| DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12 |
| AWG. |
| |
| 4) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING |
| DWELLING SLEEPING ROOMS PER FBC R313 AND NFPA-72 |
| 11.5.1.1.1, 11.8.3 |
| PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING |
| DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE |
| CURRENT VERSION OF NFPA-72 11.5.1.1.1 AND 11.8.3 OR NEW |
| TO BE INSTALLED. |
| |
| 6) NOTE: PLEASE SEE MISSING DISCONNECTS FOR A/C |
| CONDENSING UNIT AND AH UNITPER 440.11. |
| PLEASE ALSO SEE THE MISSING GFI PER 210.8, 210.63. |
| |
| 7) NOTE: PLEASE SHOW LAYOUT OF NEW PROPOSED KITCHEN |
| CABINETS SHOWING KITCHEN COUNTER SPACE GFI RECEPTACLES |
| NEW MEETING CODE OR EXISTING MEETING MINIMUM CODE PER |
| 210.52B1, 210.52C1-5, 210.8A6. |
| |
| 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED |
| LIGHTING PER FBC 13-606.ABC.1.2.4 |
| |
| 9) NOTE: PLAN TITLE BLOCKS MENTIONS DESIGNER FOR |
| RESIDENTIAL AND COMMERCIAL WORK. PLEASE SEE FLORIDA |
| STATUTES 481.229 AS SCOPE OF WORK ON COMMERCIAL |
| PROJECTS REQUIRE LICENSE UNDER ARCHITECTURAL |
| REGULATIONS. PLEASE COMPLETE TITLE BLOCKS WITH REQUIRED |
| LICENSING PER FAC 61G1-16.004, FS 481.219. |
| PLANS WILL BE REQUIRED TO BE SIGNED, DATED AND SEALED |
| BY ANY LICENSED DESIGNER OF RECORD. FS 481.221. |
| |
| |
| *** IMPORTANT** |
| AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, |
| THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| CAN NOT BE MADE AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |