Plan Review Notes
Plan Review Notes For Permit 07120532
Permit Number 07120532
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-08 10:28:592004 FBC W/2007 REVISIONS
  
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) THE DESIGN PRESSURES FOR THE CASEMENT WINDOWS
 (CIRCLED ON PAGE 4 OF NOA 05-1129.09 ARE FOR 3/16"
 ANNEALED GLASS) ARE + & - 40 PSF. THE PLANS SUBMITTED
 SPECIFY + 35 & - 47.2AS THE REQUIRED DESIGN PRESSURES
 FOR THESE WINDOWS. THE NEGATIVE PRESSURE OF THE
 SPECIFIED PRODUCT IS NOT ADEQUATE. PLEASE CORRECT. SEE
 FBC R301.2.1.
  
 2) THE STORM PANEL INSTALLATION SCHEDULE IS INCORRECT.
 PLEASE CLARIFY THE ANCHOR TYPE. WILL TAPCONS BE USED OR
 ELCO PANELMATES. IF TAPCONS ARE USED AND THE EDGE
 DISTANCE IS LESS THAN 3-1/2" THE ANCHOR SPACING IN THE
 TABLES ARE REQUIRED TO BE REDUCED BY THE FACTORS IN THE
 TABLE AT THE BOTTOM OF SHEET 7 OF DRAWING # 05-270. THE
 SPANS ARE INCORRECT. IF THE PANELS ARE INSTALLED
 VERTICALLY THE SPAN IS THE OPENING HEIGHT PLUS THE EDGE
 DISTANCE. ON SHEET 3 OF DRAWING # 05-270 SECTIONS 2 AND
 2A ARE CIRCLED. USE THESE TO DETERMINE THE ANCHOR
 SPACING IN THE TABLE ON SHEET 7.
  
 3) SHOW COMPLIANCE WITH FBC EXISTING BUILDING SECTION
 604.4.3 FOR SMOKE ALARMS.
  
 4) ADDRESS COMMENTS OF OTHER TRADES.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]