Plan Review Notes For Permit 07120532 |
Permit Number |
07120532 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-01-08 10:28:59 | 2004 FBC W/2007 REVISIONS | | | | LEVEL 2 ALTERATION | | | | DENIED BY BUILDING | | | | 1) THE DESIGN PRESSURES FOR THE CASEMENT WINDOWS | | (CIRCLED ON PAGE 4 OF NOA 05-1129.09 ARE FOR 3/16" | | ANNEALED GLASS) ARE + & - 40 PSF. THE PLANS SUBMITTED | | SPECIFY + 35 & - 47.2AS THE REQUIRED DESIGN PRESSURES | | FOR THESE WINDOWS. THE NEGATIVE PRESSURE OF THE | | SPECIFIED PRODUCT IS NOT ADEQUATE. PLEASE CORRECT. SEE | | FBC R301.2.1. | | | | 2) THE STORM PANEL INSTALLATION SCHEDULE IS INCORRECT. | | PLEASE CLARIFY THE ANCHOR TYPE. WILL TAPCONS BE USED OR | | ELCO PANELMATES. IF TAPCONS ARE USED AND THE EDGE | | DISTANCE IS LESS THAN 3-1/2" THE ANCHOR SPACING IN THE | | TABLES ARE REQUIRED TO BE REDUCED BY THE FACTORS IN THE | | TABLE AT THE BOTTOM OF SHEET 7 OF DRAWING # 05-270. THE | | SPANS ARE INCORRECT. IF THE PANELS ARE INSTALLED | | VERTICALLY THE SPAN IS THE OPENING HEIGHT PLUS THE EDGE | | DISTANCE. ON SHEET 3 OF DRAWING # 05-270 SECTIONS 2 AND | | 2A ARE CIRCLED. USE THESE TO DETERMINE THE ANCHOR | | SPACING IN THE TABLE ON SHEET 7. | | | | 3) SHOW COMPLIANCE WITH FBC EXISTING BUILDING SECTION | | 604.4.3 FOR SMOKE ALARMS. | | | | 4) ADDRESS COMMENTS OF OTHER TRADES. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|