Date |
Text |
2007-12-26 10:10:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE PROPOSED NEW GREASE INTERCEPTOR SHALL BE |
| APPROVED PER THE FOLLOWING. |
| PER MUNICIPAL CODE ARTICLE III SECTION 90-124, THE |
| EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED AND |
| LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: |
| (561) 822-2272, E-MAIL: [email protected] OR CLAVIN |
| WILLIAMS, PHONE: (561) 822-2284, E-MAIL: |
| [email protected]. THEIR FAX NUMBER IS (561) 822-2287. |
| NOTE: WRITTEN APPROVAL IS REQUIRED OF THE |
| EXISTING/PROPOSED GREASE INTERCEPTOR FROM ENVIRONMENTAL |
| COMPLIANCE BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2. SHEET 1.0A, GREASE TRAP DETAIL: THE INLET PIPING |
| SHALL EXTEND 24" BELOW THE SURFACE. PER *1003.5.3, |
| INLET AND OUTLET PIPING. |
| |
| 3. SHEET 1.0A, GREASE TRAP DETAIL: MINIMUM SIZE OF |
| MANHOLE WITH LID SHALL BE 24". PER APPROVED "THE CITY |
| OF WEST PALM BEACH, STANDARD GREASE TRAP DETAIL". |
| **PLEASE REFERENCE THE APPROVED "THE CITY OF WEST PALM |
| BEACH, STANDARD GREASE TRAP DETAIL" ATTACHED TO THESE |
| PLUMBING COMMENTS FOR REFERENCE FOR THE RESUBMITTAL. |
| |
| 4. SHEET 1.0A, SANITARY ISOMETRIC RISER DIAGRAM: THE |
| INLET AND OUTLET PIPING SHALL HAVE A TWO-WAY CLEANOT |
| TEE INSTALLED. PER *1003.5.3, INLET AND OUTLET PIPING. |
| **THE INLET PIPING IS MISSING THE REQUIRED TWO-WAY |
| CLEANOUT AND THE LOCATION OF THE OUTLET TWO-WAY |
| CLEANOUT SHOULD BE CLOSER TO THE GREASE TRAP. |
| |
| 5. PER FS 713.13 (1) THRU (6): A NOTICE OF |
| COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY |
| COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE |
| HWY., BEFORE A PERMIT CAN BE ISSUED. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |