2007-12-22 14:03:09** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE NO ELECTRICAL PLANS WERE SUBMITTED
 FOR APPLIED SCOPE OF WORK.
 PLEASE SEE NO LIGHTING, CIRCUITS, ETC WERE SHOWN.
 PLEASE SEE 225.31-225.39, 250.32.
 PLEASE PROVIDE LOCATION OF BRANCH CIRCUITS AND WHERE
 THEY ARE FED FROM ETC.
 ** AS NO ELECTRICAL SCOPE IS SHOWN AND AN ELECTRICAL
 PERMIT IS BEING APPLIED FOR PLEASE SUBMIT INFORMATION
 FOR CODE REVIEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.