Date Text
2008-02-13 10:22:10***DENIED***
  
 SOME COMMENTS FROM PREVIOUS REVIEW NEED ADDRESSING:
  
 1) OK
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) PLANS ILLUSTRATE EXITING THROUGH A WORK STATION
 AREA. PLEASE CLARIFY HOW THIS WOULD BE ALLOWED NFPA
 101,SEC. 7.5.2.1 AND WHAT PREVENTS OBSTRUCTION OF
 REQUIRED MEANS OF EGRESS.
  
 4) OK
  
 5) ADDRESSING (SUITE CHARACTERS) SHALL COMPLY WITH CITY
 OF WEST PALM BEACH REQUIREMENTS FOR COMMERCIAL
 BUILDINGS AND BE CLEAR AND VISIBLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL