Date |
Text |
2008-02-04 08:47:14 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE SEE THE ELECTRICAL PLANS CONTAIN A LOT |
| OF INFORMATION WHICH IS VERY FAINT AND NOT EASILY READ. |
| PLEASE SEE THERE ARE SEVERAL WALLS AND MOST IMPORTANTLY |
| THE ROOM AND AREA DESIGNATIONS WHICH CAN NOT BE READ. |
| IN ORDER TO REVIEW MANY ITEMS FOR OTHER CODE SECTIONS |
| PLEASE REPRINT SHEETS SO A COMPLETE REVIEW CAN BE |
| DONE. |
| FBC ADMIN SECTION 106.1.1, 106.1.3 |
| |
| 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND WITH ALL |
| FIXTURES WHICH ARE SHOWN ON PLANS. PLEASE BE SURE TO |
| COORDINATE ALL FIXTURES WITH THE LIGHTING ALLOWANCES. |
| FOR EXAMPLE: PLEASE SEE STORAGE ROOM 209 FIXTURE IS NOT |
| FIGURED, IS NOT ON LEGEND ETC. |
| THIS IS ONE EXAMPLE. |
| FBC 13-415.1.ABC.1.1, .1.2, 13-415.2 |
| |
| 3) NOTE: PLEASE SEE THE RESPONSE WITH RESPECT TO USE OF |
| METHOD *A* WITHIN A TENANT SPACE DOES NOT MEET *WHOLE |
| BUILDING*. |
| PLEASE KNOW THIS WAS CONFIRMED WITH THE FLORIDA |
| BUILDING COMMISSION BY THIS OFFICE ON SEPTEMBER 26TH, |
| 2007. PLEASE KNOW THE METHOD *A* INPUT DATA REPORT DOES |
| NOT COORDINATE WITH PLANS AT THIS TIME IN EITHER CASE. |
| ADDRESS ON METHOD *A* STILL SHOWN FOR BOCA LOCATION. |
| FOR EXAMPLE: 88W LUMINAIRE, YET FIXTURE LEGEND DOES NOT |
| INCLUDE ANY OF THESE. |
| PLEASE SEE THE REST OF THIS COMMENT WITH RESPECT TO |
| *METHOD *A* AND CALCULATIONS NEEDED. |
| |
| PLEASE SEE THE LIGHTING POWER ALLOWANCES REQUIRED PER |
| 13-415.2. THE PLANS DO SHOW A TABLE FOR METHOD *B* |
| SPACE BY SPACE, YET THERE IS INFORMATION STILL NEEDED. |
| THE WAY THIS IS SET UP AND SHOWN IS OK, ONLY NEEDS SOME |
| COORDINATION AND COMPLETION OF SOME ADDITIONAL |
| INFORMATION. |
| PLEASE SEE THERE ARE SEVERAL LOCATIONS (ROOMS) WHERE |
| THE ALLOWANCE IS OVER THE PERMITTED ALLOWANCE. AS THERE |
| IS NO TOTAL FOR DESIGN AND NO TOTAL FOR ALLOWANCE, |
| PLEASE COMPLETE TABLE FOR THESE. |
| |
| |
| 4) NOTE: PLEASE SEE THE FLOOR LAYOUTS ON ELECTRICAL |
| PLANS ARE NOT THE SAME AS THAT OF THE LIFE SAFETY OR |
| ARCHITECTURAL PLANS. |
| PLEASE SEE FOR EXAMPLE: WALL ON ELECTRICAL PLANS FOR |
| GYM IS MISSING WHEN SHOWN ON OTHER PLANS. |
| PLEASE SEE FOR EXAMPLE: EGRESS PATH ON ELECTRICAL PLANS |
| AT CUBICLE IS SMALLER THAN THAT OF LIFE SAFETY PLANS. |
| PLEASE COORDINATE. FBC ADMIN SECTION 106.1.2 FOR |
| COORDINATION. |
| |
| 5) NOTE: PLEASE BE SURE TO INCLUDE SUITE/UNIT NUMBERS |
| ON TITLE BLOCKS ONCE DETERMINED. THIS IS ONCE TENANT |
| SPACE NOT FOUR AS STATED ON PERMIT APPLICATION. |
| THIS INFORMATION WAS SENT TO ADDRESSING REVIEWER. |
| FAC 61G15-23.002, FAC 61G1-16.004, FBC ADMIN SECTION |
| 106.5 ETC |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2008-02-01 19:11:36 | 2008-02-01 19:11:36 |
| |
| IN ELEC FOR ERVIEW, NOTES TO FOLLOW. |