Plan Review Notes
Plan Review Notes For Permit 07120492
Permit Number 07120492
Review Stop B
Sequence Number 2
Notes
Date Text
2008-02-05 12:10:59BUILDING PLAN REVIEW
 PERMIT: 07120492
 ADD: 2475 ? MERCER AVE
 CONT: SEAL-TITE
 TEL: (561)346-8191
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 2-5-08
  
 1A)OK
  
 1B) OK
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)OK
 4)OK
 5)OK
  
 **NOTED: HOWEVER, DETAIL #5 ON SHEET A-3 SHOWS NO
 CHANGE. THE DOORS ARE IN THE SAME LOCATION.
 6)ON SHEET A-3 DETAIL #5 THE GALLEY KITCHEN SINK
 SHALL MEET THE FOLLOWING REQUIREMENTS: A. 11-4.24.3
 KNEE CLEARANCE / B. 11-4.24.4 SINK DEPTH /////
 /C.11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH)
 REQUIRED MAXIMUM 19 INCHES UNDERNEATH THE SINK. NO
 CABINET DOORS ALLOWED IN THE CLEAR FLOOR SPACE. / D
 11-4.24.6 EXPOSE PIPES & SURFACES AND E. 11-4.24.7
 FAUCETS
  
 **NOTED HOWEVER, SHOWER STALLS THAT ARE 30 INCHES BY 60
 INCHES MINIMUM SHALL NOT HAVE CURBS. 11-4-21.7**
 7)THE SHOWER STALL SHALL MEET THE REQUIREMENTS OF FBC
 11-4.21. PROVIDE ELEVATION DETAIL DRAWINGS SHOWING ALL
 DIMENSIONS AND ELEVATIONS FOR THE SEAT 11-4.21.3/ GRAB
 BARS 11-4.21.4 / CONTROLS 11-4.21.5 / SHOWER UNIT
 11-4.21.6 / CURBS 11-4-21.7 / SHOWER ENCLOSURE
 11-4.21.8. THE CLEAR FLOOR SPACE AND WHEELCHAIR TURNING
 SPACE SHALL ALSO BE INDICATED ON THE PLANS.
  
 8)OK
 9)OK
 10)OK
  
 **NEW**HOW CAN A PROJECT IN THE CITY OF WEST PALM BEACH
 HAVE A BOCA RATON ADDRESS? ALL PAGES SHALL HAVE THE
 SAME ADDRESS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE WORK
 PROPOSED. FBC 106.1.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  