2008-02-05 12:10:59 | BUILDING PLAN REVIEW |
| PERMIT: 07120492 |
| ADD: 2475 ? MERCER AVE |
| CONT: SEAL-TITE |
| TEL: (561)346-8191 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 2ND |
| ACTION: DENIED |
| 2-5-08 |
| |
| 1A)OK |
| |
| 1B) OK |
| |
| 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 REVISIONS. |
| |
| 2)OK |
| 4)OK |
| 5)OK |
| |
| **NOTED: HOWEVER, DETAIL #5 ON SHEET A-3 SHOWS NO |
| CHANGE. THE DOORS ARE IN THE SAME LOCATION. |
| 6)ON SHEET A-3 DETAIL #5 THE GALLEY KITCHEN SINK |
| SHALL MEET THE FOLLOWING REQUIREMENTS: A. 11-4.24.3 |
| KNEE CLEARANCE / B. 11-4.24.4 SINK DEPTH ///// |
| /C.11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH) |
| REQUIRED MAXIMUM 19 INCHES UNDERNEATH THE SINK. NO |
| CABINET DOORS ALLOWED IN THE CLEAR FLOOR SPACE. / D |
| 11-4.24.6 EXPOSE PIPES & SURFACES AND E. 11-4.24.7 |
| FAUCETS |
| |
| **NOTED HOWEVER, SHOWER STALLS THAT ARE 30 INCHES BY 60 |
| INCHES MINIMUM SHALL NOT HAVE CURBS. 11-4-21.7** |
| 7)THE SHOWER STALL SHALL MEET THE REQUIREMENTS OF FBC |
| 11-4.21. PROVIDE ELEVATION DETAIL DRAWINGS SHOWING ALL |
| DIMENSIONS AND ELEVATIONS FOR THE SEAT 11-4.21.3/ GRAB |
| BARS 11-4.21.4 / CONTROLS 11-4.21.5 / SHOWER UNIT |
| 11-4.21.6 / CURBS 11-4-21.7 / SHOWER ENCLOSURE |
| 11-4.21.8. THE CLEAR FLOOR SPACE AND WHEELCHAIR TURNING |
| SPACE SHALL ALSO BE INDICATED ON THE PLANS. |
| |
| 8)OK |
| 9)OK |
| 10)OK |
| |
| **NEW**HOW CAN A PROJECT IN THE CITY OF WEST PALM BEACH |
| HAVE A BOCA RATON ADDRESS? ALL PAGES SHALL HAVE THE |
| SAME ADDRESS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE WORK |
| PROPOSED. FBC 106.1.1. |
| |