Plan Review Notes
Plan Review Notes For Permit 07120492
Permit Number 07120492
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-27 15:58:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET G-1 INDICATES OCCUPANCY AS "B" PER SECTION
 *403, MINIMUM PLUMBING FACILITIES, TABLE *403.1 FOR
 OCCUPANCY "B" A DRINKING FOUNTAIN IS REQUIRED AND SHALL
 BE COMPLIANT TO CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 PER THE FOLLOWING.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2. SHEET P-1 SANITARY RISER DIAGRAM: SIZE ALL TRAPS
 PER SECTION *106.3.5.1.3 PLUMBING. **TRAP SIZES MISSING
 FOR P-2H AND P-4 FIXTURES.
  
 3. SHEET A-3 DETAIL #2: CLEARLY INDICATE IN THE
 RESUBMITTED DETAIL WHERE THE 27" MINIMUM KNEE CLEARANCE
 IS LOCATED AS WELL AS THE 6" AND 9" TOE CLEARANCE WITH
 THE ANGLE COMPLIANT TO FIGURE 31. PLEASE REFERENCE
 FIGURE 31, ATTACHED TO THESE PLUMBING COMMENTS WITH THE
 HIGHLIGHTED AREAS OF QUESTION.
  
 4. SHEET A-3 TYPICAL RESTROOM ACCESSORY LOCATION:
 PLEASE CORREC THE MINIMUM AND MAXIMUM HANDI CAP WATER
 CLOSET HEIGHT TO BE 17"-19". PER *11-4.16.3, HEIGHT.
  
 5. SHEET A-1 FLOOR PLAN ROOM #212, GYM IS INDICATING A
 SHOWER. THE PROPOSED SHOWER MUST BE COMPLIANT TO
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE. PLEASE CORRECT
 SHEET A-5 SHOWER DETAIL #10 TO COMPLY WITH THE
 FOLLOWING.
  
 11-4.21 SHOWER STALLS.(ELEVATION DETAIL REQUIRED)
  
 11-4.21.1 GENERAL. ACCESSIBLE SHOWER STALLS SHALL
 COMPLY WITH SECTION11-4.21.
  
 11-4.21.2 SIZE AND CLEARANCES.
 EXCEPT AS SPECIFIED IN SECTION 11-9.1.2 , SHOWER STALL
 SIZE AND CLEAR FLOOR SPACE SHALL COMPLY WITH FIGURE 35
 (A) OR FIGURE 35 (B). THE SHOWER STALL IN FIGURE 35 (A)
 SHALL BE 36 INCHES BY 36 INCHES (915 MM BY 915 MM).
 SHOWER STALLS REQUIRED BY SECTION 11-9.1.2 SHALL COMPLY
 WITH FIGURE 57 (A) OR FIGURE 57 (B). THE SHOWER STALL
 IN FIGURE 35 (B) WILL FIT INTO THE SPACE REQUIRED FOR A
 BATHTUB.
  
 11-4.21.3 SEAT.
 A SEAT SHALL BE PROVIDED IN SHOWER STALLS 36 INCHES BY
 36 INCHES (915 MM BY 915 MM) AND SHALL BE AS SHOWN IN
 FIGURE 36 . THE SEAT SHALL BE MOUNTED 17 INCHES TO 19
 INCHES (430 MM TO 485 MM) FROM THE BATHROOM FLOOR AND
 SHALL EXTEND THE FULL DEPTH OF THE STALL. IN A 36-INCH
 BY 36-INCH (915 MM BY 915 MM) SHOWER STALL, THE SEAT
 SHALL BE ON THE WALL OPPOSITE THE CONTROLS. WHERE A
 FIXED SEAT IS PROVIDED IN A 30-INCH BY 60-INCH MINIMUM
 (760 MM BY 1525 MM) SHOWER STALL, IT SHALL BE A FOLDING
 TYPE AND SHALL BE MOUNTED ON THE WALL ADJACENT TO THE
 CONTROLS AS SHOWN IN FIGURE 57 . THE STRUCTURAL
 STRENGTH OF SEATS AND THEIR ATTACHMENTS SHALL COMPLY
 WITH SECTION 11-4.26.3 .
  
 11-4.21.4 GRAB BARS.
 GRAB BARS COMPLYING WITH SECTION 11-4.26 SHALL BE
 PROVIDED AS SHOWN IN FIGURE 37 .
  
 11-4.21.5 CONTROLS.
 FAUCETS AND OTHER CONTROLS COMPLYING WITH SECTION
 11-4.27.4 SHALL BE LOCATED AS SHOWN IN FIGURE 37 . IN
 SHOWER STALLS 36 INCHES BY 36 INCHES (915 MM BY 915
 MM), ALL CONTROLS, FAUCETS, AND THE SHOWER UNIT SHALL
 BE MOUNTED ON THE SIDE WALL OPPOSITE THE SEAT.
  
 11-4.21.6 SHOWER UNIT.
 A SHOWER SPRAY UNIT WITH A HOSE AT LEAST 60 INCHES
 (1525 MM) LONG THAT CAN BE USED BOTH AS A FIXED SHOWER
 HEAD AND AS A HAND-HELD SHOWER SHALL BE PROVIDED.
 EXCEPTION: IN UNMONITORED FACILITIES WHERE VANDALISM IS
 A CONSIDERATION, A FIXED SHOWER HEAD MOUNTED AT 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR MAY BE USED IN
 LIEU OF A HAND-HELD SHOWER HEAD.
  
 11-4.21.7 CURBS.
 IF PROVIDED, CURBS IN SHOWER STALLS 36 INCHES BY 36
 INCHES (915 MM BY 915 MM) SHALL BE NO HIGHER THAN ?
 INCH (13 MM). SHOWER STALLS THAT ARE 30 INCHES BY 60
 INCHES (760 MM BY 1525 MM) MINIMUM SHALL NOT HAVE
 CURBS.
  
 11-4.21.8 SHOWER ENCLOSURES.
 IF PROVIDED, ENCLOSURES FOR SHOWER STALLS SHALL NOT
 OBSTRUCT CONTROLS OR OBSTRUCT TRANSFER FROM WHEELCHAIRS
 ONTO SHOWER SEATS.
  
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 6. SHEET A-1 FLOOR PLAN ROOM #226, GALLEY KITCHEN IS
 INDICATING A SINK. THE PROPOSED SINK MUST BE COMPLIANT
 TO CHAPTER 11, FLORIDA ACCESSIBILITY CODE. PLEASE
 CORRECT SHEET A-3, DETAIL #5 TO COMPLY WITH THE
 FOLLOWING.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 7. SHEET A-5 DETAIL #1, PLEASE DELETE THE SINK FROM
 BUILT IN DESK DETAIL. THE DESKS DO NOT HAVE SINKS. PER
 *106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. SEE ELECTRICAL REVIEW NOTES #5 AND #8 AND CORRECT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved