2007-12-23 09:34:43 | ** DENIED** |
| |
| |
| 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE |
| NEEDED AS FOLLOWS |
| 2004 FBC W/2007 REVISIONS |
| 2005 NFPA-70 |
| 2003 NFPA-101(SHOWS 2006) |
| 2002 NFPA-72 (SHOWS 2007) |
| |
| 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS |
| LIGHTING CONTROLS ARE REQUIRED FOR ALL AREAS. FOR |
| EXAMPLE: PLEASE SEE ROOMS 209, 231, BATHROOM ETC |
| WITHOUT ANY CONTROLS. |
| PLEASE LIST MAXIMUM TIMES ON DEVICES. |
| |
| 3) NOTE: PLEASE SEE POSSIBLE COMMENTS FOR EGRESS |
| THROUGH WORK STATION CUBICLE FROM BUILDING AND FIRE |
| MARSHAL REVIEW. THIS WOULD AFFECT ELECTRICAL PLANS. |
| THIS IS NOTED FOR INFORMATION AT THIS TIME. |
| |
| 4) NOTE: PLEASE SEE THE ELECTRICAL PANELS AND LOCATION |
| SHOWN ARE NOT PERMITTED IN THE STORAGE ROOM. |
| 110.26, 240.24, 408.17 |
| |
| 5) NOTE: PLEASE SEE THE PACKAGE AS SUBMITTED CONTAINED |
| METHOD *A* CALCULATIONS FOR *WHOLE BUILDING*. THIS IS |
| NOT A WHOLE BUILDING. PLEASE ALSO SEE THESE SAME |
| CALCULATIONS ARE SHOWN WITH PROJECT LOCATED IN BOCA |
| RATON ON SOUTH FEDERAL HWY. |
| PLEASE KNOW AS ASSUMPTIONS WERE MADE UNDER THE BASE |
| BUILDING AND THIS IS NOT A WHOLE BUILDING PLEASE |
| VERIFY. PLEASE KNOW THAT IN ANY CASETHE INPUT DATA |
| REPORT AS SUBMITTED DOES NOT COORDINATE WITH PLANS FOR |
| NUMBER OF LIGHT FIXTURES, CONTROLS, AND WATTAGES. |
| PLEASE SEE THE PLANS DO INDICATE THE LIGHTING |
| PERFORMANCE CALCULATIONS HOWEVER AS THESE SHOW TABLE |
| *C* BEING PERFORMED, THE TOTAL WATTS PER SQ FT IS |
| EXCEED BASED ON THE OFFICE NOTED AS 1.0 PER SQ FT. |
| PLEASE COMPLETE FIXTURE DESIGNATIONS ON PLANS WHICH |
| CORRELATE WITH THE FIXTURE LEGEND. |
| PLEASE BE SURE TO SEE 13-415.2 AND ADJUST CALCULATIONS |
| AS NEEDED. |
| |
| 6) NOTE: PLEASE VERIFY ROOM ON PLANS WHICH IS SHOWN AS |
| AN *IT* ROOM. THIS ROOM DOES NOT APPEAR TO CONFORM TO |
| 645.4 OF THE NEC. IF THIS IS AN IT ROOM PLEASE ADJUST |
| PLANS. IF THIS IS A SERVER ROOM PLEASE ADJUST |
| DESIGNATION. |
| |
| 7) NOTE: PLEASE SEE 422.1, 110.26, 240.24 ETC FOR OVER |
| CURRENT PROTECTION ON WHAT APPEARS TO BE A TANK-LESS |
| WATER HEATER. PLEASE KNOW IF THE DISCONNECT AS SHOWN |
| UNDER CABINET CONTAINS OVER CURRENT PROTECTION THIS |
| WILL BE REQUIRED TO BE RELOCATED. THIS IS A FIRE/LIFE |
| SAFETY HAZARD. |
| PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| UNIT. |
| 110.3, 90.7 |
| FBC 106.1.2 |
| |
| 8) NOTE: PLEASE SEE THE ADDRESS IS TO BE STATED ON |
| TITLE BLOCKS. (2475 MERCER AVE). |
| PLEASE KNOW ONCE A SUITE OR UNIT NUMBER HAS BEEN |
| GENERATED, THIS SHOULD ALSO BE PLACED ON PLANS. THIS |
| HAS BEEN ROUTED TO ADDRESSING FOR SUITE/UNIT |
| DETERMINATION. |
| |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |