2007-12-23 09:34:43** DENIED**
  
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101(SHOWS 2006)
 2002 NFPA-72 (SHOWS 2007)
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS
 LIGHTING CONTROLS ARE REQUIRED FOR ALL AREAS. FOR
 EXAMPLE: PLEASE SEE ROOMS 209, 231, BATHROOM ETC
 WITHOUT ANY CONTROLS.
 PLEASE LIST MAXIMUM TIMES ON DEVICES.
  
 3) NOTE: PLEASE SEE POSSIBLE COMMENTS FOR EGRESS
 THROUGH WORK STATION CUBICLE FROM BUILDING AND FIRE
 MARSHAL REVIEW. THIS WOULD AFFECT ELECTRICAL PLANS.
 THIS IS NOTED FOR INFORMATION AT THIS TIME.
  
 4) NOTE: PLEASE SEE THE ELECTRICAL PANELS AND LOCATION
 SHOWN ARE NOT PERMITTED IN THE STORAGE ROOM.
 110.26, 240.24, 408.17
  
 5) NOTE: PLEASE SEE THE PACKAGE AS SUBMITTED CONTAINED
 METHOD *A* CALCULATIONS FOR *WHOLE BUILDING*. THIS IS
 NOT A WHOLE BUILDING. PLEASE ALSO SEE THESE SAME
 CALCULATIONS ARE SHOWN WITH PROJECT LOCATED IN BOCA
 RATON ON SOUTH FEDERAL HWY.
 PLEASE KNOW AS ASSUMPTIONS WERE MADE UNDER THE BASE
 BUILDING AND THIS IS NOT A WHOLE BUILDING PLEASE
 VERIFY. PLEASE KNOW THAT IN ANY CASETHE INPUT DATA
 REPORT AS SUBMITTED DOES NOT COORDINATE WITH PLANS FOR
 NUMBER OF LIGHT FIXTURES, CONTROLS, AND WATTAGES.
 PLEASE SEE THE PLANS DO INDICATE THE LIGHTING
 PERFORMANCE CALCULATIONS HOWEVER AS THESE SHOW TABLE
 *C* BEING PERFORMED, THE TOTAL WATTS PER SQ FT IS
 EXCEED BASED ON THE OFFICE NOTED AS 1.0 PER SQ FT.
 PLEASE COMPLETE FIXTURE DESIGNATIONS ON PLANS WHICH
 CORRELATE WITH THE FIXTURE LEGEND.
 PLEASE BE SURE TO SEE 13-415.2 AND ADJUST CALCULATIONS
 AS NEEDED.
  
 6) NOTE: PLEASE VERIFY ROOM ON PLANS WHICH IS SHOWN AS
 AN *IT* ROOM. THIS ROOM DOES NOT APPEAR TO CONFORM TO
 645.4 OF THE NEC. IF THIS IS AN IT ROOM PLEASE ADJUST
 PLANS. IF THIS IS A SERVER ROOM PLEASE ADJUST
 DESIGNATION.
  
 7) NOTE: PLEASE SEE 422.1, 110.26, 240.24 ETC FOR OVER
 CURRENT PROTECTION ON WHAT APPEARS TO BE A TANK-LESS
 WATER HEATER. PLEASE KNOW IF THE DISCONNECT AS SHOWN
 UNDER CABINET CONTAINS OVER CURRENT PROTECTION THIS
 WILL BE REQUIRED TO BE RELOCATED. THIS IS A FIRE/LIFE
 SAFETY HAZARD.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 UNIT.
 110.3, 90.7
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE THE ADDRESS IS TO BE STATED ON
 TITLE BLOCKS. (2475 MERCER AVE).
 PLEASE KNOW ONCE A SUITE OR UNIT NUMBER HAS BEEN
 GENERATED, THIS SHOULD ALSO BE PLACED ON PLANS. THIS
 HAS BEEN ROUTED TO ADDRESSING FOR SUITE/UNIT
 DETERMINATION.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.