2007-12-20 16:58:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. NOTE: THERE IS NOT AN APPROVED GENERATOR FOR THIS
 RESIDENCE. THE REFERENCED GENERATOR FOR THE PROPOSED
 GAS SYSTEM WILL NEED A SEPERATE PERMIT. PLEASE
 REFERENCE THE RESIDENTIAL GENERATOR PLAN REVIEW
 REQUIREMENTS ATTACHED TO THESE GAS COMMENTS FOR
 INFORMATION REQUIRED FOR THAT PERMIT. A GAS PERMIT CAN
 NOT BE ISSUED UNTIL A GEN/RES PERMIT APPLICATION HAS
 BEEN APPLIED FOR AND APPROVED BY ZONING FOR THE
 GENERATOR LOCATION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE
 CORRESPONDING LENGTHS INDICATED AS REQUIRED. REFERENCE
 THE YELLOW HIGHLIGHTER WITH MISSING CORRESPONDING
 LENGTHS.
  
 3. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 **NOTE: THIS VALVE IS NOT ON THE SUBMITTED GAS RISER
 DIAGRAM. PLEASE INDICATE THIS REQUIRED VALVE ON THE
 RESUBMITTAL.
  
 4. NOTE: THE MP REGULATOR FOR THE POOL HEATER WILL
 NEED TO BE A MAXITROL 325-7L. THE INDICATED MAXITROL
 325-5AL FOR MAXIMUM INDIVIDUAL LOAD IS ONLY GOOD FOR
 300,000 BTU'S. THE POOL HEATER IS 400,000 BTU'S. PLEASE
 INDICATE THIS REQUIRED CHANGE ON THE RESUBMITTAL.
  
 5. SUBMIT TWO COPIES OF SURVEY OR SITE PLANS
 INDICATING THE PROPOSED LOCATION OF THE GENERATOR.
 INDICATE ALL DIMENSIONS FROM PROPERTY LINES AND ALL
 STRUCTURES OF THE PROPOSED GENERATOR.
  
 6. SUBMIT MANUFACTURE SHEETS FOR GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: SHEETS REQUIRED FOR THE GENERATOR, COOK TOP,
 STOVE, WATER HEATER, AND POOL HEATER TO VERIFY THE BTU
 LOAD AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL). FOR THE GENERATOR MANUFACTURER
 SETBACK RECOMMENDATIONS FROM STRUCTURES IS ALSO
 REQUIRED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON