2007-12-20 16:58:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. NOTE: THERE IS NOT AN APPROVED GENERATOR FOR THIS |
| RESIDENCE. THE REFERENCED GENERATOR FOR THE PROPOSED |
| GAS SYSTEM WILL NEED A SEPERATE PERMIT. PLEASE |
| REFERENCE THE RESIDENTIAL GENERATOR PLAN REVIEW |
| REQUIREMENTS ATTACHED TO THESE GAS COMMENTS FOR |
| INFORMATION REQUIRED FOR THAT PERMIT. A GAS PERMIT CAN |
| NOT BE ISSUED UNTIL A GEN/RES PERMIT APPLICATION HAS |
| BEEN APPLIED FOR AND APPROVED BY ZONING FOR THE |
| GENERATOR LOCATION. |
| |
| ******IMPORTANT INFORMATION****** |
| AS OF 8/25/06 GENERATOR (GEN/RES AND |
| GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| MATION AND GAS (OR DIESEL) INFORMATION |
| IS ALL SUBMITTED AT THE SAME TIME. THE |
| GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| FORMATION WILL BE ROUTED TOGETHER. THIS |
| WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| THE MANUFACTURER'S SPECI- |
| FICATIONS AND INSTALLATION INSTRUCTIONS) |
| ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| **NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE |
| CORRESPONDING LENGTHS INDICATED AS REQUIRED. REFERENCE |
| THE YELLOW HIGHLIGHTER WITH MISSING CORRESPONDING |
| LENGTHS. |
| |
| 3. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| **NOTE: THIS VALVE IS NOT ON THE SUBMITTED GAS RISER |
| DIAGRAM. PLEASE INDICATE THIS REQUIRED VALVE ON THE |
| RESUBMITTAL. |
| |
| 4. NOTE: THE MP REGULATOR FOR THE POOL HEATER WILL |
| NEED TO BE A MAXITROL 325-7L. THE INDICATED MAXITROL |
| 325-5AL FOR MAXIMUM INDIVIDUAL LOAD IS ONLY GOOD FOR |
| 300,000 BTU'S. THE POOL HEATER IS 400,000 BTU'S. PLEASE |
| INDICATE THIS REQUIRED CHANGE ON THE RESUBMITTAL. |
| |
| 5. SUBMIT TWO COPIES OF SURVEY OR SITE PLANS |
| INDICATING THE PROPOSED LOCATION OF THE GENERATOR. |
| INDICATE ALL DIMENSIONS FROM PROPERTY LINES AND ALL |
| STRUCTURES OF THE PROPOSED GENERATOR. |
| |
| 6. SUBMIT MANUFACTURE SHEETS FOR GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| **NOTE: SHEETS REQUIRED FOR THE GENERATOR, COOK TOP, |
| STOVE, WATER HEATER, AND POOL HEATER TO VERIFY THE BTU |
| LOAD AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| LABORATORY (NRTL). FOR THE GENERATOR MANUFACTURER |
| SETBACK RECOMMENDATIONS FROM STRUCTURES IS ALSO |
| REQUIRED. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |