2008-09-26 08:49:46 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| REVISION TO MECHANICAL PLAN M-1 |
| *** DENIED *** |
| |
| *AS NOTED IN LAST REVIEW 9/23/08* |
| |
| 1) THE LETTER SUBMITTED TO TERMINATE AGILE ENGINEERING |
| INC. CAN NOT BE EXCEPTED AS THE MECHANICAL CONTRACTOR |
| WAS NOT THE PERSON TO HIRER THEIR FIRM, SEE F.A.C. |
| 61G15-27. THE PROPERTY OWNER OR THE GENERAL CONTRACTOR |
| (PERSON WHO HIRED THE FIRM) NEEDS TO PREPARE AND SUBMIT |
| THE LETTER TO REMOVE THE ENGINEER. PLEASE HAVE THE JOB |
| ADDRESS AND PERMIT NUMBER ON THE LETTER WHEN |
| SUBMITTING. |
| |
| 2) TITLE BLOCK OF REVISED PLAN HAS THE WRONG LICENSE |
| NUMBER FOR SCOTT WEBSTER. |
| |
| 3) BE ADVISED "TROPICAL COOLING, INC." IS NOT A |
| LICENSED COMPANY, PLEASE CORRECT. |
| |
| 4) IF THIS PLAN IS TO BE SUBMITTED AFTER THE ABOVE |
| CORRECTIONS ARE MADE. THE RETURN AIR TRANSFER DUCT |
| (FLEX) FROM THE BEDROOM TO THE OFFICE NEEDS TO BE SIZED |
| ON THE PLAN, PER 2004 FBC/R M1602.4. |
| |