Plan Review Notes
Plan Review Notes For Permit 07120426
Permit Number 07120426
Review Stop M
Sequence Number 4
Notes
Date Text
2008-04-03 08:48:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 ** ENERGY CALCULATIONS FOR GUEST HOUSE HAVE NOT BEEN
 REVISED SO COMMENTS FROM LAST REVIEW STILL NEED TO BE
 ADDRESSED. **
  
 1) ENERGY CALCULATIONS FOR GUEST HOUSE LINE 12A SHOWS A
 34,200 BTU A/C SYSTEM BEING INSTALLED PLANS STATE A
 17,300 BTU SYSTEM IS BEING INSTALLED, PLEASE CORRECT
 ENERGY CAL'S.
  
 2) ENERGY CALCULATIONS FOR GUEST HOUSE SHOW UNDUCTED
 COOLING AND HEATING SYSTEM, PLANS SHOW A DUCTED SYSTEM,
 PLEASE CORRECT ENERGY CAL'S.
  
 3) ENERGY CALCULATION FOR THE GUEST HOUSE ARE TAKING
 THE CROSS VENTILATION CREDIT ON LINE 15. PLEASE SUBMIT
 CALCULATIONS FOR THE 12% BUILDING OPENINGS TO FLOOR
 AREA, SEE 2004 FBC 13-607.1.A.3.1.
  
 3A) ALSO ADD DETAIL FOR SCREEN DOORS TO BE INSTALLED AT
 DOOR OPENING IF THESE OPENINGS ARE INCLUDED IN THE
 ABOVE CALCULATIONS, PER 2004 FBC 13-607.1.A.3.1.
  
 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT.
 HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS
 VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION
 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE
 AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR
 AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN
 BEDROOMS.
 INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND
 DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL
 SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE
 VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1)
 MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES)
 TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE
 LOUVERS.
 THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM
 OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT
 MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE
 WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN
 ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED
 ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. WHERE
 WING WALLS ARE INCLUDED IN THE BUILDING DESIGN FOR
 VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN
 WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE
 ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE
 GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE
 OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A
 DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE
 WINDOW.
 NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH
 EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE
 COOLING MONTHS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]