2008-04-03 08:48:07 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| |
| ** ENERGY CALCULATIONS FOR GUEST HOUSE HAVE NOT BEEN |
| REVISED SO COMMENTS FROM LAST REVIEW STILL NEED TO BE |
| ADDRESSED. ** |
| |
| 1) ENERGY CALCULATIONS FOR GUEST HOUSE LINE 12A SHOWS A |
| 34,200 BTU A/C SYSTEM BEING INSTALLED PLANS STATE A |
| 17,300 BTU SYSTEM IS BEING INSTALLED, PLEASE CORRECT |
| ENERGY CAL'S. |
| |
| 2) ENERGY CALCULATIONS FOR GUEST HOUSE SHOW UNDUCTED |
| COOLING AND HEATING SYSTEM, PLANS SHOW A DUCTED SYSTEM, |
| PLEASE CORRECT ENERGY CAL'S. |
| |
| 3) ENERGY CALCULATION FOR THE GUEST HOUSE ARE TAKING |
| THE CROSS VENTILATION CREDIT ON LINE 15. PLEASE SUBMIT |
| CALCULATIONS FOR THE 12% BUILDING OPENINGS TO FLOOR |
| AREA, SEE 2004 FBC 13-607.1.A.3.1. |
| |
| 3A) ALSO ADD DETAIL FOR SCREEN DOORS TO BE INSTALLED AT |
| DOOR OPENING IF THESE OPENINGS ARE INCLUDED IN THE |
| ABOVE CALCULATIONS, PER 2004 FBC 13-607.1.A.3.1. |
| |
| 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT. |
| HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS |
| VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION |
| 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE |
| AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR |
| AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN |
| BEDROOMS. |
| INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND |
| DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL |
| SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE |
| VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1) |
| MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES) |
| TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE |
| LOUVERS. |
| THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM |
| OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT |
| MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE |
| WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN |
| ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED |
| ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. WHERE |
| WING WALLS ARE INCLUDED IN THE BUILDING DESIGN FOR |
| VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN |
| WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE |
| ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE |
| GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE |
| OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A |
| DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE |
| WINDOW. |
| NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH |
| EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE |
| COOLING MONTHS. |
| |