2008-03-03 16:02:33 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW |
| ARE STILL IN NEED OF ADDRESSING. |
| ** PLEASE ALSO SEE THAT MANY COMMENTS ARE NEW AS THESE |
| THINGS ARE JUST NOW BEING SHOWN. |
| PLEASE ALSO SEE THE RISER HAS NOW BEEN COMPLETELY |
| REVISED. SOME NEW COMMENTS HAVE NOW BEEN CREATED. MANY |
| ITEMS WHICH WERE CODE COMPLIANT ON PREVIOUS REVIEW HAVE |
| NOW COMPLETELY CHANGED AND ARE NOW NO LONGER CODE |
| COMPLIANT. |
| |
| 1) NOTE: PLEASE SEE THE RISER HAS BEEN REVISED REMOVING |
| A MAIN FOR GROUPING OF MAINS AS REQUIRED PER 230.72. ON |
| THE PREVIOUS REVIEW A COMMENT WAS MADE THAT A MAIN |
| DISCONNECT WAS MISSING AT THE MAIN HOUSE AS REQUIRED |
| PER 225.31-225.39. THIS MAIN WHICH WAS ON PREVIOUS |
| RISER GROUPED, HAS NOW BEEN MOVED. THE CODE REQUIRES |
| MAINS FOR SERVICE TO BE GROUPED PER 230.72 AND A MAIN |
| AT THE DETACHED STRUCTURE PER 225.31-225.39. PLEASE |
| ADJUST RISER. |
| |
| 2) NOTE: PLEASE ALSO CORRELATE RISER AND PLANS. THE |
| RISER SHOWS THE MAIN AT THE HOUSE AS 200AMPS AND THE |
| PLANS CLEARLY SHOW A MAIN DISCONNECT RATED AT 125AMPS? |
| PLEASE SEE THE PREVIOUS PLANS INDICATE 125AMPS FOR |
| PANEL AND MAIN AND THESE NOW INDICATE 200AMP FOR |
| BOTH?? |
| 230, 225, 240.4, 310.16 ETC |
| FBC 106.1.2 FOR COORDINATION. IT IS UNCLEAR AT THIS |
| TIME WHAT MAINS AND PANELS ARE REALLY BEING DESIGNED. |
| PLEASE ALSO SEE NEXT COMMENT AS SERVICE SIZE HAS NOW |
| BEEN INCREASED. |
| |
| 3) NOTE: PLEASE SEE PREVIOUS PLANS WHICH SHOWED ONE |
| 125AMP MAIN AND ONE 75AMP MAIN WHICH WAS IN LINE WITH |
| THE 200AMP RATED CONDUCTORS AND SERVICE. HOWEVER PLEASE |
| NOW SEE AS THE SERVICE NOW SHOWS A NEW 200AMP MAIN AND |
| A NEW 100AMP MAIN THE RATING OF THE SERVICE NEEDS TO |
| COORDINATE AND BE SIZED FOR THE OVER CURRENT PROTECTION |
| AND CONDUCTORS. THIS IS NOW SHOWN AS A 300AMP SERVICE. |
| RISER SHOWS 3/0 CONDUCTORS TO THE 100AMP MAIN AND 3/0 |
| CONDUCTORS TO THE 100AMP SUB PANEL? |
| PLEASESEE 240.4, 310.16 ETC |
| AS THERE ARE SEVERAL ITEMS WHICH WILL BE ADJUSTED, A |
| FULL REVIEW OF ALL ITEMS CAN NOT BE DONE AT THIS TIME. |
| FBC 106.3.5.4 |
| **PLEASE ALSO SEE THE METER WOULD ALSO NOW NEED TO BE |
| SHOWN AS 300AMPS. |
| |
| 4) NOTE: PLEASE SEE 240.4, 250.66, 310.15B6 AND 310.16. |
| IF THE MINIMUM SERVICE IS NOW GOING TO BE 300AMPS, |
| PLEASE ADJUST SERVICE ENTRANCE CONDUCTORS AND THE |
| GROUNDING ELECTRODE CONDUCTOR AT THE MAIN SERVICE. IF |
| SERVICE IS GOING TO BE 300AMPS, THEN BASED ON MINIMUM |
| SERVICE ENTRANCE CONDUCTORS PER 310.15B6 AND THE |
| SIZING ON TABLE 250.66 REQUIRES THE GEC AT #2 AWG AT |
| MAIN SERVICE LOCATION. |
| |
| 5) NOTE: PREVIOUS REVIEW NOTE REQUESTED TO SHOW THE |
| GROUNDING ELECTRODE SYSTEM AT BOTH GUEST HOUSE AND |
| DETACHED STRUCTURE (MAIN HOUSE). THE RESPONSE MENTIONS |
| THIS IS NOW SHOWN HOWEVER ONLY SHOWS A GROUNDOF SOME |
| TYPE. THIS WILL REQUIRE FOOTER STEEL, (METAL) CWP AND |
| BONDING OF ANY GAS PIPING PER 250.50, 250.56, 250.52, |
| AND 250.104. |
| |
| 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE |
| LIGHT FIXTURES OUTSIDE GUEST HOUSE AND MAIN HOUSE WHICH |
| DID NOT MEET 680.22B1 |
| THE PLANS HAVE NOW BEEN REVISED TO SHOW THESE FIXTURES |
| AT 12FT AFF YET THIS WOULD PLACE THE FIXTURES ABOVE THE |
| ROOF LINE BASED ON THE ELEVATIONS ON THE ARCHITECTURAL |
| PLANS.??? |
| PLEASE SEE THE LOCATIONS OF THE LIGHTING FIXTURES NEED |
| TO BE REVISED. PLEASE ALSO SEE THAT BASED ON THE SCALE |
| ON PLANS THE GFI RECEPTACLES ON BOTH THE MAIN HOUSE AND |
| GUEST ARE SHOWN AT 5FT. THESE MUST BE MORE THAN 5FT |
| FROM WATERS EDGE. THESE COULD BE REDLINED TO VIF |
| HOWEVER BASED ON PLANS AT THIS TIME THIS NEEDS TO BE |
| VERIFIED AS LIGHT FIXTURES NEED TO BE RELOCATED. |
| |
| 7) NOTE: PLEASE SEE AS PANEL SCHEDULES ARE NOW BEING |
| SUBMITTED. PLEASE SEE THAT THESE ARE REQUIRED TO BE |
| DETAILED FOR ALL ROOMS AND AREAS IN WHICH THEY FEED PER |
| 408.4, 240.4, 310.16. |
| IE; BEDRM #2 LTS, KITCHEN LTS. ETC |
| FBC 106.1.2, 106.3.5.4, 106.5 |
| |
| 8) NOTE: PLEASE SEE MISSING RECEPTACLE ALONG KITCHEN |
| WALL IN GUEST HOUSE AND NEW MASTER BEDROOM WALL PER |
| 210.52. |
| ONE WAS GIVEN ON PREVIOUS REVIEW AND CODE FOR 210.52. |
| THE PREVIOUS EXAMPLE FOR MISSING WAS DONE BUT NOT ALL |
| LOCATIONS FOR NEW WALLS 2FT OR MORE WHERE REQUIRED PER |
| 210.52. |
| |
| 9) NOTE: PLEASE GO OVER LOAD CALCULATIONS AS THE SQ FT |
| FOR GUEST HOUSE ON MAIN SERVICE LOAD SUMMARY DOES NOT |
| COORDINATE WITH THE SQ FT ON GUEST HOUSE PANEL |
| CALCULAITONS. |
| NEC 220 |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |