Plan Review Notes
Plan Review Notes For Permit 07120426
Permit Number 07120426
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-03 16:02:33** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THAT MANY COMMENTS ARE NEW AS THESE
 THINGS ARE JUST NOW BEING SHOWN.
 PLEASE ALSO SEE THE RISER HAS NOW BEEN COMPLETELY
 REVISED. SOME NEW COMMENTS HAVE NOW BEEN CREATED. MANY
 ITEMS WHICH WERE CODE COMPLIANT ON PREVIOUS REVIEW HAVE
 NOW COMPLETELY CHANGED AND ARE NOW NO LONGER CODE
 COMPLIANT.
  
 1) NOTE: PLEASE SEE THE RISER HAS BEEN REVISED REMOVING
 A MAIN FOR GROUPING OF MAINS AS REQUIRED PER 230.72. ON
 THE PREVIOUS REVIEW A COMMENT WAS MADE THAT A MAIN
 DISCONNECT WAS MISSING AT THE MAIN HOUSE AS REQUIRED
 PER 225.31-225.39. THIS MAIN WHICH WAS ON PREVIOUS
 RISER GROUPED, HAS NOW BEEN MOVED. THE CODE REQUIRES
 MAINS FOR SERVICE TO BE GROUPED PER 230.72 AND A MAIN
 AT THE DETACHED STRUCTURE PER 225.31-225.39. PLEASE
 ADJUST RISER.
  
 2) NOTE: PLEASE ALSO CORRELATE RISER AND PLANS. THE
 RISER SHOWS THE MAIN AT THE HOUSE AS 200AMPS AND THE
 PLANS CLEARLY SHOW A MAIN DISCONNECT RATED AT 125AMPS?
 PLEASE SEE THE PREVIOUS PLANS INDICATE 125AMPS FOR
 PANEL AND MAIN AND THESE NOW INDICATE 200AMP FOR
 BOTH??
 230, 225, 240.4, 310.16 ETC
 FBC 106.1.2 FOR COORDINATION. IT IS UNCLEAR AT THIS
 TIME WHAT MAINS AND PANELS ARE REALLY BEING DESIGNED.
 PLEASE ALSO SEE NEXT COMMENT AS SERVICE SIZE HAS NOW
 BEEN INCREASED.
  
 3) NOTE: PLEASE SEE PREVIOUS PLANS WHICH SHOWED ONE
 125AMP MAIN AND ONE 75AMP MAIN WHICH WAS IN LINE WITH
 THE 200AMP RATED CONDUCTORS AND SERVICE. HOWEVER PLEASE
 NOW SEE AS THE SERVICE NOW SHOWS A NEW 200AMP MAIN AND
 A NEW 100AMP MAIN THE RATING OF THE SERVICE NEEDS TO
 COORDINATE AND BE SIZED FOR THE OVER CURRENT PROTECTION
 AND CONDUCTORS. THIS IS NOW SHOWN AS A 300AMP SERVICE.
 RISER SHOWS 3/0 CONDUCTORS TO THE 100AMP MAIN AND 3/0
 CONDUCTORS TO THE 100AMP SUB PANEL?
 PLEASESEE 240.4, 310.16 ETC
 AS THERE ARE SEVERAL ITEMS WHICH WILL BE ADJUSTED, A
 FULL REVIEW OF ALL ITEMS CAN NOT BE DONE AT THIS TIME.
 FBC 106.3.5.4
 **PLEASE ALSO SEE THE METER WOULD ALSO NOW NEED TO BE
 SHOWN AS 300AMPS.
  
 4) NOTE: PLEASE SEE 240.4, 250.66, 310.15B6 AND 310.16.
 IF THE MINIMUM SERVICE IS NOW GOING TO BE 300AMPS,
 PLEASE ADJUST SERVICE ENTRANCE CONDUCTORS AND THE
 GROUNDING ELECTRODE CONDUCTOR AT THE MAIN SERVICE. IF
 SERVICE IS GOING TO BE 300AMPS, THEN BASED ON MINIMUM
 SERVICE ENTRANCE CONDUCTORS PER 310.15B6 AND THE
 SIZING ON TABLE 250.66 REQUIRES THE GEC AT #2 AWG AT
 MAIN SERVICE LOCATION.
  
 5) NOTE: PREVIOUS REVIEW NOTE REQUESTED TO SHOW THE
 GROUNDING ELECTRODE SYSTEM AT BOTH GUEST HOUSE AND
 DETACHED STRUCTURE (MAIN HOUSE). THE RESPONSE MENTIONS
 THIS IS NOW SHOWN HOWEVER ONLY SHOWS A GROUNDOF SOME
 TYPE. THIS WILL REQUIRE FOOTER STEEL, (METAL) CWP AND
 BONDING OF ANY GAS PIPING PER 250.50, 250.56, 250.52,
 AND 250.104.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE
 LIGHT FIXTURES OUTSIDE GUEST HOUSE AND MAIN HOUSE WHICH
 DID NOT MEET 680.22B1
 THE PLANS HAVE NOW BEEN REVISED TO SHOW THESE FIXTURES
 AT 12FT AFF YET THIS WOULD PLACE THE FIXTURES ABOVE THE
 ROOF LINE BASED ON THE ELEVATIONS ON THE ARCHITECTURAL
 PLANS.???
 PLEASE SEE THE LOCATIONS OF THE LIGHTING FIXTURES NEED
 TO BE REVISED. PLEASE ALSO SEE THAT BASED ON THE SCALE
 ON PLANS THE GFI RECEPTACLES ON BOTH THE MAIN HOUSE AND
 GUEST ARE SHOWN AT 5FT. THESE MUST BE MORE THAN 5FT
 FROM WATERS EDGE. THESE COULD BE REDLINED TO VIF
 HOWEVER BASED ON PLANS AT THIS TIME THIS NEEDS TO BE
 VERIFIED AS LIGHT FIXTURES NEED TO BE RELOCATED.
  
 7) NOTE: PLEASE SEE AS PANEL SCHEDULES ARE NOW BEING
 SUBMITTED. PLEASE SEE THAT THESE ARE REQUIRED TO BE
 DETAILED FOR ALL ROOMS AND AREAS IN WHICH THEY FEED PER
 408.4, 240.4, 310.16.
 IE; BEDRM #2 LTS, KITCHEN LTS. ETC
 FBC 106.1.2, 106.3.5.4, 106.5
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE ALONG KITCHEN
 WALL IN GUEST HOUSE AND NEW MASTER BEDROOM WALL PER
 210.52.
 ONE WAS GIVEN ON PREVIOUS REVIEW AND CODE FOR 210.52.
 THE PREVIOUS EXAMPLE FOR MISSING WAS DONE BUT NOT ALL
 LOCATIONS FOR NEW WALLS 2FT OR MORE WHERE REQUIRED PER
 210.52.
  
 9) NOTE: PLEASE GO OVER LOAD CALCULATIONS AS THE SQ FT
 FOR GUEST HOUSE ON MAIN SERVICE LOAD SUMMARY DOES NOT
 COORDINATE WITH THE SQ FT ON GUEST HOUSE PANEL
 CALCULAITONS.
 NEC 220
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]