2007-12-28 14:21:24 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET P-1 PLUMBING PLAN, AND SHEET P-2 SANITARY |
| RISER: THE HORIZONTAL DRY VENT FOR THE GUEST HOUSE |
| SHOWER IS NOT ALLOWED PER THE FOLLOWING. |
| |
| 905.3 VENT CONNECTION TO DRAINAGE SYSTEM. |
| EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| PIPE. |
| |
| 905.4 VERTICAL RISE OF VENT. |
| EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 |
| INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE |
| HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| EXCEPTION: VENTS FOR INTERCEPTORS LOCATED OUTDOORS. |
| |
| 2. SHEET P-1 PLUMBING PLAN AND SHEET P-2 SANITARY |
| RISER: TWO-WAY CLEANOUTS ARE REQUIRED FOR THE ADDITION |
| AND GUEST HOUSE SANITARY SYSTEM PER THE FOLLOWING. |
| |
| 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION. |
| THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE |
| BUILDING DRAIN AND THE BUILDING SEWER. THE CLEANOUT |
| SHALL BE EITHER INSIDE OR OUTSIDE THE BUILDING WALL AND |
| SHALL BE BROUGHT UP TO THE FINISHED GROUND LEVEL OR TO |
| THE BASEMENT FLOOR LEVEL. AN APPROVED TWO-WAY CLEANOUT |
| IS ALLOWED TO BE USED AT THIS LOCATION TO SERVE AS A |
| REQUIRED CLEANOUT FOR BOTH THE BUILDING DRAIN AND |
| BUILDING SEWER. THE CLEANOUT AT THE JUNCTION OF THE |
| BUILDING DRAIN AND BUILDING SEWER SHALL NOT BE REQUIRED |
| IF THE CLEANOUT ON A 3-INCH (76 MM) OR LARGER DIAMETER |
| SOIL STACK IS LOCATED WITHIN A DEVELOPED LENGTH OF 10 |
| FEET (3048 MM) OF THE BUILDING DRAIN AND BUILDING SEWER |
| CONNECTION. THE MINIMUM SIZE OF THE CLEANOUT AT THE |
| JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER SHALL |
| COMPLY WITH SECTION 708.7 . |
| |
| 3. SHEET P-1 PLUMBING PLAN AND SHEET P-2 SANITARY |
| RISER: PLEASE INDICATED THAT THE SANITARY CONNECTION |
| FROM THE ADDITION AND GUEST HOUSE TO THE EXISTING |
| SYSTEM SHALL CONNECT DOWNSTREAM OF THE EXISTING WET |
| VENTED BATHROOM PER THE FOLLOWING. |
| |
| 909.1 WET VENT PERMITTED. |
| ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE |
| VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED |
| THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE |
| CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE |
| FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE |
| DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY |
| THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| WET VENT. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |