Plan Review Notes For Permit 07120426 |
Permit Number |
07120426 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-12-24 08:30:08 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) ENERGY CALCULATIONS LINE 13A AND B ARE CALLING FOR | | HEAT PUMP UNITS, MECHANICAL PLAN PAGE M-2 IS SHOWING | | STRAIGHT COOLING UNITS, THE TWO MUST COINCIDE, PLEASE | | CORRECT. | | | | 2) THE TWO BUILDING CAN NOT BE ON THE SAME ENERGY | | CALCULATIONS, THEY MUST EACH HAVE THERE OWN ENERGY | | CALCULATIONS DONE, SEE 2004 FBC 13-101.2.5.1. PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|