Plan Review Notes
Plan Review Notes For Permit 07120426
Permit Number 07120426
Review Stop M
Sequence Number 1
Notes
Date Text
2007-12-24 08:30:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 13A AND B ARE CALLING FOR
 HEAT PUMP UNITS, MECHANICAL PLAN PAGE M-2 IS SHOWING
 STRAIGHT COOLING UNITS, THE TWO MUST COINCIDE, PLEASE
 CORRECT.
  
 2) THE TWO BUILDING CAN NOT BE ON THE SAME ENERGY
 CALCULATIONS, THEY MUST EACH HAVE THERE OWN ENERGY
 CALCULATIONS DONE, SEE 2004 FBC 13-101.2.5.1. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]