Plan Review Notes
Plan Review Notes For Permit 07120426
Permit Number 07120426
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-24 13:06:35** DENIEDREVIEW **
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 ** THE FOLLOWING COMMENTS ARE BASED ON PLANS SUBMITTED
 ONLY.
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING ADOPTED CODES BY THE STATE.
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEERING
 FIRM IS MISSING THE PRINTED NAME AND PRINTED LICENSE
 NUMBER OF THE ENGINEER AS REQUIRED BY THE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002
  
 3) NOTE: PLEASE SEE THE NEW SERVICE RISER AS SUBMITTED
 NEEDS SEVERAL ITEMS TO BE ADDRESSED:
  
 A) PLEASE SEE THE NEW MAIN DISCONNECT AND NEW PANEL FOR
 THE NEW GUEST HOUSE SHOWS 75AMP MAIN AND PANEL, HOWEVER
 THIS DOES NOT CORRELATE WITH THE STANDARD OVER CURRENT
 PROTECTION DEVICES OR EQUIPMENT AS STATED IN THE NEC
 240.6.
 PLEASE ALSO SEE 110.3, 90.7 AND ADJUST.
  
 B) PLEASE INCLUDE THE SIZE (AMPERAGE) OF NEW METER.
 90.7, 230.70, 230.71, 230.90 ETC
  
 C) PLEASE INCLUDE THE TAPPED CONDUCTORS FROM NEW
 SERVICE GUTTER TO NEW MAIN. 240.21, 240.4, 310.16 ETC
  
 D) PLEASE SEE MISSING REQUIRED DISCONNECTING MEANS AT
 THE MAIN HOUSE PER 225.31-225.39.
  
 E) PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM AT THE
 MAIN HOUSE PER 250.32, 250.50.
  
 F) PLEASE COMPLETE GROUNDING ELECTRODE AT THE SERVICE
 LOCATION. THE GROUNDING DETAIL ON E-2 NOTES GROUND RODS
 PER 250.83, AND 250.84 HOWEVER PLEASE SEE THE 2005 NEC,
 AS 250.83 DOES NOT EXIST AND 250.84 IS NOT FOR GROUND
 RODS. PLEASE ADJUST SYSTEM AND NOTES.
  
 4) NOTE: PLEASE CLARIFY THE SMOKE DEVICES ON PLANS.
 PLEASE SEE THE SYMBOL AS SHOWN WHICH IS THE *S* IN THE
 BOX IS NOTED AS A DUCT DETECTOR ON SYMBOL LEGEND.
 PLEASE SEE R313 AND NFPA-72 11.5.1.1.1 AND 11.8.3 AS
 THESE SHOULD BE NOTED AS SA FOR SMOKE ALARMS.
 PLEASE SEE MISSING SA OUTSIDE BEDROOM AT THE GUEST
 HOUSE.
 PLEASE ADJUST NOTES AND PLANS.
  
 5) NOTE: PLEASE SUBMIT PANEL SCHEDULES FOR BOTH THE NEW
 PANEL AT GUEST HOUSE AND THE NEW PANEL AT THE MAIN
 HOUSE. PLEASE SHOW ALL NEW MINIMUM CIRCUITS REQUIRED BY
 THE NEC ALONG WITH THE ADDITIONAL AND EXISTING
 CIRCUITS. PLEASE PROVIDE THE BRANCH CIRCUIT SIZE, OVER
 CURRENT PROTECTION RATING AND CONDUCTORS.
 PLEASE SEE SOME COMMENTS BELOW AS THE *LOAD SUMMARY*
 SUBMITTED CONTAIN ITEMS WHICH DO NOT MEET THE MINIMUM
 PER NEC.
 408.4, 240.4, 310.16, ETC
 FBC 106.3.5.4
  
 6) NOTE: PLEASE SEE THE WATER HEATER AS SHOWN ON LOAD
 SUMMARY DOES NOT MEET 422.1AND422.13. PLEASE SEE THE
 LOAD IS SHOWN AT 6KW YET THE OVER CURRENT PROTECTION IS
 SHOWN AS A 20AMP BREAKER.
 ** PLEASE ALSO SEE THE PLAN WHICH SHOWS 60AMP FOR THE
 WATER HEATER?
 ** IS THERE ARE WATER HEATER AT THE MAIN HOUSE?
  
 7) NOTE: PLEASE SEE THE MINIMUM LOAD WHICH THE CODE
 REQUIRES FOR THE DRYER SHALL BE 5KW. PLEASE SEE NEC
 220.54.
 PLEASE ALSO SEE THE SIZE OF THE CIRCUIT SHALL BE BASED
 ON THE LOAD AND VOLTAGE SUPPLIED. (SHOWS 20AMPS BREAKER
 WHICH IS NOT RATED FOR 5KW AT 240V). PLEASE ADJUST
  
 8) NOTE: PLEASE SUBMIT REVISED LOAD CALCULATIONS FOR
 EACH PANEL AND FOR SERVICE. PLEASE CORRECT AS PER NOTES
 ABOVE PER NEC 220.
 FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE DISCONNECT(S) SHOWN FOR CONDENSING
 UNITS DO NOT COMPLIANCE FOR 110.26.
 PLEASE RE-LOCATE
  
 10) NOTE: PLEASE VERIFY THE GFI SHOWN ON PLANS AT THE
 MAIN HOUSE MEETING 210.63/210.8A FOR THE OUTSIDE
 CONDENSING UNIT. PLAN SHOWS THIS FOR A PUMP. IF THIS IS
 FOR THE PUMP, THE SERVICE RECEPTACLE AS REQUIRED PER
 SECTIONS GIVEN WOULD BE IN ADDITION TO THE DEDICATE GFI
 SUPPLIED FOR THE PUMP.
  
 11) NOTE: PLEASE SEE NEC 680.22 AS THE LIGHTING
 FIXTURES SHOWN ON MAIN HOUSE AND GUEST HOUSE DO NOT
 MEET THE MINIMUM DISTANCES PER SECTION GIVEN.
  
 12) NOTE: PLEASE SEE THE EGRESS LIGHTING CONTROL AT THE
 GUEST HOUSE MUST BE INSIDE THE ROOM (OFFICE) AS SHOWN
 PER 210.70.
  
 13) NOTE: PLEASE SEE NEC2005 210.12 WHICH REQUIRED
 AFCI PROTECTION FOR ALL OUTLETS IN BEDROOM/SLEEPING
 ROOMS. THIS INCLUDES ALL RECEPTACLES, LIGHTS, FANS,
 SMOKE ALARMS ETC.
 PLEASE SEE THE PLANS ONLY SHOW PROTECTION FOR
 RECEPTACLES WHICH WAS IN THE 2002 NEC.
 PLEASE LIST ON THE BRANCH CIRCUITS TO BE PROVIDED ON
 THE NEW PANEL SCHEDULES TO BE SUBMITTED.
  
 14) NOTE: PLEASE SUBMIT AND SHOW THE REQUIRED AIC
 RATING FOR SERVICE MAINS AND EQUIPMENT PER 110.9.
  
 15) NOTE: PLEASE PROVIDE NOTE FOR TYPE OF RECESSED
 LIGHTING FIXTURES PER 13-606.1.ABC.1.2.4
  
 16) NOTE: PLEASE SEE THERE ARE SEVERAL GFI RECEPTACLES
 ON PLAN WHICH SHOWS THE SYMBOL FOR HALF SWITCHED
 DEVICE. GFI RECEPTACLES CAN NOT BE HALF SWITCHED.
 110.3
  
 17) NOTE: PLEASE SEE MISSING RECEPTACLE IN OFFICE ALONG
 2FT OF WALL PER 210.52
  
 18) NOTE: PLEASE SEE REQUIRED DEDICATED CIRCUIT(S) FOR
 BATH ROOMS TO BE CONFIRMED ON NEW PANEL SCHEDULES.
 PLEASE SEE 210.11C3 AS THESE ARE REQUIRED TO BE 20AMP
 AND #12.
  
 ** AS NOTED ABOVE, PLEASE KNOW AS THERE ARE MANY ITEMS
 NOT SUBMITTED OR SHOWN, A COMPLETER REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.** IF THERE ARE
 QUESTIONS, PLEASE CALL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.