Plan Review Notes
Plan Review Notes For Permit 07120384
Permit Number 07120384
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-22 16:56:11** DENIED**
  
 *
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70 (SHOWS 2002)
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER PER FAC 61G1-16.004
 AND FS 481.219.
 PLEASE CONFIRM.
  
 3) NOTE: PLEASE CLARIFY IF ALL CIRCUITS FROM EXISTING
 PANEL LOCATION WILL BE ROUTED TO NEW PANEL LOCATION.
 PLEASE SEE IF UNIT AND ALL BRANCH CIRCUIT CONDUCTORS
 ARE NOT BEING ROUTED AND RE-WIRED TO NEW PANEL LOCATION
 THE ONE INCH CONDUIT BEING SHOWN AS NEW TO BE INSTALLED
 IS NOT LARGE ENOUGH FOR PIPE FILL.
 PLEASE SEE TABLES IN CHAPTER NINE OF THE NEC.
  
 4) NOTE: PLEASE SEE NOTE ON THE BOTTOM OF THE PANEL
 SCHEDULE MENTIONS ALL BEDROOM CIRCUITS TO BE ARC FAULT
 WHICH IS OK, HOWEVER PLEASE SEE ONLY CIRCUIT #12 IS
 SHOWN AS AFCI ON PANEL SCHEDULE.
 210.12 OF THE 2005 NEC REQUIRE ALL OUTLETS INCLUDING
 LIGHTING AND SMOKE ALARMS.
  
 5) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE DEVICES
 ON PLANS SHOW SMOKE DETECTORS WHICH ARE DEVICES WHICH
 DETECT AND DO NOT SOUND AN ALARM. IF THE DEVICES ARE
 UNITS WHICH DETECT AND SOUND AN ALARM PLEASE ADJUST
 DESIGNATION TO SA.
 ** NOTE ON LEFT OF PLANS LEND TO THESE AS BEING SMOKE
 ALARMS**
  
 6) NOTE: PLEASE CLARIFY KITCHEN CIRCUITING AS THE
 KITCHEN ONLY INDICATES ONE SMALL APPLIANCE CIRCUIT.
 PLEASE SEE 210.52B1, 210.11C1. IF RE-WIRE OF BRANCH
 CIRCUITS TO PANEL IS BEING DONE, THIS WILL BE REQUIRED
 TO MEET THE MINIMUM. THIS IS A SAFETY ISSUE DUE TO OVER
 LOADING OF CIRCUIT IN KITCHEN IF ONLY ONE IS PRESENT.
  
 7) NOTE: PLEASE SEE NEC 210.4B AS THE DISHWASHER AND
 DISPOSAL IS BEING SHOWN ON THE SAME YOKE YET THE PANEL
 SCHEDULE SHOWS BOTH OF THESE CIRCUITS ON SINGLE POLE
 BREAKERS. THIS WOULD BE REQUIRED TO BE A DOUBLE POLE
 BREAKER IF FEEDING A SINGLE YOKE/DEVICE.
 PLEASE ADJUST.
  
 8) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND LOAD
 CALCULATIONS.
 PLEASE SEE THE PANEL SCHEDULE INDICATES AN OVEN, YET
 NOT IN LOAD CALCULATIONS.
 PLEASE ALSO SEE THE OVEN IS NOT SHOWN ON PLANS.
 PLEASE SEE THE CALCULATIONS INDICATES A LAUNDRY
 CIRCUIT, HOWEVER NO LAUNDRY ON PLANS OR PANEL
 SCHEDULE.
 PLEASE SEE THE WATER HEATER IS SHOWN AS 3KW ON
 CALCULATIONS, YET THE PANEL SCHEDULE SHOWS THIS AS
 4.5KW.
 PLEASE ALSO SEE THIS SAME WATER HEATER WITH A 4.5KW
 LOAD IS SHOWN ON A SINGLE POLE 20AMP BREAKER WITH #12
 CONDUCTORS.
 PLEASE SEE 408.4, 240.4, 310.16 ETC AND ADJUST AND
 CORRELATE ALL.
 THE ABOVE WAS A FEW EXAMPLES, PLEASE BE SURE TO GO OVER
 ALL.
  
 9) NOTE: PLEASE KNOW DEPENDING ON SCOPE WORK A NEW GFI
 RECEPTACLE MAY BE REQUIRED ALONG KITCHEN COUNTER SPACE
 AS THIS DOES NOT MEET 210.52C1.
 PLEASE SEE THE CODE HAS REQUIRED SPACE ALONG COUNTERS
 TO MEET 210.52C1 FOR DECADES.
 PLEASE SEE AS IT APPEARS THE EXISTING PANEL WAS PLACED
 INSIDE THE OLDER KITCHEN CABINETS WHICH WAS NEVER
 PERMITTED UNDER THE NEC, THE COUNTER SPACE/CABINETS
 APPEAR TO HAVE BEEN ADDED AT SOME POINT.
 IF SPACING EXISTS AND MEETS NEC, PLEASE SHOW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]