Date |
Text |
2007-12-26 11:59:19 | |
| BUILDING PLAN REVIEW |
| PERMIT: 07120384 |
| ADD: 2800 N. FLAGLER DR. #412 |
| CONT: R.W. MORRELL |
| TEL: (561)714-8216 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2)THE CERTIFICATE OF AUTHORIZATION IS MISSING FROM |
| THE DRAWINGS. ANY PERSON PRACTICING UNDER A FICTITIOUS |
| NAME, OFFERING ARCHITECTURAL SERVICES TO THE PUBLIC |
| SHALL DISPLAY THEIR CERTIFICATE OF AUTHORIZATION NUMBER |
| ON SAID INFORMATION. FLORIDA STATUTES 481.219 AND |
| F.A.C. 61G1-16.004. |
| |
| 3)THE DIMENSION OF THE WINDOW SHALL BE INDICATED ON |
| THE DRAWINGS PER FBC 106.1.1. |
| |
| 4)106.3.3* PRODUCT APPROVALS- 2004 |
| THOSE PRODUCTS THAT ARE REGULATED BY DCA RULE 9B-72 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS ARE |
| MISSING THE APPROVAL SIGNATURE OF THE DESIGNER OF |
| RECORD. |
| |
| NOTE: SEE MIAMI DADE NOA #05-1018-01 WHICH HAS MORE |
| INFORMATION THE WINDOW SUBMITTED. YOU MAY ALSO SUBMIT |
| NOA ALONG THE FL#2769.FROM THE NOA CIRCLE THE WINDOW |
| WHICH WILL BE INSTALLED AND ALL INFORMATION PERTAINING |
| TO THE INSTALLATION. |
| |
| 5) THE DESIGN PRESSURES FOR ALL BUILDINGS OVER 60 FEET |
| SHALL BE CALCULATED BY A PROFESSIONAL ENGINEER USING |
| ASCE 7 AND EXPOSURE A, B OR C DEPENDING ON THE LOCATION |
| OF THE BUILDING. THE DESIGN PROFESSIONAL SHALL INDICATE |
| THE DESIGN PRESSURES FOR THE WINDOWS. THE MEAN ROOF |
| HEIGHT AND EXPOSURE CATEGORY SHALL BE STATED ON THE |
| PLANS PER FBC 1609. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |