2008-03-24 14:21:09** DENIED**
  
 1) NOTE: THE PLANS WERE ISSUED WITH A PROVISO TO HAVE
 THE PANEL SCHEDULE REVISED BEFORE FINAL. THE NEW
 CIRCUITING IS STILL NOT SHOWN ON PLANS AND PANEL
 SCHEDULE ONLY SHOWS *GENERAL LTS AND RECEPTACLES*. PER
 408.4, THE ROOMS, AREAS AND CIRCUITS FOR WHICH THEY
 FEED SHALL BE SPECIFIC.
 PLEASE OBTAIN CIRCUITING INFORMATION, PLACE ON NEW
 SHEETS AND HAVE CONTRACTOR SEND IN TO CHANGE OUT
 SHEETS.
  
 ** THE ABOVE WORDING WAS E-MAIL TO THE ENGINEER OF
 RECORD AT 2:18PM ON 3/24/08.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW