Plan Review Notes
Plan Review Notes For Permit 07120310
Permit Number 07120310
Review Stop E
Sequence Number 4
Notes
Date Text
2008-03-14 09:21:29** DENIED REVISION ***
  
 1) NOTE: PLEASE SEE PLANS NOW STATES A NEW MAIN PANEL
 BOARD HOWEVER NO INFORMATION WAS SUBMITTED SHOWING ANY
 NEW FEEDERS, RISER INFORMATION, COMPLETE LOAD
 CALCULATIONS ADDING NEW PANEL BOARD ETC.
 PLEASE SEE NEC 220,230, 215, 240 ETC
 FBC 106.3.5.1.2
 ** NO REVIEW OF MANY ITEMS COULD BE DONE AS NO
 INFORMATION WAS SUBMITTED FOR NEW PANEL.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.