Plan Review Notes
Plan Review Notes For Permit 07120310
Permit Number 07120310
Review Stop M
Sequence Number 3
Notes
Date Text
2008-01-15 16:46:54*** PROVISO ***
 1) PER 2004 FBC/M 607.5.3DUCT PENETRATIONS IN FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING, OR
 MEET THE EXCEPTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729