Plan Review Notes For Permit 07120310 |
Permit Number |
07120310 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-01-08 12:49:38 | BUILDING PLAN REVIEW | | PERMIT: 07120310 | | ADD: 2090 PBL BLVD. SUITE #? | | CONT: S.O. ENTERPRISES | | TEL: (561)827-6508 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 2ND | | ACTION: DENIED | | 12/24/07 | | | | 1A)OK | | 2)OK | | 3)OK | | | | **NEW** | | FBC. 708.1 (5) WALLS SEPARATING INDIVIDUAL TENANT | | SPACES.EXCEPTION (1)IN GROUP B AND S OCCUPANCIES | | WALL USED TO SEPARATE TENANTS SHALL NOT BE REQUIRED TO | | HAVE FIRE-RESISTANCE RATING, PROVIDED NO AREA BETWEEN | | FIRE PARTITIONS HAVING A 1-HOUR FIRE-RESISTANCE RATING | | EXCEEDS 3,000 SQUARE FEET. SUITE #802 IS OVER THE 3000 | | SQUARE FOOTAGE LIMIT, THEREFORE, THE ENTIRE SEPERATION | | WALL REQUIRES A 1-HOUR SEPERATION. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|