Plan Review Notes For Permit 07120310 |
Permit Number |
07120310 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-12-22 15:09:14 | ** DENIED REVIEW ** | | | | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED | | ON PLANS: | | 2004 FBC W/2007 REVISIONS. | | 2005 NFPA-70 | | 2003 NFPA-101 | | 2002 NFPA-72 | | | | 2) NOTE: PLEASE SEE PLANS CALL FOR SCOPE OF WORK ON 6TH | | FLOOR SUITES 601 AND 602 YET THE PERMIT APPLICATION | | STATES SUITE 800. PLANS AND PERMIT INFORMATION HAS BEEN | | ROUTED TO THE ADDRESSING REVIEWER. | | PLEASE BE SURE TO ADJUST INFORMATION ONCE DETERMINED. | | | | 3) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND | | SEALED BY THE ENGINEER OF RECORD AS SHOWN ON TITLE | | BLOCKS. PLEASE SEE FAC 61G15-23.002 AND FS 471.025 | | | | 4) NOTE: PLEASE VERIFY CIRCUITING OF NEW RECEPTACLES | | SHOWN ON PLANS. WHERE ARE THEY CIRCUITED FROM? HOW WILL | | THE OCCUPANT HAVE ACCESS TO CIRCUITS AND OVER CURRENT | | PROTECTION DEVICES? | | PLEASE SEE 240.24, 310.16, 240.4 ETC. | | PLEASE INDICATE CIRCUITING FOR NEW EXIT/EMERGENCY | | LIGHTS PER 700.12F. | | FBC 106.1.2, 106.3.5.1.2 | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|