Plan Review Notes
Plan Review Notes For Permit 07120310
Permit Number 07120310
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-22 15:09:14** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS:
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE PLANS CALL FOR SCOPE OF WORK ON 6TH
 FLOOR SUITES 601 AND 602 YET THE PERMIT APPLICATION
 STATES SUITE 800. PLANS AND PERMIT INFORMATION HAS BEEN
 ROUTED TO THE ADDRESSING REVIEWER.
 PLEASE BE SURE TO ADJUST INFORMATION ONCE DETERMINED.
  
 3) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND
 SEALED BY THE ENGINEER OF RECORD AS SHOWN ON TITLE
 BLOCKS. PLEASE SEE FAC 61G15-23.002 AND FS 471.025
  
 4) NOTE: PLEASE VERIFY CIRCUITING OF NEW RECEPTACLES
 SHOWN ON PLANS. WHERE ARE THEY CIRCUITED FROM? HOW WILL
 THE OCCUPANT HAVE ACCESS TO CIRCUITS AND OVER CURRENT
 PROTECTION DEVICES?
 PLEASE SEE 240.24, 310.16, 240.4 ETC.
 PLEASE INDICATE CIRCUITING FOR NEW EXIT/EMERGENCY
 LIGHTS PER 700.12F.
 FBC 106.1.2, 106.3.5.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.