Date Text
2008-05-19 14:04:20NOTE ADDED: PER FS 713.13(2), THE RECORDED NOC IS NOW
 VOID AS WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING.
2008-05-19 14:01:59** DENIED4TH TIME***
  
 SEE SOME THE EXACT SAME NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE:** THIS IS THE FORTH TIME THIS SAME COMMENT
 HAS BEEN MADE.
 PLEASE *LIST* ON PANEL SCHEDULE THE *REQUIRED ARC FAULT
 PROTECTED CIRCUITS*.THIS WAS REQUESTED ON PREVIOUS
 REVIEWS AND THE PLANS NOW HAVE A NOTE TO SAY AFCI
 PROTECTION IS REQUIRED AND TO SEE THE PANEL SCHEDULE
 FOR THESE CIRCUITS. HOWEVER PLEASE LOOK AT THE PANEL
 SCHEDULE, THERE ARE NO ARC FAULT PROTECTED CIRCUITS
 LISTED. MAY NOT NOTE OR QUOTE THE CODE IN LIEU OF
 REQUIRE CODE ITEMS/DETAILS ETC.
 210.12, 408.4.
 FBC 106.3.5.4
  
 2) NOTE: THIS COMMENT IS ONE AGAIN REPEATED FOR THE
 THIRD REVIEW.
 PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 COORDINATION OF THE MECHANICAL SYSTEMS IN THIS
 DWELLING. IT WAS NOTED PREVIOUSLY THAT THE SIZE AND
 HEAT STRIPS ON MECHANICAL PLANS AND EVEN SHEETS IN THE
 SETS DID NOT MATCH.
 ONCE AGAIN THE SAME COMMENT IS MADE.PLEASE LOOK AT
 THE MECHANICAL PLANS AND PLANS. THESE DO NOT SHOW THE
 SAME KW FOR HEAT STRIPS.
 ELECTRICAL PLANS SPECIFICALLY INDICATE TWO 5KW HEAT
 STRIPS ON LOAD CALCULATIONS YET PANEL SCHEDULE SHOWS
 2-10KW HEAT STRIPS.
 PLEASE SEE AS PREVIOUSLY NOTED CALCULATIONS AND
 COORDINATION OF THESE SYSTEMS SHALL MEET 220.83B.
 WHAT IS THE SIZE OF THE EXISTING ELECTRICAL
 PANEL/SERVICE?
  
 3) NOTE: PLEASE SEE MISSING SMOKE ALARM IN BEDROOM AS
 PREVIOUSLY NOTED. R313, NFPA-72 11.5.1.1, 11.8.3
 THIS WAS REDLINED ON PLANS WHICH MAY HELP TO LOCATE
 MISSING.
  
 4) NOTE: PLEASE SEE PLANS STILL DO NOT CONTAIN ANY
 SIGNATURE OF A DESIGN PROFESSIONAL AS REQUIRED UNDER FS
 471.003, 481.229, 489 ETC
 PLANS SHALL BE DESIGNED BY RESPONSIBLE PERSON. PLANS
 SHALL BE DONE BY LICENSED PROFESSIONAL OR MEETING ONE
 OF THE EXCEPTIONS UNDER THE DESIGN AND RESPONSIBILITY
 OF THOSE PERSONS.
  
 5) NOTE: PLEASE LIST THE DEDICATED CIRCUITS PER
 210.11C3, 210.52D FOR BATHROOM(S).
 MAY NOT LIST *GENERAL LIGHTS AND RECEPTS* OR *GFI*
 CIRCUITS AS THESE DO NOT PROVIDE ANY DESIGNATION.
 PLEASE SEE 408.4 AS ALL CIRCUITS ARE REQUIRED TO BE
 SPECIFIC TO ALL ROOMS AND AREAS IN WHICH THEY FEED.
 FBC 106.3.5.4, 106.1.2
  
 6) NOTE: PLEASE KNOW THERE ARE ITEMS IN EXISTING
 DWELLING WHICH DO NOT MEET CURRENT CODE AND ARE NOT
 PART OF THIS ELECTRICAL REVIEW.
 ** THIS IS ONLY NOTED FOR INFORMATION.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. AS THE DESIGNER OF RECORD HAS CHANGED THE
 FEW AT THIS TIME IS NOT ASSESSED HOWEVER WILL BE
 ASSESSED ON THE FOLLOWING REVIEW TO THE DESIGNER AS
 LISTED.
 THIS FINE WILL BE REQUIRED UNDER THE ABOVE STATUTES AND
 WILL BE $1,615 WHICH WILL BE REQUIRED TO BE PAID BEFORE
 RESUBMITTING PLANS. THIS FEE WILL BE THE RESPONSIBILITY
 OF THE DESIGNER. NOT THE OWNER OR CONTRACTOR.
 ** THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.