2008-05-19 14:04:20 | NOTE ADDED: PER FS 713.13(2), THE RECORDED NOC IS NOW |
| VOID AS WORK HAS NOT COMMENCED WITHIN 90 DAYS OF |
| RECORDING. |
2008-05-19 14:01:59 | ** DENIED4TH TIME*** |
| |
| SEE SOME THE EXACT SAME NOTES FROM PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING. |
| |
| |
| 1) NOTE:** THIS IS THE FORTH TIME THIS SAME COMMENT |
| HAS BEEN MADE. |
| PLEASE *LIST* ON PANEL SCHEDULE THE *REQUIRED ARC FAULT |
| PROTECTED CIRCUITS*.THIS WAS REQUESTED ON PREVIOUS |
| REVIEWS AND THE PLANS NOW HAVE A NOTE TO SAY AFCI |
| PROTECTION IS REQUIRED AND TO SEE THE PANEL SCHEDULE |
| FOR THESE CIRCUITS. HOWEVER PLEASE LOOK AT THE PANEL |
| SCHEDULE, THERE ARE NO ARC FAULT PROTECTED CIRCUITS |
| LISTED. MAY NOT NOTE OR QUOTE THE CODE IN LIEU OF |
| REQUIRE CODE ITEMS/DETAILS ETC. |
| 210.12, 408.4. |
| FBC 106.3.5.4 |
| |
| 2) NOTE: THIS COMMENT IS ONE AGAIN REPEATED FOR THE |
| THIRD REVIEW. |
| PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| COORDINATION OF THE MECHANICAL SYSTEMS IN THIS |
| DWELLING. IT WAS NOTED PREVIOUSLY THAT THE SIZE AND |
| HEAT STRIPS ON MECHANICAL PLANS AND EVEN SHEETS IN THE |
| SETS DID NOT MATCH. |
| ONCE AGAIN THE SAME COMMENT IS MADE.PLEASE LOOK AT |
| THE MECHANICAL PLANS AND PLANS. THESE DO NOT SHOW THE |
| SAME KW FOR HEAT STRIPS. |
| ELECTRICAL PLANS SPECIFICALLY INDICATE TWO 5KW HEAT |
| STRIPS ON LOAD CALCULATIONS YET PANEL SCHEDULE SHOWS |
| 2-10KW HEAT STRIPS. |
| PLEASE SEE AS PREVIOUSLY NOTED CALCULATIONS AND |
| COORDINATION OF THESE SYSTEMS SHALL MEET 220.83B. |
| WHAT IS THE SIZE OF THE EXISTING ELECTRICAL |
| PANEL/SERVICE? |
| |
| 3) NOTE: PLEASE SEE MISSING SMOKE ALARM IN BEDROOM AS |
| PREVIOUSLY NOTED. R313, NFPA-72 11.5.1.1, 11.8.3 |
| THIS WAS REDLINED ON PLANS WHICH MAY HELP TO LOCATE |
| MISSING. |
| |
| 4) NOTE: PLEASE SEE PLANS STILL DO NOT CONTAIN ANY |
| SIGNATURE OF A DESIGN PROFESSIONAL AS REQUIRED UNDER FS |
| 471.003, 481.229, 489 ETC |
| PLANS SHALL BE DESIGNED BY RESPONSIBLE PERSON. PLANS |
| SHALL BE DONE BY LICENSED PROFESSIONAL OR MEETING ONE |
| OF THE EXCEPTIONS UNDER THE DESIGN AND RESPONSIBILITY |
| OF THOSE PERSONS. |
| |
| 5) NOTE: PLEASE LIST THE DEDICATED CIRCUITS PER |
| 210.11C3, 210.52D FOR BATHROOM(S). |
| MAY NOT LIST *GENERAL LIGHTS AND RECEPTS* OR *GFI* |
| CIRCUITS AS THESE DO NOT PROVIDE ANY DESIGNATION. |
| PLEASE SEE 408.4 AS ALL CIRCUITS ARE REQUIRED TO BE |
| SPECIFIC TO ALL ROOMS AND AREAS IN WHICH THEY FEED. |
| FBC 106.3.5.4, 106.1.2 |
| |
| 6) NOTE: PLEASE KNOW THERE ARE ITEMS IN EXISTING |
| DWELLING WHICH DO NOT MEET CURRENT CODE AND ARE NOT |
| PART OF THIS ELECTRICAL REVIEW. |
| ** THIS IS ONLY NOTED FOR INFORMATION. |
| |
| 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| COMPLIANCE. AS THE DESIGNER OF RECORD HAS CHANGED THE |
| FEW AT THIS TIME IS NOT ASSESSED HOWEVER WILL BE |
| ASSESSED ON THE FOLLOWING REVIEW TO THE DESIGNER AS |
| LISTED. |
| THIS FINE WILL BE REQUIRED UNDER THE ABOVE STATUTES AND |
| WILL BE $1,615 WHICH WILL BE REQUIRED TO BE PAID BEFORE |
| RESUBMITTING PLANS. THIS FEE WILL BE THE RESPONSIBILITY |
| OF THE DESIGNER. NOT THE OWNER OR CONTRACTOR. |
| ** THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |