2008-04-16 15:43:06** DENIED3RD REVIEW**
  
 ** PLEASE SEE SEVERAL NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES
 DUE TO NEW ITEMS ONLY NOW BEING SUBMITTED FOR THE FIRST
 TIME FOR REVIEW.
  
 1) NOTE: PLEASE SEE MISSING SMOKE ALARMS INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS PER NFPA-72 11.5.1.1,
 11.8.3.
 PLEASE ALSO SEE R313.
 PLEASE SEE THE NEW LAYOUT OF THE EXISTING DWELLING
 STILL SHOWS SD FOR SMOKE DETECTORS WHICH ARE NOT SMOKE
 ALARMS.
 PLEASE SEE DEFINITIONS IN NFPA-72
 PLEASE SEE NEW ADDITION AREA IS STILL MISSING THE
 REQUIRED DEVICES.
  
 2) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTED
 CIRCUITS PER 210.12. PLEASE LIST ON PANEL AS PREVIOUSLY
 REQUESTED.
  
 3) NOTE: PLEASE SEE THE WRONG TYPE OF RECESSED FIXTURE
 IS STILL BEING SHOWN ON PLANS.
 PLEASE SEE FBC 13-606.ABC.1.2.4
  
 4) NOTE: PLEASE SEE NEW MECHANICAL PLANS INDICATE 5KW
 HEAT FOR ONE AC SYSTEM YET THE NEW PANEL SCHEDULE ONLY
 NOW SUBMITTED INDICATES TWO 10KW HEAT STRIPS/ AC
 SYSTEMS.
 IN EITHER CASE NEITHER THE MECHANICAL PLANS NOR THE
 ELECTRICAL PLANS COORDINATE.
 M-SHEETS:SHOWS ONE 5KW,
 SHEET -1 SHOWS ONE 10KW,
 SHEET- B SHOWS TWO 10KW.
  
 PLEASE COMPLETE ELECTRICAL AND MECHANICAL COORDINATION
 AND PLEASE SEE 220.83B FOR CORRECTED LOAD
 CALCULATIONS.
  
 5) NOTE: PLEASE SEE ONE SET OF THE NEW PLANS SUBMITTED
 ARE NOT SIGNED, DATED OR SEALED BY THE DESIGNER OF
 RECORD AS SHOWN ON TITLE BLOCKS AS REQUIRED UNDER FAC
 61G15-23.002, FS 471.025.
 PLEASE ALSO SEE THAT SEVERAL OF THE SHEETS WHICH
 CONTAIN ELECTRICAL ARE SHOWN WITH A TITLE BLOCK FOR THE
 ENGINEER HOWEVER NOT ALL SHEETS FOR THE SAME SCOPE OF
 WORK IS DONE BY THE SAME DESIGNER.
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B). PLEASE SEE THAT
 THE FEE AS REQUIRED PER STATUTES WILL BE CHARGED IF THE
 SAME CODE COMPLIANT COMMENTS ARE NOT ADDRESSED ON NEXT
 RE-SUBMISSION.
 THERE ARE CODE COMMENTS WHICH ARE NOW BEING REPEATED
 MORE THAN ONCE AND THIS IS BEING GIVEN AS A NOTICE AT
 THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved