Date |
Text |
2008-04-16 15:43:06 | ** DENIED3RD REVIEW** |
| |
| ** PLEASE SEE SEVERAL NOTES FROM PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES |
| DUE TO NEW ITEMS ONLY NOW BEING SUBMITTED FOR THE FIRST |
| TIME FOR REVIEW. |
| |
| 1) NOTE: PLEASE SEE MISSING SMOKE ALARMS INSIDE AND |
| OUTSIDE ALL SLEEPING ROOMS PER NFPA-72 11.5.1.1, |
| 11.8.3. |
| PLEASE ALSO SEE R313. |
| PLEASE SEE THE NEW LAYOUT OF THE EXISTING DWELLING |
| STILL SHOWS SD FOR SMOKE DETECTORS WHICH ARE NOT SMOKE |
| ALARMS. |
| PLEASE SEE DEFINITIONS IN NFPA-72 |
| PLEASE SEE NEW ADDITION AREA IS STILL MISSING THE |
| REQUIRED DEVICES. |
| |
| 2) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTED |
| CIRCUITS PER 210.12. PLEASE LIST ON PANEL AS PREVIOUSLY |
| REQUESTED. |
| |
| 3) NOTE: PLEASE SEE THE WRONG TYPE OF RECESSED FIXTURE |
| IS STILL BEING SHOWN ON PLANS. |
| PLEASE SEE FBC 13-606.ABC.1.2.4 |
| |
| 4) NOTE: PLEASE SEE NEW MECHANICAL PLANS INDICATE 5KW |
| HEAT FOR ONE AC SYSTEM YET THE NEW PANEL SCHEDULE ONLY |
| NOW SUBMITTED INDICATES TWO 10KW HEAT STRIPS/ AC |
| SYSTEMS. |
| IN EITHER CASE NEITHER THE MECHANICAL PLANS NOR THE |
| ELECTRICAL PLANS COORDINATE. |
| M-SHEETS:SHOWS ONE 5KW, |
| SHEET -1 SHOWS ONE 10KW, |
| SHEET- B SHOWS TWO 10KW. |
| |
| PLEASE COMPLETE ELECTRICAL AND MECHANICAL COORDINATION |
| AND PLEASE SEE 220.83B FOR CORRECTED LOAD |
| CALCULATIONS. |
| |
| 5) NOTE: PLEASE SEE ONE SET OF THE NEW PLANS SUBMITTED |
| ARE NOT SIGNED, DATED OR SEALED BY THE DESIGNER OF |
| RECORD AS SHOWN ON TITLE BLOCKS AS REQUIRED UNDER FAC |
| 61G15-23.002, FS 471.025. |
| PLEASE ALSO SEE THAT SEVERAL OF THE SHEETS WHICH |
| CONTAIN ELECTRICAL ARE SHOWN WITH A TITLE BLOCK FOR THE |
| ENGINEER HOWEVER NOT ALL SHEETS FOR THE SAME SCOPE OF |
| WORK IS DONE BY THE SAME DESIGNER. |
| |
| 6) NOTE: PLEASE SEE FS 553.80(2)(B). PLEASE SEE THAT |
| THE FEE AS REQUIRED PER STATUTES WILL BE CHARGED IF THE |
| SAME CODE COMPLIANT COMMENTS ARE NOT ADDRESSED ON NEXT |
| RE-SUBMISSION. |
| THERE ARE CODE COMMENTS WHICH ARE NOW BEING REPEATED |
| MORE THAN ONCE AND THIS IS BEING GIVEN AS A NOTICE AT |
| THIS TIME. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |