Notes
Date Text
2008-04-23 18:36:15 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT FULLY ADDRESSED IN THE
 1ST AND 2ND REVIEWS
  
 6)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD. *******THE DRAWINGS
 SUBMITTED ARE NOT SIGNED AND SEALED BY THE TRUSS
 MANUFACTURERS ENGINEER, PLEASE HAVE ENGINEERED SETS
 THAT ARE REVIEWED AND APPROVED BY YOUR DESIGNER OF
 RECORD AVAILABLE TO INSPECTOR PRIOR TO TRUSS
 ERECTION********
  
 ******PLEASE NOTE THAT THE TRUSS ENGINEERING THAT HAS
 BEEN SUBMITTED IS A LAYOUT SET ONLY, THE REQUIRED SETS
 SHALL HAVE ALL LOADS PRESENT TO MATCH PERMIT DRAWINGS
 AND THE DESIGNED UPLIFTS AT TRUSS BEARING POINTS ETC.
 IF NOT SUBMITTED AT PLAN REVIEW MAY BE PROVIDED TO SITE
 INSPECTOR PRIOR TO TRUSS ERECTION******
  
 10)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG ******NO
 PRODUCT APPROVALS WERE SUBMITTED FOR MULLIONS, AND
 CONNECTORS AND STRAPS. IN LUE OF PRODUCT APPROVALS
 STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE
 DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL
 NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE FLORIDA INDEX
 WITH CONNECTORS TO BE USED HIGHLIGHTED******
  
 ********NO APPROVALS WERE SUBMITTED FOR WINDOW #1
 MULLIONS WHERE 2 SINGLE HUNG UNITS ARE
 INSTALLED********
  
 13)PRODUCT APPROVALS WERE SUBMITTEDEASTERN METAL
 SUPPLY,CIRCLE THE METHOD THAT WILL BE USED TO MOUNT
 THE PANELS AND FILL OUT A SHUTTER SCHEDULE WITH KEY
 PLAN FOR THE OPENINGS PER WEST PALM BEACH MEMO (SEE
 ATTACHED) *******INFORMATION AND SCHEDULE WERE INSERTED
 WITH FIRST REVIEW COMMENTS, PRODUCT APPROVALS WERE NOT
 MARKED WITH INSTALLATION METHOD AND NO INSTALLATION
 SCHEDULE HAS BEEN PROVIDED********
  
 *********THE FOLLOWING PROBLEMS REQUIRE ATTENTION ON
 THE SHUTTER SCHEDULE********
 1)THESH24 WINDOWS ARE 37" X 50 5/8" WITH 3 1/2"
 EDGE DISTANCE X 2 = 7" PLUS APPROX 1" CLEARANCE X 2 THE
 SHUTTER SPANS WOULD BE APPROX 60" NOT 46" AS STATED
  
 2) THE #1 WINDOW IS 2 - SH24 WINDOWS THEREFORE THE
 WINDOW OPENING WOULD BE APPROX 6'-2" IN WIDTH NOT 3'-0"
 AS NOTED ON SCHEDULE
  
 3)TOTAL OPENINGS ON THE DRAWING IS 5 BUT SCHEDULE AND
 ENGINEERING WIND LOAD SHEET SPECIFY 6, ALSO 3 WINDOWS
 AND 2 DOORS ON DRAWINGS WHILE SCHEDULE/ENGINEERING HAS
 2 WINDOWS AND 4 DOORS
  
 *******NEW COMMENT******
  
 1)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004. ONE SET IS MISSING SEAL,SIGNATURE AND DATE.
  
 BLDG PLAN REVIEW