2008-04-23 18:36:15 | |
| |
| DENIED |
| |
| THE FOLLOWING COMMENTS WERE NOT FULLY ADDRESSED IN THE |
| 1ST AND 2ND REVIEWS |
| |
| 6)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD. *******THE DRAWINGS |
| SUBMITTED ARE NOT SIGNED AND SEALED BY THE TRUSS |
| MANUFACTURERS ENGINEER, PLEASE HAVE ENGINEERED SETS |
| THAT ARE REVIEWED AND APPROVED BY YOUR DESIGNER OF |
| RECORD AVAILABLE TO INSPECTOR PRIOR TO TRUSS |
| ERECTION******** |
| |
| ******PLEASE NOTE THAT THE TRUSS ENGINEERING THAT HAS |
| BEEN SUBMITTED IS A LAYOUT SET ONLY, THE REQUIRED SETS |
| SHALL HAVE ALL LOADS PRESENT TO MATCH PERMIT DRAWINGS |
| AND THE DESIGNED UPLIFTS AT TRUSS BEARING POINTS ETC. |
| IF NOT SUBMITTED AT PLAN REVIEW MAY BE PROVIDED TO SITE |
| INSPECTOR PRIOR TO TRUSS ERECTION****** |
| |
| 10)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG ******NO |
| PRODUCT APPROVALS WERE SUBMITTED FOR MULLIONS, AND |
| CONNECTORS AND STRAPS. IN LUE OF PRODUCT APPROVALS |
| STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE |
| DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL |
| NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE FLORIDA INDEX |
| WITH CONNECTORS TO BE USED HIGHLIGHTED****** |
| |
| ********NO APPROVALS WERE SUBMITTED FOR WINDOW #1 |
| MULLIONS WHERE 2 SINGLE HUNG UNITS ARE |
| INSTALLED******** |
| |
| 13)PRODUCT APPROVALS WERE SUBMITTEDEASTERN METAL |
| SUPPLY,CIRCLE THE METHOD THAT WILL BE USED TO MOUNT |
| THE PANELS AND FILL OUT A SHUTTER SCHEDULE WITH KEY |
| PLAN FOR THE OPENINGS PER WEST PALM BEACH MEMO (SEE |
| ATTACHED) *******INFORMATION AND SCHEDULE WERE INSERTED |
| WITH FIRST REVIEW COMMENTS, PRODUCT APPROVALS WERE NOT |
| MARKED WITH INSTALLATION METHOD AND NO INSTALLATION |
| SCHEDULE HAS BEEN PROVIDED******** |
| |
| *********THE FOLLOWING PROBLEMS REQUIRE ATTENTION ON |
| THE SHUTTER SCHEDULE******** |
| 1)THESH24 WINDOWS ARE 37" X 50 5/8" WITH 3 1/2" |
| EDGE DISTANCE X 2 = 7" PLUS APPROX 1" CLEARANCE X 2 THE |
| SHUTTER SPANS WOULD BE APPROX 60" NOT 46" AS STATED |
| |
| 2) THE #1 WINDOW IS 2 - SH24 WINDOWS THEREFORE THE |
| WINDOW OPENING WOULD BE APPROX 6'-2" IN WIDTH NOT 3'-0" |
| AS NOTED ON SCHEDULE |
| |
| 3)TOTAL OPENINGS ON THE DRAWING IS 5 BUT SCHEDULE AND |
| ENGINEERING WIND LOAD SHEET SPECIFY 6, ALSO 3 WINDOWS |
| AND 2 DOORS ON DRAWINGS WHILE SCHEDULE/ENGINEERING HAS |
| 2 WINDOWS AND 4 DOORS |
| |
| *******NEW COMMENT****** |
| |
| 1)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA |
| STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND |
| DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC |
| 2004. ONE SET IS MISSING SEAL,SIGNATURE AND DATE. |
| |
| BLDG PLAN REVIEW |