Plan Review Notes For Permit 07120265 |
Permit Number |
07120265 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-02-25 13:52:25 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 2) ENERGY CALCULATIONS ARE CALLING FOR A 14 SEER A/C | | SYSTEM, SYSTEM LISTED ON MECHANICAL PLAN IS A 13 SEER | | (SEE ATTACHED ARI CERTIFICATE) THE PLANS CAN NOT CALL | | FOR A LOWER SEER THAN THE ENERGY CAL'S. SEE 2004 FBC | | 13-607.1.ABC.3.1.1. PLEASE CORRECT. | | | | 3) THE A/C HEAT PUMP SYSTEM LISTED ON THE MECHANICAL | | PLAN HAS BEEN DISCONTINUED IN THE ARI LISTING (SEE | | ATTACHED ARI CERTIFICATE) SEE 2004 FBC | | 13-607.1.ABC.3.1.1. PLEASE CORRECT. | | | | 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND | | CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE | | W.P.B. AMEND. 106.1.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|