2008-02-25 13:52:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) ENERGY CALCULATIONS ARE CALLING FOR A 14 SEER A/C
 SYSTEM, SYSTEM LISTED ON MECHANICAL PLAN IS A 13 SEER
 (SEE ATTACHED ARI CERTIFICATE) THE PLANS CAN NOT CALL
 FOR A LOWER SEER THAN THE ENERGY CAL'S. SEE 2004 FBC
 13-607.1.ABC.3.1.1. PLEASE CORRECT.
  
 3) THE A/C HEAT PUMP SYSTEM LISTED ON THE MECHANICAL
 PLAN HAS BEEN DISCONTINUED IN THE ARI LISTING (SEE
 ATTACHED ARI CERTIFICATE) SEE 2004 FBC
 13-607.1.ABC.3.1.1. PLEASE CORRECT.
  
 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]