2008-03-04 07:51:04 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE MANY COMMENTS FROM THE PREVIOUS REVIEW |
| ARE STILL IN NEED OF ADDRESSING. |
| |
| |
| 1) NOTE:PLEASE SUBMIT A COMPLETE PLANS INCLUDING |
| PANEL SCHEDULE SHOWING ALL NEW CIRCUITS ALONG WITH |
| EXISTING COMPLYING WITH THE 2005 NEC. |
| NO PANEL SCHEDULE WAS SUBMITTED. |
| THE LOAD CALCULATIONS CAN NOT BE VERIFIED WITH THE |
| CIRCUITING TO BE SHOWN ON PANEL SCHEDULE. ALSO CAN NOT |
| VERIFIY WITH MINIMUM REQUIRED CIRCUIT(S) FOR NEW AND |
| EXISTING. |
| DOES THE DWELLING ALREADY CONTAIN AN A/C SYSTEM? |
| PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS. |
| PLEASE BE SURE TO LIST ALL OVER CURRENT PROTECTION |
| DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC 210.52, |
| 210.11, 408.4, 240.4, 310.16 ETC |
| FBC 106.3.5.4 |
| |
| 3) NOTE: PLEASE SEE 210.12 FOR MISSING REQUIRED ARC |
| FAULT FOR ALL OUTLETS. THIS REQUIRES *CIRCUITS* IN |
| PANEL TO BE LABELED. |
| |
| 4) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED |
| DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12 |
| AWG. |
| THESE NEED TO BE LISTED ON PANEL SCHEDULE. * MAY NOT |
| QUOTE THE CODE IN LIEU OF REQUIRED MINIMUM* |
| |
| 5) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING |
| DWELLING AS WELL AND THE NEW ROOMS WHICH ARE SLEEPING |
| ROOMS OR ADAPTABLE SLEEPING ROOMS PER FBC R313 AND |
| NFPA-72 11.5.1.1.1, 11.8.3. |
| THIS WAS NOT DONE. IN FACT THE NOTE ADDED TO PLANS |
| MENTIONS *SMOKE DETECTORS* WHICH WOULD BE PART OF A LOW |
| VOLTAGE FIRE ALARM PANEL AND SYSTEM. IF THESE ARE GOING |
| TO BE SMOKE DETECTORS, PLEASE COMPLETE PLANS WITH ALL |
| DEVICES FOR A FIRE ALARM SYSTEM WITH HORN ALARM |
| DEVICES. PLEASE SEE NFPA-72 FOR DEFINITIONS FOR A SMOKE |
| ALARM AND SMOKE DETECTOR. IF THESE ARE GOING TO BE |
| SMOKE ALARMS, PLEASE INDICATE AND COMPLETE PLANS |
| ACCORDINLY. |
| THE PREVIOUS REVIEW REQUESTED TO SHOW EXISTING SHOWING |
| CURRENT CODE COMPLIANCE OR NEW TO BE INSTALLED. PLANS |
| SUBMITTED DO NOT SHOW EITHER. |
| PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING |
| DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE |
| CURRENT VERSION OF NFPA-72 11.5.1.1.1 OR NEW TO BE |
| INSTALLED. |
| *MAY NOT QUOTE CODE IN LIEU OF SHOWING MINIMUM DETAILS |
| FOR CODE COMPLIANCE. |
| |
| 6) NOTE: THE A/C UNITS ARE NOW SHOWN HOWEVER PLEASE SEE |
| 210.70, 210.63 FOR REQUIRED SERVICE OUTLETS IN ATTIC |
| WHICH ARE NOT SHOWN ON PLANS. |
| |
| 7) NOTE: PLEASE SEE THE ELECTRICAL SHOWN ON SHEET 2 FOR |
| REAR PORCH IS NOT THE SAME AS THE ELECTRICAL SHOWN ON |
| A-SHEET. |
| PLEASE COORDINATE PLANS. FBC 106.1.2, 106.3.5.4 |
| ** THIS IS THE SAME COMMENT. RESPONSE MENTIONS |
| |
| 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED |
| LIGHTING PER FBC 13-606.ABC.1.2.4 |
| THE NOTE WHICH WAS ADDED TO PLANS INDICATES A TYPE *IC* |
| RATED RECESSED LUMINAIRE WHICH IS NOT THE SECTION OF |
| THE CODE GIVEN IN PREVIOUS REVIEW. |
| PLEASE ADJUST NOTE AND TYPE OF FIXTURE. |
| |
| 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE. THIS IS |
| ONLY A NOTICE GIVEN AT THIS TIME TO THE DESIGN |
| PROFESSIONAL. |
| |
| |
| *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR |
| REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |