Plan Review Notes
Plan Review Notes For Permit 07120265
Permit Number 07120265
Review Stop Z
Sequence Number 1
Notes
Date Text
2007-12-17 11:52:13***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 3)INDICATE HEIGHT DIMENSIONS OF PROPOSED ADDITION
 FROM GRADE ON THE SHOWN ELEVATIONS.
  
 4)THE SURVEY INDICATES A REAR SETBACK DIMENSION OF
 5.77', THIS DOES NOT APPEAR ACCURATE GIVEN THE
 DIMENSIONS OF THE LOT AND THE DIMENSIONS OF THE
 PROPOSED, PLEASE CLARIFY.IF THIS IS ACCURATE, IT DOES
 NOT MEET THE MINIMUM SETBACK REQUIREMENTS SET FORTH IN
 SECTION 94-72(A)(2) OF THE ZLDRS.MUST MEET MINIMUM
 REAR SETBACK OF 10' (10% OF LOT DEPTH).PLEASE SHOW
 SETBACK DIMENSION FROM PROPOSED TO ALL PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720