2007-12-21 15:08:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 13A IS CALLING FOR A HEAT
 PUMP SYSTEM, A/C UNIT LISTED ON MECHANICAL PLAN IS
 STRAIGHT COOL ONLY WITH ELECTRIC HEAT, THE TWO MUST
 COINCIDE, PER 2004 FBC 13-103.1.1, PLEASE CORRECT.
  
 2) ENERGY CALCULATIONS LINE 12A IS CALLING FOR 17,600
 TOTAL COOLING BTU'S, MECHANICAL PLAN A/C SYSTEM IS
 25,000 TOTAL COOLING BTU'S, THE TWO MUST COINCIDE,
 PLEASE CORRECT.
  
 3) COOLING LOAD CALCULATIONS ARE CALLING FOR 11,224
 TOTAL COOLING BTU'S, MECHANICAL PLAN A/C SYSTEM TOTAL
 COOLING BTU'S IS 25,000. THE PLAN CAN ONLY CALL FOR 15%
 MORE THAN THE COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 4) SEE MECHANICAL PLAN, PLEASE SHOW THE SIZE OF THE
 SUPPLY AIR DUCT FROM THE AIR HANDLER TO THE MIXING BOX
 (SEE YELLOW HIGH LIGHT ON MECH. PLAN).
  