Plan Review Notes
Plan Review Notes For Permit 07120265
Permit Number 07120265
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-23 14:32:09** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS:
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SUBMIT A COMPLETE PLANS INCLUDING PANEL
 SCHEDULE SHOWING ALL NEW CIRCUITS ALONG WITH EXISTING
 COMPLYING WITH THE 2005 NEC.
 PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS.
 PLEASE BE SURE TO LIST ALL OVER CURRENT PROTECTION
 DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC 408.4,
 240.4, 310.16 ETC
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SEE 210.12 FOR MISSING REQUIRED ARC
 FAULT FOR ALL OUTLETS.
  
 4) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12
 AWG.
  
 5) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING
 DWELLING AS WELL AND THE NEW ROOMS WHICH ARE SLEEPING
 ROOMS OR ADAPTABLE SLEEPING ROOMS PER FBC R313 AND
 NFPA-72 11.5.1.1.1, 11.8.3
 PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING
 DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE
 CURRENT VERSION OF NFPA-72 11.5.1.1.1 OR NEW TO BE
 INSTALLED.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECTS FOR A/C
 CONDENSING UNITS PER 440.11.
 PLEASE ALSO SEE THE NEW AHU IS MISSING FROM ELECTRICAL
 PLANS.
 440.11, 110.26
  
 7) NOTE: PLEASE SEE THE ELECTRICAL SHOWN ON SHEET 2 FOR
 REAR PORCH IS NOT THE SAME AS THE ELECTRICAL SHOWN ON
 A-SHEET.
 PLEASE COORDINATE PLANS. FBC 106.1.2, 106.3.5.4
  
 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED
 LIGHTING PER FBC 13-606.ABC.1.2.4
  
  
 *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR
 REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved