Plan Review Notes
Plan Review Notes For Permit 07120262
Permit Number 07120262
Review Stop P
Sequence Number 1
Notes
Date Text
2008-03-04 18:56:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. SURVEY SHEET THE ADDRESS FOR WALLACE SURVEYING #4569
 DOES NOT REFLECT THE STATE OF FLORIDA DBPR ADDRESS OF
 RECORD. PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR
 WEBSITE PRIOR TO RESUBMITTING. FAC 61G16.004(1) & FS
 481.306.
  
 2. IRRIGATION PLANS & PERMIT REQUIRED. SECTION
 106.3.5.1.3(9).
  
 3. THE ADDRESS ON THE PLANS AND THE BINDER ARE
 DIFFERENT. 2501 N FLAGLER AND 2500 PONCE DE LEON AVE.
 PLEASE CORRELATE. FAC 61G1-16.004(3) & FS 481.2055.
  
 4. SHT G-0.03 APPLICABLE CODE TO INCLUDE FHA-98 DESIGN
 MANUAL.
  
 5. SHTS A-2.52 & A-2.53 DRAINS AROUND THE POOL ARE
 INDICATED AS FLOOR DRAINS. IF THEY ARE FOR DRAINING THE
 STORM WATER OFF THE DECK THEY SHOULD BE INDICATED AS
 DECK DRAINS.--ALSO SEE FLOOR DRAINS AT THE "TH
 UNITS". PLEASE CLARIFY WHAT IS BEING DRAIND. THEY
 APPEAR TO BE ROOF DRAINS AT THE SPA. SECTIONS 106.1.1
 106.2.1, TABLES 710.1(1), 710.1(2) & 1106.3.
  
 6. SUBMIT CALCULATION FOR MINIMUM FACILITIES FOR THE
 COMMON AREAS, FITNESS, RECREATION, SOCIAL BAR, SOCIAL
 /LOUNGE OFFICE ETC. TABLES 1004.1.2 & 403.1.
  
 7. SHT A-2.6.2 NO SECONDARY ROOF DRAINS/EOS SHOWN AT
 STAIR #9. SECTION 1107.
  
 8. SHT A-2.6.3 NO SECONDARY ROOF DRAINS/EOS SHOWN AT
 STAIR #7. SECTION 1107.
  
 9. SHTS A-3.10 THRU A-3.53 SHOW COMPLIANCE WITH
 REQUIREMENTS 6 & 7 FOR EACH UNIT, OR SHOW COMPLIANCE
 FOR A TYPICAL UNIT OF EACH TYPE. SHOW THE WATER CLOSET
 AT 18" OFF THE WALL TO THE CENTERLINE OF THEFIXTURE
 WHERE APPLICABLE, (PAGE 6.3) & SHOW A MINIMUM 33"
 OPENING FOR THE WATER CLOSETS. INDICATE 18" & 15" FROM
 THE CENTERLINE OF THE FIXTURE TO ADJACENT FIXTURES WHEN
 NOT NEXT TO A WALL. (PAGE 6.7). FHA-98 DESIGN MANUAL.
 --SEE PAGE 6.10 FOR REINFORCING AT NON CONVENTIONAL
 BATHTUBS. IF THIS TYPE OF TUB IS TO BE ADAPTABLE PLEASE
 SHOW THE BACKING.
  
 10. SHTS A-3.10 THRU A-3.53 SHOW CLEAR FLOOR SPACE IN
 THE KITCHEN AS REQUIRED ON PAGES 7.3 & 7.4 FHA-98
 HOUSING MANUAL.--SHOW MINIMUM CLEARANCE DIMENSION
 BETWEEN REFRIG, RANGE & BASE CABINETS AS REQUIRED ON
 PAGES 7.7 & 7.8 FHA-98 DESIGN MANUAL.--SHOW TURNING
 IN THE "U" SHAPED KITCHENS THAT HAVE A SINK, RANGE OR
 COOKTOP AT ITS BASEAS REQUIRED ON PAGE 7.9 OR SEE
 EXCEPTION ON PAGE 7.11. INDICATE ON PLANS IF EXCEPTION
 WILL BE USED AND SUBMIT A DETAIL FOR EXCEPTION.
  
 11. SHTS A-3.10 THRU A-3.53 INDICATE ON PLANS WHICH
 SPECIFICATION, "A" OR "B" TO BE USED FOR EACH UNIT AS
 REQUIRED ON PAGES 7.34 & 7.35. SEE REQUIREMENTS FOR
 EACH.--SHOW THE CLEAR FLOOR SPACE, (SUPERIMPOSED
 ON THE FLOOR PLANS), FOR THE ACCESSIBLE FIXTURES FOR
 EACH UNIT. SEE PAGES 7.43 THRU 7.57.
  
 12. SHT A-3.16 SHOW THE CLEAR FLOOR SPACE FOR THE
 ACCESSIBLE FIXTURES IN THE MEN'S AND WOMEN'S LOCKER
 ROOMS. SHOW THE TURNING AREA. SHOW THE CLEAR FLOOR
 SPACE FOR THE ACCESSIBLE DRINKING FOUNTAIN. SHOW THE
 ACCESSIBLE W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE AND THE LAV TO BE A MINIMUM
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE.
 SECTIONS 11-4.16.2, 11-4.18.3, 11-4.19.3, 11-4.21.2
 11-4.22.3 & FIGURE 28 AS WELL AS SECTION 11-4.15.5 FOR
 THE DRINKING FOUNTAIN.
  
 13 SHT A3.1.6 ACCESSIBLE STALLS SHALL COMPLY WITH
 FIGURE 30(E), FLUSH CONTROLS FOR WATER CLOSETS SHALL
 COMPLY WITH SECTION 11-4.16.5. LAVS SHALL COMPLY WITH
 SECTIONS 11-4.19.4 EXPOSED PIPES AND SURFACES AS WELL
 AS 11-4.19.5 FAUCETS. PLEASE SUBMIT DETAILS.
  
 14. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A).
  
 15. SHT A-3.28 MEN'S AND WOMEN'S TOILET ROOMS. SHOW THE
 CLEAR FLOOR SPACE FOR ACCESSIBLE FIXTURES PER SECTIONS
 11-4.16.2 & 11-4.19.3.
  
 16. SHT A-3-31 SHOW W/C'S TO BE 18" OFF THE WALL AND
 THE LAVS MINIMUM 15" OFF THE WALL. FIG 28.--STALLS
 TO COMPLY WITH FIG. 11-30(E).
  
 17. SHT A-3.31 MORE INFORMATION REQUIRED. WILL THERE BE
 COOKING IN THE CATERING KITCHEN? SECTION 106.1.2.
  
 18. SHTS A-7.04 & A-7.05 FINISH SCHEDULE FOR COMMON
 AREAS. PLEASE INDICATE WHERE THE LEGEND FOR THE FINISH
 TYPES CAN BE LOCATED. REMARKS STATE "REFER TO ID.
 DRAWINGS". PLEASE INDICATE THE SHEET NUMBER FOR ID
 DRAWINGS. SECTION 106.1.2.
  
 19. SUBMIT CALCULATIONS FOR PRIMARY AND SECONDARY ROOF
 & DECK DRAINS FOR THE ROOF, GROUND FLOOR DECK AND
 SECOND FLOOR. SHOW SECONDARY DRAINS FOR SHEETS P-1.1
 THRU P-1.5 AND SHTS P-2.1 THRU P-2.4. SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS AND TABLES. SHOW THE AREA
 BEING DRAINED BY EACH ROOF DRAIN, DECK DRAIN AND 1/2
 THE AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS FOR
 EACH DRAIN AFFECTED, AS WELL AS ANY AREA FROM A ROOF
 THAT DRAINS TO THE ROOF/DECK FROM ABOVE IN THE
 CALCULATIONS.
  
 20. SHT P-00 NOTE STATES "2 INCH COLD WATER TO COOLING
 TOWER METER, FOR EXACT LOCATION SEE CIVIL ENGINEERING
 DRAWING" - COOLING TOWER METERWATER NOT SHOWN ON SHEET
 C3. PLEASE CLARIFY. SECTIONS 106.1.2 AND 608.13.2.
  
 21. SHT P-00 IN ONE SET OF PLANS HAS DIFFERENT
 INFORMATION THAN THE SHT P-00 IN THE OTHER SET OF
 PLANS. ALSO THE DATE THAT THE SEAL AND SIGNATURE WERE
 AFFIXED IS DIFFERENT. WHY 2 SHEETS WITH P-00
 DESIGNATIONS? PLEASE CLARIFY. SECTION 106.1.2.
  
 22. SHTS P-001, P-002, P-00, P-01 & P-.2 ARE DRAWN AT
 1/16TH PER FT. SCALE & HAS ALOT OF INFORMATION AND IS
 NOT LEGIBLE AS TO ITS INTENT. BLDG PLANS SHALL BE DRAWN
 TO A MINUMUM 1/8" PER FT SCALE PER SECTION 106.1.3.
  
 23. SHT P-001 DOMESTIC PUMP ROOM A SHUT OFF VALVE IS
 REQUIRED FOR THE LINE TO THE HOSE BIBB. SECTION
 606.2(2).--PIPING IS NOT SHOWN TO MANY DECK DRAINS.
 --SUMP PUMP #11 WAS NOT FOUND.--2 SUMP PUMPS HAVE
 THE # 20 SHOWN. PLEASE CLARIFY--MANY NOTES ON THE
 FLOOR PLAN ARE NOT LEGIBLE. (RISER DESIGNATION NUMBERS
 OVER THE TOP OF NOTES). PLEASE CLARIFY--SHOW ALL
 PIPE SIZES AND RISER DESIGNATIONS FOR STORM RISERS.--
 INDICATE WHERE THE SANITARY PIPE CONTINUES TO WHEN
 INDICATING CONTINUATION OF PIPE. (WHAT SHEET DOES IT
 CONTINUE ON)?--TWO RISER 63 DESIGNATIONS. PLEASE
 CLARIFY--IDENTIFY FIXTURES BEHIND THE ELEVATORS AND
 INDICATE WHICH RISER THE VENT CONNECT TO AT ELEVATORS
 ONE THRU FIVE. SHOW VENT ON RISER. SECTIONS 106.1.1 &
 106.1.2. TABLES 710.1(1), 710.1(2), 916.1, 1106.2 &
 1106.3.
  
 24. SHT P-002 ONE GAS RISER NOT CONNECTED TO GAS MAIN.
 -- SOME GAS RISERS ARE INDICATED AS RISING UP AND
 DROPING DOWN FROM THE LOWER LEVEL GARAGE. ARE THERE GAS
 APPLIANCES BELOW THE LOWER GARAGE? PLEASE CLARIFY.--
 IDENTIFY RISERS AT THE BASE OF THE STACK SO COMMENTS
 CAN BE ADDRESSED TO SPECIFIC RISERS.--SOME NOTES
 ARE NOT LEGIBLE.--INDICATE GAS PIPE SIZES. SECTIONS
 106.1.1, 106.1.2 TABLE 402.4(3).
  
 25 INDICATE THE STORM RISER NUMBERS FOR EACH STORM
 RISER ON EACH SHEET THROUGH OUT THE BUILDING SO THE
 RISERS CAN BE TRACKED. SHEET WILL BE REVIEWED WHEN
 SUBMITTED TO ACCEPTABLE SCALE. SECTION 106.1.3. TABLES
 1106.2 & 1106.3.
  
 26. SHTS P-001 AND P-01 HAVE THE SAME INFORMATION.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 27. SHT P-1.1 SHOWS PIPING TO FIXTURES THAT ARE NOT ON
 THE FLOOR PLAN, EXAMPLE RISER #2. THE SHEET ALSO SHOWS
 FIXTURES WITH NO PIPING INDICATED, EXAMPLE RISER NUMBER
 33. SHOW ALL PIPING TO THE FIXTURES. THE SANT. PIPING
 SHALL BE SHOWN ON THE SAME SHEET AS THE FIXTURES. THE
 STORM PIPING SHALL BE SHOWN ON THE SAME SHEET AS THE
 DECK DRAINS, PLANTER DRAINS ETC. (SEE SHT P-5.2 RISER
 49 AS AN EXAMPLE).--WHAT RISER DOES THE SINK BY
 STAIR 1A CONNECT TO?--SANITARY RISER #4 DOES NOT
 REFLECT THE FLOOR PLAN.--IDENTIFY THE PIPE BY RISER
 115 NOT SHOWN ON THE RISER.--INDICATE RISER NUMBERS
 FOR W/M'S BEHIND ELEVATORS 1, 2 & 3 AS WELL AS THE
 W/M'S BEHIND STAIR #2 & STAIR #3.--EXPLAIN THE
 NUMBER 5 IN THE RECTANGLE BY THE HOSE BIBB NEAR COL.
 LINE 3/D. SECTIONS 106.1.1 & 106.1.2. TABLE 1106.3.
  
 28. SHTS P-1.2, P-1.3, P-1.4, P-1.5, P-2.1, P-2.2,
 P-2.3, P-2.4, P-3.1, P-3.4, P-4.1, P-4.2, P-4.3, P-4.4,
 P-5.1, P-5.4, P-6.1, P-6.2, P-7.1 & P-7.2SHOW PIPING
 TO FIXTURES, DECK DRAINS & PLANTER DRAINS ON THE SHEET
 THAT THE FIXTURES, DECK DRAIN & PLANTER DRAINS ARE
 LOCATED. SEE SHT P-2.3 RECREATION REST ROOM OR SHT
 P-3.3 SOCIAL ROOM BATHROOM AS EXAMPLES OF CORRECT
 INFORMATION. SECTIONS 106.1.1 & 106.1.3.
  
 29. SHT P-1.2 IDENTIFY THE RISER NUMBERS FOR W/M'S
 BEHINDSTAIR NUMBER 4, STAIR NUMBER 5 AS WELL AS
 ELEVATORS NUMBERS 4, 5 & 6.--2 RISERS NUMBERED 63.
 PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2 & TALBES
 710.1(1), 710.1(2).
  
 30. SHT P1.3 THE OVERFLOW FROM THE FOUNTAIN SHALL DRAIN
 TO THE STORM, NOT SANITARY AS SHOWN. (NOTE #3). --
 WATER RISER 18 & CONDENSATE 17 IN THE SAME UNIT? SEE
 WATER RISER 17 & CONDENSATE 18ALSO.-- RECREATION
 BATHROOM SHOWS 1/2" COLD WATER SUPPLY TO THE BATHROOM
 THEN INCREASES TO 1-1/4". WATER ALSO SHOWS 2" SUPPLY
 DROPS BETWEEN THE SHOWERS. PLEASE CLARIFY. SECTIONS
 106.1.1 & 106.1.2. TABLE 604.5.--SHOW RISER
 DESIGNATION NUMBERS FOR RISER 76, 77, 79 & 80 AS WELL
 AS RISERS 81, 82 & 87.--SHUT OFF VALVE IS REQUIRED
 ON THE SUPPLY LINE TO THE HOSE BIBB IN THE FOUNTAIN
 EQUIPMENT ROOM.SECTIONS 106.1.1, 106.1.2 & 606.2(2).
  
 31. SHTS P2.1 THRU P2.4 SHOW THE SANITARY PIPING TO
 EACH FIXTURE THAT REFLECTS THE FLOOR PLAN. SECTION
 106.1.1, 106.1.2 & 106.3.5.1.3.
  
 32. SHT P-4.1 BRANCH LINE TO KITCHEN SINK MISSING FOR
 RISER #34. SECTION 106.1.1, 106.1.2 & TABLE 709.1.
  
 33. SHT P-4.2 BRANCH LINE TO KITCHEN SINK MISSING FOR
 RISER #34. SECTION 106.1.1, 106.1.2 & TABLE 709.1.
  
 34. SHT P-4.4 SHOWS TWO 2" LINES TO THE COOLING TOWER.
 ARE THERE TWO COOLING TOWERS? PLEASE CLARIFY. SECTION
 106.1.2.
  
 35. SHT P-5.2 INDICATE WHERE THE 1/4" SCALE TO THE
 TOILET ROOMS CAN BE LOCATED AS REFERENCED. INFORMATION
 AT THE RIGHT SIDE OF THE FLOOR PLAN IN NOT COMPLETE.
 PLEASE SHOW ALL INFORMATION INTENDED. SECTIONS 106.1.1
 & 106.1.2.
  
 36. SHT P-5.3 VENT 87 IS NOT SHOWN AND VENT 91A
 INDICATED IS NOT SHOWN ON THE LOWER LEVELS. PLEASE
 CORRELATE. SECTION 106.1.1 & TABLE 916.1.
  
 37. SHT P-5.4 VENTS 105 & 107 ARE SHOWN CONNECTING TO
 THE EAST VENT ON SHT P-4.4. PLEASE CLARIFY.--
 COOLING TOWER WATER SUPPLY PIPING DOES NOT REFLECT THE
 FLOOR PLAN AS THE HOSE BIBB IS MISSING. PLEASE
 CORRELATE. SECTION 106.1.1 & TABLE 916.1.
  
 38. SHT P-6.2 SHOW THE VTR FOR RISERS 70 & 71. SECTIONS
 106.1.1 & 903.3.
  
 39. SHT P-7.1 INDICATE THE RISER NUMBER FOR THE 7TH
 FLOOR TOILET ROOMS SANITARY. SECTION 106.1.1 & TABLES
 710.1(1) & 710.1(2).
  
 40. SHT P-7.2 UNABLE TO REVIEW INFORMATION ON THE NORTH
 END, (LEFT SIDE),OF SHEET WITHOUT TAKING PLANS APART.
 SECTION 106.1.3. PLEASE SEE THAT ALL INFORMATION IS
 AVAILABLE FOR REVIEW.--SHOW ALL RISER NUMBERS AT
 THE TOILET ROOMS. SECTIONS 106.1.1 106.1.2 & TABLES
 710.1(1) & 710.1(2).
  
 41. SHT P-8 LINE TO THE ICE MAKER NOT SHOWN ON THE
 FLOOR PLAN FOR BOTH A UNITS. PLEASE CORRELATE. SECTION
 106.1.1.
  
 42. SHT P-9 UNIT "B" FLOOR PLAN DOES NOT SHOW THE WATER
 LINE TO THE ICE MAKER TO REFLECT THE ISO. RISER
 DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.--UNIT
 "B" GROUND FLOOR PLAN SHOWS THE WATER LINE TO THE ICE
 MAKER UNDER THE SLAB ON THE FLOOR PLAN, BUT NOT ON THE
 ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1.
  
 43. SHT P-10 UNIT"C" WATER RISER DOES NOT REFLECT THE
 FLOOR PLAN WHERE THE WASH MACHINE CONNECTS TO THE
 HOT/COLD WATER MAIN. PLEASE CORRELATE. SECTIONS 106.1.1
 & 604.
  
 44. SHT P-11 UNIT "B" FLOOR PLAN DOES NOT SHOW THE
 WATER LINE TO THE ICE MAKER TO REFLECT THE ISOMETRIC
 RISER DIAGRAM.--UNIT "B" GROUND FLOOR PLAN
 INDICATES THE ICE MAKER SUPPLY LINE IN THE SLAB, BUT
 THE RISER DIAGRAM SHOWS THE ICE MAKER LINE IN THE WALL.
 CORRELATE. SECTION 106.1.1.
  
 45. SHT P-12 UNIT "C" WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE WASH MACHINE CONNECTS
 TO THE WATER MAIN. PLEASE CORRELATE. SECTIONS 106.1.1 &
 604.
  
 46. SECOND SHT P-11 UNIT "C" DOUBLE RISER DIAGRAM
 MISLABELED A LAV FOR A TUB & A LAV FOR A BIDET AND DOES
 NOT REFLECT THE PIPING AT THE TUB/LAV IN THE MASTER
 BATH.--PIPING AT THE TUB & LAV DOES NOT REFLECT THE
 FLOOR PLAN.--TUB INDICATED AS LAV IN TUB BATH BY
 WASH MACHINE.PLEASE CORRELATE. SECTION 106.1.1 &
 TABLE 709.1.
  
 47. SECOND SHT P-12 INDICATES UNIT "CH" MOD. 1& 2
 FIRST, SECOND & THIRD FLOORS, BUT THE RISER DIAGRAM IS
 FOR MOD. 3. PLEASE CLARIFY. SECTION 106.1.1.
  
 48. THE SEQUENCE OF SHEETS SUBMITTED IS AS FOLLOWS:
 P-11, P-12, P-11, P-12, P-13, P-14 & P-15. PLEASE
 NUMBER SHEETS IN A SEQUENCE THAT CAN BE LOGICALLY
 FOLLOWED. SECTIONS 106.1.3 & 106.1.3.
  
 49. SHT P-15 SHOWS THE SAME INFORMATION THAT SHEET P-13
 SHOWS. PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.3.
  
 50. SHT P-14 UNITS "E" FLOOR PLANS & "E" GROUND FLOOR
 PLANS DO NOT SHOW THE WATER LINES TO THE ICE MAKERS
 THAT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.--
 UNIT "E" GROUND FLOOR PLAN SHOWS HOT & COLD WATER
 SUPPLY TO THE WATER CLOSET IN THE 2ND BATHROOM. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 51. SECOND SHT P-15 UNIT "F" FLOOR PLAN DOES NOT SHOW
 THE WATER LINE TO THE ICE MAKER THAT REFLECTS THE RISER
 DIAGRAM.--UNIT "F" GROUND FLOOR PLAN WATER RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN AT THE 2ND
 BATHROOM. PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 52. SHT P-16 UNIT H FLOOR PLAN. PLEASE SHOW PIPING TO
 THE HOSE BIBB TO REFLECT THE RISER DIAGRAM. SECTIONS
 106.1.1 601.1.
  
 53. SHT P-17 ALL "J" UNITS THE WATER RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN AT THE WATER LINES TO THE
 ICE MAKERS.--UNIT "J" GROUND WATER RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN AT THE WASH MACHINE.
 --UNIT "J" FLOOR PLAN SHALL REFLECT THE RISER
 DIAGRAM. NO HOSE BIBB LINE SHOWN, NO ICE MAKER LINE
 SHOWN.--NO UNIT "J" GROUND MOD 2 FLOOR PLAN
 SUBMITTED.PLEASE CORRELATE. SECTIONS 106.1.1 &
 601.1.
  
 54. SHT P-19 UNIT "R" RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AT THE WATER LINE TO THE ICE MAKER.--
 UNIT "P" WATER RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN AT THE WATER LINE TO THE ICE MAKER, AND WHERE THE
 SHOWER IN THE MASTER BATH CONNECTS TO THE MAIN & OFFSET
 BY THE REFR.--UNIT "U" REV WATER RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN WHERE THE COLD & HOT RISERS
 CONNECT TO THE WATER MAIN. PLEASE CORRELATE. SECTIONS
 106.1.1 & 6011.1.
  
 55. SHT P-20 UNIT "TH" MOD REV 3RD FLOOR PLAN DOES NOT
 SHOW THE WATER PIPING TO THE MASTER BATH THAT REFLECTS
 THE RISER DIAGRAM.--UNIT "TH" R MOD 1 & MOD WATER
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN WHERE THE
 RISER TO THE 5TH FLOOR POWDER ROOM CONNECTS AT THE 4TH
 FLOOR. LAV SHOULD BE ON THE OTHER SIDE OF THE RISER 4TH
 FLOOR. PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 56. SHT P-21 UNITS "TH" & "TH" REV WATER RISER DIAGRAM
 DO NOT REFLECT THE FLOOR PLANS AT THE 4TH FLOOR. RISER
 IS SHOWN BEHIND THE W/C NOT TO THE LEFT SIDE OF THE LAV
 AS INDICATED ON THE RISER DIAGRAM.--UNITS "TH" &
 "TH" REV FLOOR PLANS DO NOT SHOW THE WATER PIPING TO
 THE MASTER BATH. PLEASE SHOW ALL PIPING. SECTIONS
 106.1.1 & 601.1.
  
 57. SHT P-22WATER RISERS 1 THRU 14 INDICATE WHERE THE
 CONTINUATION OF RISER CAN BE FOUND TO REFLECT THE
 PIPING ON THE 7TH FLOOR. ALSO THE OFFSETS SHOWN ON THE
 6TH FLOOR FOR ALL RISERS BUT RISER 14IS NOT SHOWN ON
 THE RISER DIAGRAMS.--RISERS 4, 6, 8 & 10 INDICATE
 1" HW (TYP) BUT SHOW 34" BELOW.--RISERS 5. 7. 9 &
 11SHOWS 3/4 HW FROM THE COLD WATER RISER AT THE 7TH
 FLOOR.--RISER 13 SHOWS 3/4" HW (TYP) BUT SHOW 1"
 BELOW.--RECREATION MEN'S BATHROOM DOES NOT REFLECT
 THE FLOOR PLAN AT THE LAV/URINAL.--PLEASE CLARIFY
 1/2" DESIGNATIONS BY THE SHOWERS. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 601.1.
  
 58. SHT P-23 INDICATE THE LOCATION OF THE WATER RISERS
 1C THRU 7C AND WATER RISERS 1T THRU 15T. UNABLE TO
 LOCATE.--UNABLE TO READ/REVIEW INFORMATION AT THE
 FAR LEFT SIDE OF THE SHEET WITHOUT TAKING THE PLANS
 APART. PLEASE MAKE ALL INFORMATION AVAILABLE.--PIPE
 SIZING AT THE GANG TOILETS SUPPLY, (1-1/2") DOES NOT
 REFLECT THE FLOOR PLAN, (2"). SECTIONS 106.1.1, 106.1.2
 & 601.1.
  
 59. SHT P-24 RISERS 2, 4 & 6 DO NOT REFLECT THE FLOOR
 PLAN AT THE GROUND FLOOR.--RISER 11 DOES NOT
 REFLECT THE FLOOR PLAN.--RISER 16CLEANOUTS ARE
 REQUIRED ON THE VENT PRIOR TO CONNECTING TO THE VENT
 STACK ON ISLAND VENTS. SECTION 913.3 (SEE FIG. 913.2).
 --RISER 19 SHOWS A SHOWER ON THE FIRST FLOOR BUT THE
 FLOOR PLAN SHOWS A TUB.--RISERS 20, 29, 38 & 47 DO
 NOT REFLECT THE FLOOR PLAN AT THE 5TH FLOOR. --RISERS
 21, 30, 39 & 48 THREE INCH PIPE REQUIRED ON THE BRANCH
 LINE TO THE WASH MACHINES. SECTION 406.3.--RISERS
 23, 32 & 41 DO NOT REFLECT THE FLOOR PLAN AT THE 5TH
 FLOOR.PLEASE CORRLEATE. SECTIONS 106.1.1, 701.1 &
 TABLES 710.1(1), 710.1(2).
  
 60. SHT P-25 RISERS 25, 34 & 43 CLEANOUTS ARE REQUIRED
 ON THE VENT PRIOR TO CONNECTING TO THE VENT STACK ON
 ISLAND VENTS. SECTION 913.3 (SEE FIG. 913.2). RISERS
 SHOW SHOWERS ON THE 6TH FLOOR, BUT FLOOR PLAN SHOWS
 TUBS.--RISERS 28, 37, 46 DO NOT REFLECT THE FLOOR
 PLAN. RISER SHOWS SHOWERS 1ST FLOOR BUT FLOOR PLAN
 SHOWS TUBS.--RISER 55 DOES NOT REFLECT THE FLOOR
 PLAN 1ST FLOOR. FLOOR PLAN SHOWS TUB/SHOWER IN BOTH
 BATHROOMS.--RISERS 52 & 65 CLEANOUTS ARE REQUIRED
 ON THE VENT PRIOR TO CONNECTING TO THE VENT STACK ON
 ISLAND VENTS. SECTION 913.3 (SEE FIG. 913.2).--
 RISER 52 DOES NOT REFLECT THE FLOOR PLAN AT THE 5TH &
 6TH FLOORS.--RISERS 67 & 68 DO NOT REFLECT THE
 FLOOR PLAN AT THE 2ND FLOOR FOR RISER 68 AND FOR THE
 OFFSET ABOVE THE FIRST FLOOR ON RISER 67 PLUS RISER 67
 SHOWS TUBS BUT THE FLOOR PLAN SHOWS SHOWERS.--
 RISER 70 TOILET ROOM 4TH FLOORWILL REVIEW FOR CODE
 COMPLIANCE WHEN 1/4" FLOOR PLAN IS FOUND. (SEE NOTE
 P-5.2).--BOILER ROOM DETAIL SHOWS A FLOOR DRAIN FOR
 INDIRECT WASTE. FLOOR DRAINS ARE NOT APPROVED WASTE
 RECEPTORS. A FLOOR SINK OR HUB DRAIN WILL BE REQUIRED
 PER SECTIONS 802.3 & 802.3.2. ALSO THE INDIRECT WASTE
 SHALL BE LOCATED TO NOT BECOME A TRIPPING HAZARD.
 PLEASE CORRELATE.SECTIONS 106.1.1, 701.1 & TABLES
 710.1(1), 710.1(2).
  
 61. SHT P-26. RISER 18 INDICATES NOTE TWO WHICH STATES
 "FOR CONTINUATION REFER TO VENTILATION PIPING. SEE
 HORIZONTAL DIAGRAM ON SHT P-28". SHT P-28 AS SUBMITTED
 IS STORM RISERS. PLEASE CLARIFY. SECTION 106.1.1--
 RISER 114 DOES NOT REFLECT THE FLOOR PLAN AT THE 5TH
 LEVEL. (DRINKING FOUNTAINS NOT SHOWN).--ALL "C" AND
 "T" RISERS HAVE NOT BEEN REVIEWED AT THIS TIME BECAUSE
 THE PIPING ON THE FLOOR PLANS IS NOT SHOWN ON THE FLOOR
 WITH THE FIXTURES AND IS VERY HARD TO FOLLOW. PUT
 PUPING ON THE FLOOR PLAN WITH THE FIXTURES. (SEE POOL
 BATH PIPING LAYOUT ON SHT P-5.1 AS AN EXAMPLE).
 SECTIONS 106.1.1 &701.1. TABLES 710.1(1) & 710.1(2).
  
 62. SHTS P-24, P-25 & P-26 INDICATE THE TOTAL DFU'S AND
 TOTAL DEVELOPED LENGTH FOR COMBINED VENTS SUCH AS
 RISERS 1 THRU 5, RISERS 6 THRU 13, RISERS 14 THRU 19
 ETC. TABLE 916.1.
  
 63. SHT P-27A DOES NOT REFLECT THE FLOOR PLAN AT RISERS
 89, 93 & 94.--TWO RISERS NUMBERED 63. (ALSO SEE SHT
 P-001) PLEASE CORRELATE/CLARIFY SECTIONS 106.1.1 &
 701.1.
  
 64. SUBMIT MANUF SPECIFICATION FOR THE SUMP PUMPS. SHOW
 LISTING. (SEE SHT P-30). SECTION 303.4.
  
 65. SHT P-27B RISER DIAGRAM INDICATES 5 SUMP PUMPS.
 MORE INFORMATION IS REQUIRED. PLEASE INDICATE WHAT
 LEVEL THESE SUMP PUMPS ARE LOCATED, INDICATE WHAT WILL
 BE PUMPED OUT AND SHOW COMPLIANCE WITH SECTION 712.2.
 IS THERE A LEVEL LOWER THAN THE LOWER GARAGE? PLEASE
 CLARIFY. SECTION 106.1.2.--RISER DOES NOT REFLECT
 THE FLOOR PLAN AT RISERS 1T, 2T, C8, C10, 27T, 25T,
 C12, 29T & CT1. PLEASE CORRELATE. SECTIONS 106.1.1 &
 701.1.
  
 66. SHT P28 MOST INFORMATION IS NOT LEGIBLE WITHOUT THE
 AID OF A MAGNIFYING GLASS. SECTIONS 106.1.1 & 106.1.2.
 PLEASE SUBMIT INFORMATION THAT IS OF SUFFICIENT
 CLAIRTY.
  
 67. SHTS P28A THRU P-28D. INDICATE THE RISER NUMBERS SO
 THE RISERS CAN BE TRACKED THRU THE BUILDING. INDICATE
 WHERE THE RISER CONTINUES THAT IS NOT SHOWN ON THE
 SHEET. SOME OF THE INFORMATION CONTINUES AT THE TOP OF
 THE SHEET, SOME TO THE SIDE, AND SOME INFORMATION
 CONTINUES AT THE BOTTOM OF THE SHEET BUT DOES NOT
 INDICATE WHERE THE CONTINUED PIPE CAN BE LOCATED.
 UNABLE TO TRACK THE PIPING TO VERIFY PIPE SIZE OR
 SQUARE FOOTAGE BEING DRAINED. SECTIONS 106.1.1, 106.1.2
 & 1101.1. ALSO TABLES 1106.2 & 1106.3.
  
 68. SHT P-28E INDICATE RISER NUMBER RISER TO TRACK THE
 RISER THRU THE BUILDING AND TO VERIFY PIPE SIZE AND
 SQUARE FOOTAGE BEING DRAINED.--CLARIFY CONNECTION
 THAT INDICATES 12"-1970, 12"-25610, 1-1/4" CD & 1-1/2"
 CD.--CONDENSATE TO DRAIN SEPARATELY FROM THE
 BUILDING.--NUMEROUS PIPE SIZES THAT ARE NOT
 INDICATING WHAT THEY ARE ASSOCIATED WITH. PLEASE
 CLARIFY. SECTIONS 106.1.1, 106.1.2 & 1101.1. ALSO TABLE
 1106.3.
  
 69. SHT P-28F HORIZONTAL GARAGE PIPING ISOMETRIC
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN TO THE 4"
 TRENCH DRAINS/SUMP PUMPS 21 & 22. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 1101.1.
  
 70. SHT P-29 THE FOLLOWING INFORMATION IS REQUIRED FOR
 THE SEPARATE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE ISOMETRIC RISER DIAGRAM SUBMITTED
 DOES NOT SHOW ALL LENGTHS OF PIPE, ALL SECTIONS OF
 PIPE, ALL RISERS AND DOES NOT REFLECT THE FLOOR PLAN.
 SOME BRANCH LINES DO NOT IDENTIFY THE APPLIANCES
 CONNECTING TO THE BRANCH LINE. DELETE ALL UNIONS FROM
 THE FUTURE LINES IN THE KITCHENS. FOR ALL FUTURE
 APPLIANCES, A SHUT OFF VALVE, A NIPPLE AND A CAP ARE
 REQUIRED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. - NOT ALL PIPE
 SIZES SHOWN.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - NOT ALL BTU LOADS ARE INDICATED.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED WHEN
 COMMENT "A" IS ADDRESSED.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. SHOW ALL CUT SECTIONS AND CORRESPONDING LENGTHS AS
 WELL AS THE TOTAL DEVELOPED LENGTH DOWNSTREAM OF EACH
 REGULATOR.
  
 I. RISER DOES IT MEET CODE REQUIREMENTS. REGULATORS ARE
 REQUIRED AT ALL FIXTURES OR GROUP OF FIXTURES. MANY
 INDIVIDUAL FIXTURES FIXTURES SHOW NO REGULATORS. A SHUT
 OFF VALVE IS REQUIRED UPSTREAM OF EACH REGULATOR WITH A
 UNION DOWNSTREAM OF EACH SHUT OFF VALVE. SECTION
 409.4.
  
 J. NOTE ON SHT P-29 INDICATES "3/4 INCH GAS UP & DOWN"
 PLEASE CLARIFY DOWN TO WHERE? SECTION 106.1.1.
  
 K.RISER DOES NOT REFLECT THE FLOOR PLAN. RISERS SHOWN
 FOR THE GAS BBQ GRILL SHOWN ON THE 7TH FLOOR SHOW THE
 FUTURE CONNECTIONS FOR THE KITCHEN OF THE UNITS.
 RISERS FOR THE KITCHEN SHOW THE BBQ GRILLS. PLEASE
 CORRELATE RISERS AND FLOOR PLAN. SECTION 106.1.1 &
 TABLE 402.4(3).
  
 L. SUBMIT MANUF SPECIFICATION SHEETS FOR THE
 REGULATORS. SHEETS SHALL SHOW LISTING AND THE MODEL
 NUMBER OF THE REGULATOR SHALL BE INDICATED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]