Plan Review Notes
Plan Review Notes For Permit 07120262
Permit Number 07120262
Review Stop M
Sequence Number 1
Notes
Date Text
2008-03-10 16:20:30REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: ONE SET OF MECHANICAL PLANS HAVE BEEN MARKED UP
 DURING THE COURSE OF THIS REVIEW TO ASSIST IN
 DETERMINING THE AREAS BEING ADDRESSED IN THESE REVIEW
 COMMENTS.
  
 1. PG AC-0.1: GARAGE VENTILATION SYSTEM, FLOOR PLAN
 DOES NOT SHOW ANY SOURCE OF MAKEUP AIR FOR GARAGE
 EXHAUST FANS. PROVIDE SUPPLY AIR OR MAKEUP AIR IN
 ACCORDANCE WITH FBCM 403.1.
  
 2. PG AC-0.1, AC-1.1 AND AC-1.2: PLAN CALLS FOR SUPPLY
 DUCT TO PENETRATE FLOOR/CEILING ASSEMBLY TO SUPPLY AIR
 FOR LOWER ELEVATOR LOBBIES. PLEASE COORDINATE PLANS AS
 PG AC0.1 CALLS FOR 6X6 DUCT WHILE PG AC-1.1 CALLS FOR
 6X4 DUCT.
  
 3. PG AC-0.1 AND AC-1.4: FLOOR PLAN SHOWS CONDENSER
 WATER PIPES PENETRATING A RATED STAIR ENCLOSURE AT
 STAIR #11. PENETRATIONS INTO AND OPENINGS THROUGH AN
 EXIT ENCLOSURE ARE PROHIBITED IN ACCORDANCE WITH FBCB
 1019.1.2.
  
 4. PG AC-1.1 AND AC-3.1: DUCT RISER PA-1 SHOWS TWO DUCT
 PENETRATIONS WITH ONLY ONE FIRE/SMOKE DAMPER (FSD)
 SHOWN ON FLOOR PLAN. SHAFT ENCLOSURES THAT ARE
 PERMITTED TO BE PENETRATED BY DUCTS AND AIR TRANSFER
 OPENINGS SHALL BE PROTECTED WITH APPROVED FIRE AND
 SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING AND FBCM 607.5.5.1. THE SPECIFIC LOCATION AND
 INSTALLATION DETAILS OF EACH FIRE DAMPER AND SMOKE
 DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED ON THE
 BUILDING PLANS BY THE DESIGNER IN ACCORDANCE WITH FBCM
 607.8.
  
 5. PG AC-1.1 AND AC-1.2: ELEVATOR MACHINE ROOM IS SHOWN
 ON CORRIDOR WITH UNIT AC-7 AND BEING CONDITIONED BY
 AC-7. ELEVATOR MACHINE ROOMS THAT CONTAIN SOLID-STATE
 EQUIPMENT FOR ELEVATOR OPERATION SHALL BE PROVIDED WITH
 AN INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEM
 TO PROTECT AGAINST THE OVERHEATING OF THE ELECTRICAL
 EQUIPMENT IN ACCORDANCE WITH FBCB 3006.2. THIS
 CONDITION HAPPENS SEVERAL TIMES THROUGHOUT THE
 BUILDING. SHOW HOW THESE ROOMS ARE TO BE
 VENTILATED/CONDITIONED IN ACCORDANCE WITH THIS SECTION.
 ALSO, WHERE STANDBY POWER IS CONNECTED TO ELEVATORS,
 THE MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL
 BE CONNECTED TO THE STANDBY POWER SOURCE IN ACCORDANCE
 WITH FBCB 3003.1.4.
  
 6. PG AC-1.1 AND AC-1.2: WHERE SUPPLY DUCTS PENETRATE
 CORRIDOR FLOOR TO ENTER GARAGE, THESE PENETRATIONS
 SHALL BE PROTECTED WITH FIRE/SMOKE DAMPERS (FSD) IN
 ACCORDANCE WITH FBCM 607.5.4.
  
 7. PG AC-1.1, AC-1.2 AND THROUGHOUT BUILDING: OUTSIDE
 AIR INTAKES ARE SHOWN WITH ONLY MANUAL VOLUME DAMPERS.
 OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE.
 GRAVITY (NON-MOTORIZED) DAMPERS ARE ACCEPTABLE IN
 SYSTEMS WITH A DESIGN OUTSIDE AIR INTAKE CAPACITY OF
 300 CFM OR LESS. PROVIDE SHUTOFF DAMPER CONTROLS IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. GRAVITY DAMPERS
 ARE ACCEPTABLE FOR ALL BUILDING EXHAUST SYSTEMS.
  
 8. PG AC-1.3: OUTSIDE AIR INTAKE FOR UNIT AC-10 IS
 LOCATED AT THE DRIVEWAY ENTRANCE TO THE PARKING GARAGE.
 MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS IN ACCORDANCE WITH FBCM 401.5.1.
  
 9. PG AC-1.3: WOMEN?S RESTROOM EF-3 DOES NOT PROVIDE
 ADEQUATE VOLUME OF EXHAUST. FBCM TABLE 403.3 CALLS FOR
 50 CFM PER WATER CLOSET AND 50 CFM PER SHOWER HEAD FOR
 A TOTAL OF 250 CFM. EF-3 IS SHOWN TO PROVIDE 200 CFM.
 PROVIDE REQUIRED EXHAUST IN ACCORDANCE WITH THIS
 SECTION.
  
 10. PG AC-2.3: RESTROOMS BY STAIR #8, EACH RESTROOM
 SHOWS 100 CFM OF SUPPLY WITH 95 CFM OF EXHAUST. WHERE
 MECHANICAL EXHAUST IS REQUIRED BY TABLE 403.3,
 RECIRCULATION OF AIR FROM SUCH SPACES SHALL BE
 PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES SHALL BE
 EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT REQUIRED
 BY TABLE 403.3 IN ACCORDANCE WITH FBCM 403.2.1(3). SHOW
 EXHAUST TO BE EQUAL OR GREATER THAN THE AIR BEING
 SUPPLIED TO THE RESTROOMS.
  
 11. PG AC-2.3, AC-3.3 AND AC-4.3: SUPPLY RISER PA-2
 DUCT PENETRATION IS MISSING THE FSD. SHAFT ENCLOSURES
 THAT ARE PERMITTED TO BE PENETRATED BY DUCTS AND AIR
 TRANSFER OPENINGS SHALL BE PROTECTED WITH APPROVED FIRE
 AND SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING AND FBCM 607.5.5.1. THE SPECIFIC LOCATION AND
 INSTALLATION DETAILS OF EACH FIRE DAMPER AND SMOKE
 DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED ON THE
 BUILDING PLANS BY THE DESIGNER IN ACCORDANCE WITH FBCM
 607.8.
  
 12. PG AC-3.3: SUPPLY DUCTS IN RESTROOMS ARE MISSING
 SIZES. PLEASE CORRECT.
  
 13. PG AC-3.4: 24X24 SUPPLY AND RETURN DUCTS FROM AC-13
 BELOW ARE PENETRATING A RATED HORIZONTAL ASSEMBLY. DUCT
 AND AIR TRANSFER OPENINGS CONSTRUCTED OF APPROVED
 MATERIALS IN ACCORDANCE WITH THIS CODE THAT PENETRATE A
 FIRE-RESISTANCE-RATED FLOOR/CEILING ASSEMBLY THAT
 CONNECTS NOT MORE THAN TWO STORIES IS PERMITTED WITHOUT
 SHAFT ENCLOSURE PROTECTION PROVIDED A FIRE DAMPER IS
 INSTALLED AT THE FLOOR LINE IN ACCORDANCE WITH FBCM
 607.6.1.
  
 14. PG AC-5.2: EF-3 IN RESTROOMS IS DISCHARGING INTO
 THE BOILER ROOM RATHER THAN TO THE OUTDOORS. THE AIR
 REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM SHALL BE
 DISCHARGED OUTDOORS IN ACCORDANCE WITH FBCM 501.2.
 ALSO, THE EXHAUST OUTLET DUCT IS PENETRATING A 2-HOUR
 RATED WALL WITHOUT AN OPENING PROTECTIVE. DUCT
 PENETRATIONS AND AIR TRANSFER OPENINGS IN FIRE BARRIERS
 SHALL BE PROTECTED WITH APPROVED FIRE DAMPERS INSTALLED
 IN ACCORDANCE WITH THEIR LISTING AND FBCM 607.5.2.
 NOTE: PG G-0.03 CALLS FOR BOILER ROOM TO HAVE 2-HOUR
 SEPARATION.
 ALSO, WILL THERE BE ANY PROVISIONS MADE FOR VENTING AND
 COMBUSTION AIR FOR THE BOILER ROOM?
  
 15. PG AC-5.4: CONDENSER WATER PIPES FROM COOLING
 TOWERS ARE SHOWN PENETRATING STAIR #12 ENCLOSURE.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED IN ACCORDANCE WITH FBCB
 1019.1.2.
  
 16. PG AC-7.1 AND AC-7.2: ROOMS ADJACENT TO CORRIDORS
 ARE LABELED AS ?MECH? ROOMS. IF THESE ARE ELEVATOR
 MACHINE ROOMS, AN INDEPENDENT VENTILATION OR AIR
 CONDITIONING SYSTEM IS REQUIRED FOR THESE ROOMS IN
 ACCORDANCE WITH FBCB 3006.2.
  
 17. PG AC-7.1, AC-7.2 AND THROUGHOUT BUILDING: DUCTS
 AND AIR TRANSFER OPENINGS WHICH PENETRATE FIRE RATED
 CORRIDOR ASSEMBLIES SHALL BE PROTECTED WITH SMOKE
 DAMPERS IN ACCORDANCE WITH FBCM 607.5.4 ALONG WITH FIRE
 DAMPERS IN ACCORDANCE WITH FBCM 607.5. THERE ARE
 SEVERAL DUCT PENETRATIONS AND AIR TRANSFER OPENINGS IN
 THE CORRIDORS WHICH ARE NOT PROTECTED BY SMOKE DAMPERS.
 PLEASE CORRECT. ALSO, SHOW HOW SMOKE DAMPERS ARE TO BE
 ACTUATED IN ACCORDANCE WITH FBCM 607.5.4.1.
  
 18. PG AC-8 UNIT A FLOOR PLAN: BEDROOMS 2 AND 3 SHOW
 TWO TRANSFER DUCTS COMBINING INTO ONE. THE SIZE OF THE
 COMBINED DUCT AND GRILL ARE MISSING FROM THE PLAN.
 PLEASE CLARIFY.
 NOTE: THE DUCT SHALL BE SIZED TO PROVIDE BALANCED
 RETURN IN ACCORDANCE WITH FBCM 601.4. THE COMBINED DUCT
 SIZE SHALL BE LARGE ENOUGH TO CARRY THE AIR FROM BOTH
 BEDROOMS.
  
 19. PG AC-8 UNIT A FLOOR PLAN: 6X6 SUPPLY DROP IN
 POWDER ROOM IS BEING FED FROM A 14X8 RETURN DUCT.
 PLEASE CLARIFY. THE SIZE OF THE FLEX DUCT IS ALSO
 MISSING FROM THE PLANS. AN AIR DISTRIBUTION SYSTEM
 SHALL BE DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
 20. PG AC-8 UNIT A-GROUND FLOOR PLAN: THE RETURN AIR
 TRANSFER IS TOO SMALL TO MEET THE BALANCED RETURN AIR
 EXCEPTIONS UNDER FBCM 601.4. IF TRANSFERS ARE NOT
 DESIGNED TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE
 REQUIRED AT FINAL INSPECTION TO VERIFY A PRESSURE
 DIFFERENTIAL OF 0.01 INCHES WC OR LESS.
 NOTE: THIS CONDITION OCCURS IN SEVERAL APARTMENTS AND
 SEVERAL MORE APARTMENTS HAVE MISSING DUCT SIZES, THUS
 LEAVING THE SIZE OF RETURN TRANSFER DUCTS UNDETERMINED.
 THE ABOVE APARTMENT IS USED AS AN EXAMPLE AND EACH
 INSTANCE WILL NOT BE POINTED OUT IN THIS REVIEW.
 HOWEVER, ONE SET OF PLANS HAS BEEN MARKED TO INDICATE
 AREAS WHERE THIS CONDITION OCCURS.
  
 21. PG AC-8 THROUGH AC-23: WITH A FEW EXCEPTIONS, DRYER
 EXHAUST DUCTS ON THESE PAGES EXCEED THE MAXIMUM ALLOWED
 LENGTH OF 25 FEET. THE MAXIMUM LENGTH IS FURTHER
 REDUCED BY BENDS IN ACCORDANCE WITH FBCM 504.6.1.
 EXCEPTION: WHERE THE MAKE AND MODEL OF THE CLOTHES
 DRYER TO BE INSTALLED IS KNOWN AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS FOR SUCH DRYER ARE PROVIDED
 TO THE CODE OFFICIAL, THE MAXIMUM LENGTH OF THE EXHAUST
 DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED
 TO BE IN ACCORDANCE WITH THE DRYER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. PROVIDE DRYER MANUFACTURER?S
 INSTRUCTIONS FOR REVIEW OR SHOW THE DRYER EXHAUST DUCT
 LENGTH TO BE IN COMPLIANCE WITH THIS SECTION.
  
 22. PG AC-09: DUCT AND GRILL SIZES MISSING FROM RETURN
 AIR TRANSFERS IN BOTH APARTMENT FLOOR PLANS. PLEASE
 CORRECT AND SHOW COMPLIANCE WITH FBCM 601.4.
  
 23. PG AC-10 UNIT C-GROUND: A) RETURN DUCT FROM BEDROOM
 #2 IS MISSING SIZE. SHOW COMPLIANCE WITH FBCM 601.4.
 B) 6X6 SUPPLY DROP IN BEDROOM #2 CLOSET HAS NO DUCT.
 AIR DISTRIBUTION SYSTEMS SHALL BE DESIGNED AND
 INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF AIR IN
 ACCORDANCE WITH FBCM 603.1.
 C) SUPPLY DROP IN BATHROOM #2 IS MISSING DUCT SIZE, CFM
 AND GRILL DESIGNATION. AIR DISTRIBUTION SYSTEMS SHALL
 BE DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
 24. PG AC-10 UNIT C-GROUND MOD 2: THE 16X8 RETURN DUCT
 PENETRATIONS IN CORRIDOR SHALL BE PROTECTED BY FIRE AND
 SMOKE DAMPERS IN ACCORDANCE WITH FBCM 607.5.4 UNLESS
 THE DUCT IS DESIGNED AND INSTALLED IN ACCORDANCE WITH
 EXCEPTION #3: SMOKE DAMPERS ARE NOT REQUIRED IN
 CORRIDOR PENETRATIONS WHERE THE DUCT IS CONSTRUCTED OF
 STEEL NOT LESS THAN 0.019 INCH (0.48 MM) IN THICKNESS
 AND THERE ARE NO OPENINGS SERVING THE CORRIDOR. SHOW
 COMPLIANCE WITH EITHER THE SMOKE DAMPER REQUIREMENTS OR
 THE EXCEPTION. IN EITHER CONDITION FIRE DAMPERS ARE
 REQUIRED IN ACCORDANCE WITH FBCM 607.5.3.
  
 25. PG AC-10 UNIT C AND UNIT C-REV FLOOR PLANS: A)
 RETURN DUCT FROM AC CLOSET INTO GREAT ROOM IS MISSING
 SIZE. PLEASE CORRECT AND SHOW COMPLIANCE WITH FBCM
 601.4.
 B) 6X6 50 CFM DUCTS PENETRATING CORRIDOR WALLS SHALL BE
 PROTECTED WITH FIRE AND SMOKE DAMPERS IN ACCORDANCE
 WITH FBCM 607.5.4.
  
 26. PG AC-11: SEVERAL RETURN AND TRANSFER DUCT GRILLS
 ARE MISSING SIZE. PLEASE CLARIFY AND SHOW COMPLIANCE
 WITH FBCM 601.4.
  
 27. PG AC-11: 20X8 RETURN DUCT PENETRATIONS IN CORRIDOR
 SHALL BE PROTECTED BY FIRE AND SMOKE DAMPERS IN
 ACCORDANCE WITH FBCM 607.5.4 UNLESS THE DUCT IS
 DESIGNED AND INSTALLED IN ACCORDANCE WITH EXCEPTION #3:
 SMOKE DAMPERS ARE NOT REQUIRED IN CORRIDOR PENETRATIONS
 WHERE THE DUCT IS CONSTRUCTED OF STEEL NOT LESS THAN
 0.019 INCH (0.48 MM) IN THICKNESS AND THERE ARE NO
 OPENINGS SERVING THE CORRIDOR. SHOW COMPLIANCE WITH
 EITHER THE SMOKE DAMPER REQUIREMENTS OR THE EXCEPTION.
 IN EITHER CONDITION FIRE DAMPERS ARE REQUIRED IN
 ACCORDANCE WITH FBCM 607.5.3.
  
 28. PG AC-11: AC-2 AND AC-6 ARE SHARING A COMMON RETURN
 AIR PLENUM AND HAVE A COMBINED CAPACITY IN EXCESS OF
 2000 CFM. WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE
 COMMON SUPPLY OR RETURN AIR DUCTS OR PLENUMS WITH A
 COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM, THE
 RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH
 SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1 (SEE
 FBCM 606.2.2).
 NOTE: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH FBCM 606.4.1.
  
 29. PG AC-12AND AC-13 2ND FLOOR: A) RETURN DUCT AND
 GRILL FROM AC CLOSET MISSING SIZES. PLEASE CORRECT AND
 SHOW COMPLIANCE WITH FBCM 601.4.
 B) FLEX SUPPLY DUCTS ALL FLOORS ARE MISSING SIZES ON
 FLOOR PLANS. AIR DISTRIBUTION SYSTEMS SHALL BE DESIGNED
 AND INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF
 AIR IN ACCORDANCE WITH FBCM 603.1.
  
 30. PG AC-12 AND AC-13 3RD FLOOR: BEDROOMS DO NOT SHOW
 ANY DUCTS OR TRANSFERS FOR RETURN AIR. SHOW BALANCED
 RETURN IN THESE ROOMS IN ACCORDANCE WITH FBCM 601.4.
  
 31. PG AC-14 BOTH FLOOR PLANS: A) SEVERAL SUPPLY AND
 RETURNS ARE MISSING DUCT AND/OR GRILL SIZES ON FLOOR
 PLANS.
 B) E GROUND UNIT 14X8 RETURN TRANSFER IN BEDROOM #2 IS
 TOO SMALL TO MEET THE BALANCED RETURN EXCEPTIONS IN
 FBCM 601.4. SHOW HOW BALANCED RETURN IS TO BE ACHIEVED
 IN THIS ROOM.
 C) UNIT E FLOOR PLAN SHOWS ONE 14X8 DUCT CARRYING THE
 RETURN FOR TWO BEDROOMS. SHOW HOW BALANCED RETURN IS TO
 BE ACHIEVED FOR THESE ROOMS IN ACCORDANCE WITH FBCM
 601.4.
  
 32. PG AC-15 UNIT F: A) SUPPLY DUCT SIZE MISSING FOR
 RIGID DUCT IN KITCHEN AND FLEX DUCT FEEDING CORRIDOR.
 SHOW MISSING SIZES. AIR DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
 B) RETURN DUCT SIZES MISSING AT AC CLOSET AND MASTER
 BEDROOM. SHOW MISSING SIZES AND DEMONSTRATE COMPLIANCE
 WITH THE BALANCED RETURN AIR REQUIREMENTS OF FBCM
 601.4.
  
 33. PG AC-15 UNIT F GROUND: FLOOR PLAN SHOWS 14X6
 TRANSFER DUCT FOR THE MASTER BEDROOM. THIS IS TOO SMALL
 IN ACCORDANCE WITH EXCEPTION #3 OF FBCM 601.4 WHICH
 REQUIRES ALL DROPS IN THE MASTER SUITE TO BE INCLUDED.
 SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN THIS AREA
 IN ACCORDANCE WITH THIS SECTION.
  
 34. PG AC-16: UNITS G AND H DUCT SIZE MISSING ON RETURN
 FROM AC CLOSETS. SHOW COMPLIANCE WITH FBCM 601.4. ALSO,
 SUPPLY IN KITCHEN OF UNIT G IS MISSING SIZE. PLEASE
 CLARIFY.
  
 35. PG AC-17: ALL J UNITS, RETURN FROM AC CLOSETS
 MISSING DUCT AND GRILL SIZES. UNIT M RETURN DUCT FROM
 AC CLOSET IS MISSING SIZE. SHOW COMPLIANCE WITH FBCM
 601.4.
  
 36. PG AC-18: UNIT N AND UNIT N GROUND, SEVERAL SUPPLY
 AND RETURN DUCTS ARE MISSING SIZES. PLEASE CLARIFY
 SHOWING COMPLIANCE WITH FBCM 601.4 AND 603.1.
  
 37. PG AC-19: UNIT P AND UNIT P GROUND, RETURN TRANSFER
 DUCTS FROM MASTER BEDROOMS ARE TOO SMALL IN ACCORDANCE
 WITH EXCEPTION #3 OF FBCM 601.4 WHICH REQUIRES ALL
 DROPS IN THE MASTER SUITE TO BE INCLUDED. SHOW HOW
 BALANCED RETURN IS TO BE ACHIEVED IN THIS AREA IN
 ACCORDANCE WITH THIS SECTION.
  
 38. PG AC-19: UNIT R: RETURN DUCT IS MISSING FROM
 MASTER BEDROOM. ALSO, RETURN DUCT SIZE FROM AC CLOSET
 IS MISSING. SHOW COMPLIANCE WITH FBCM 601.4.
  
 39. PG AC-19: UNIT U, RETURN TRANSFER DUCTS MISSING
 FROM TWO ROOMS. SHOW HOW BALANCED RETURN IS TO BE
 ACHIEVED IN THESE AREAS IN ACCORDANCE WITH FBCM 601.4.
 ALSO, SUPPLY DUCT INTO KITCHEN IS MISSING SIZE. PLEASE
 CLARIFY. FBCM 603.1.
  
 40. PG AC-20: RETURN DUCT BETWEEN BEDROOMS 2 AND 3 IS
 MISSING DUCT AND GRILL SIZES. ALSO, SEVERAL SUPPLY FLEX
 DUCTS ARE MISSING SIZES. SUPPLY DUCT TO POWDER ROOM IS
 CONNECTED TO 14X8 RETURN AIR TRUNK LINE. SHOW BALANCED
 RETURN IN ACCORDANCE WITH FBCM 601.4. ALSO, AIR
 DISTRIBUTION SYSTEMS SHALL BE DESIGNED AND INSTALLED TO
 SUPPLY THE REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE
 WITH FBCM 603.1.
  
 41. PG AC-21: SEVERAL SUPPLY AND RETURN DUCTS ARE
 MISSING DUCT AND GRILL SIZES. ALSO, RETURN FROM MASTER
 SUITE IS TOO SMALL IN ACCORDANCE WITH FBCM 601.4
 EXCEPTION #3.
  
 42. PG AC-22: A) SUPPLY DUCT SIZE MISSING FOR RIGID
 DUCT IN KITCHEN AND FLEX DUCTS FEEDING CORRIDOR.SHOW
 MISSING SIZES. AIR DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
 B) RETURN DUCT SIZES MISSING AT AC CLOSET AND MASTER
 BEDROOM. SHOW MISSING SIZES AND DEMONSTRATE COMPLIANCE
 WITH THE BALANCED RETURN AIR REQUIREMENTS OF FBCM
 601.4.
  
 43. PG AC-23: A) SUPPLY DUCT SIZES MISSING FROM FLEX
 DROPS IN POWDER ROOM AND AC CLOSET.
 B) SIZE IS ALSO MISSING ON RIGID DUCT IN BEDROOM #2.
 C) THE 4 INCH FLEX DUCT IN BATHROOM FOR BEDROOM #3 IS
 NOT CONNECT TO ANY SUPPLY TRUNK LINE. AIR DISTRIBUTION
 SYSTEMS SHALL BE DESIGNED AND INSTALLED TO SUPPLY THE
 REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM
 603.1.
 D) RETURN TRANSFER DUCT FOR MASTER BEDROOM IS MISSING
 SIZE AND APPEARS TO BE TOO SMALL FOR ALL SUPPLY DROPS
 IN THE MASTER SUITE. SHOW COMPLIANCE WITH FBCM 601.4.
 E) THERE IS A 6X6 SUPPLY GRILL SHOWN IN THE 1-HOUR
 RATED CEILING NEAR THE 32X20 RETURN DUCT IN THE
 CORRIDOR. WHERE DUCT SYSTEMS CONSTRUCTED OF APPROVED
 MATERIALS IN ACCORDANCE WITH THIS CODE PENETRATE A
 CEILING OF A FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/CEILING ASSEMBLY, AN APPROVED CEILING RADIATION
 DAMPER SHALL BE INSTALLED AT THE CEILING LINE IN
 ACCORDANCE WITH FBCM 607.6.2.
  
 44. PG AC-24 1ST FLOOR: CONDENSER WATER PIPES ARE SHOWN
 LOCATED IN ELEVATOR SHAFT. PLUMBING AND MECHANICAL
 SYSTEMS SHALL NOT BE LOCATED IN AN ELEVATOR SHAFT IN
 ACCORDANCE WITH FBCB 3004.5.
  
 45. PG AC-24 2ND FLOOR: A) ONE RIGID SUPPLY DUCT
 MISSING SIZE. B) THE 6 INCH FLEX DUCT BY STAIRS IS NOT
 CONNECTED TO ANY TRUNK LINE. AIR DISTRIBUTION SYSTEMS
 SHALL BE DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
 C) IT IS UNCLEAR WHETHER EF-1 IS DISCHARGING OUTSIDE OR
 INSIDE A STAIR ENCLOSURE. PLEASE CLARIFY. THE AIR
 REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM SHALL BE
 DISCHARGED OUTDOORS IN ACCORDANCE WITH FBCM 501.2.
  
 46. PG AC-24 3RD FLOOR: SUPPLY DUCT FEEDING CHASE IS
 MISSING SIZE. PLEASE CLARIFY.
  
 47. PG AC-42 4TH FLOOR: RETURN AIR TRANSFER DUCT IS
 MISSING GRILL SIZES. THE DUCT IS ALSO TOO SMALL FOR THE
 MASTER SUITE IN ACCORDANCE WITH FBCM 601.4 EXCEPTION
 #3.
  
 48. PG AC-24 5TH FLOOR: SUPPLY DUCT APPEARS TO BE
 LOCATED OUTDOORS AND CONDITIONING THE OUTDOORS. IS THIS
 DUCT INTENDED TO CONDITION THE TOILET ROOM ON THE 5TH
 FLOOR? PLEASE CLARIFY.
  
 49. PG AC-25: THE LAYERS ON THIS PAGE DO NOT
 CORRESPOND. A REVIEW OF THIS PAGE CAN NOT BE COMPLETED
 AT THIS TIME. IT IS LIKELY THAT SIMILAR ISSUES AS THOSE
 ON PG AC-24 WILL OCCUR ON THIS PAGE. PLEASE CLARIFY.
 FBC 106.1.1.
  
 50. PG AC-28: HEAT PUMP SCHEDULE, AC-6 EFFICIENCY
 RATING IS LESS THAN THE PRESCRIPTIVE MINIMUM AS
 REQUIRED BY FBCB TABLE 13-407.1.ABC.3.2B. SHOW
 COMPLIANCE WITH THIS SECTION.
  
 51. PG AC-29: RTU #2 SHALL BE EQUIPPED WITH AUXILIARY
 DRAIN PROTECTION, SUCH AS A WATER LEVEL DETECTION
 DEVICE, TO PREVENT OVERFLOW OF CONDENSATE FROM DRAINING
 INTO THE BUILDING IN ACCORDANCE WITH FBCM 307.2.3.
  
 52. PG AC-30: ABBREVIATIONS TABLE: THE ABBREVIATION OF
 MVD IS USED EXTENSIVELY ON PLANS YET IS NOT DEFINED IN
 THE TABLE. PLEASE CLARIFY.
  
 53. PG AC-30: THE OPERATING TEMPERATURE OF FIRE DAMPER
 ACTUATING DEVICES (SUCH AS FUSIBLE LINKS) SHALL BE
 APPROXIMATELY 50 DEGREES F ABOVE THE NORMAL TEMPERATURE
 WITHIN THE DUCT SYSTEM, BUT NOT LESS THAN 160 DEGREES F
 IN ACCORDANCE WITH FBCM 607.3.1.1(1). MATERIALS NOTE J
 CALLS FOR FIRE DAMPER FUSIBLE LINKS TO BE 265 DEGREES.
 IS THE AIR TEMPERATURE WITHIN THE DUCT SYSTEMS EXPECTED
 TO BE HOT ENOUGH TO JUSTIFY THE ELEVATED TEMPERATURE OF
 THESE FUSIBLE LINKS? PROVIDE SUPPORTING DOCUMENTATION
 IF NECESSARY TO DEMONSTRATE COMPLIANCE WITH THIS
 SECTION.
  
 54. PG AC-30: MATERIALS NOTE S CALLS FOR DRYER BOOSTER
 FANS. IF DRYER BOOSTER FANS ARE TO BE USED, PROVIDE
 DOCUMENTATION SHOWING THE BOOSTER FANS LISTED AND
 LABELED FOR USE IN A DRYER APPLICATION IN ACCORDANCE
 WITH FBCM 504.6. ALSO, PROVIDE DRYER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS WHICH APPROVE THE USE OF
 EXTERNAL BOOSTER FANS. DOMESTIC DRYERS SHALL BE
 EXHAUSTED IN ACCORDANCE WITH MANUFACTURER?S
 INSTALLATION INSTRUCTIONS PER FBCM 504.1.
  
 55. PG AC-30: OUTSIDE AIR CALCULATIONS ARE MISSING
 CALCULATIONS FOR ENCLOSED PARKING GARAGE VENTILATION.
 SHOW THE VENTILATION RATE REQUIRED AT BOTH THE 0.05 CFM
 PER SQ FT AND THE 1.5 CFM PER SQ FT RATES IN ACCORDANCE
 WITH FBCM SECTION 404. THERE IS NO INDICATION THAT THE
 GARAGE EXHAUST FANS WILL RUN CONTINUOUSLY AT THE 0.05
 CFM RATE AS REQUIRED BY FBCM 404.2. SHOW COMPLIANCE
 WITH THIS SECTION.
  
 56. PG AC-31: COOLING TOWER, RTUS, WATER HEATER, ALL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. ROOF-MOUNTED MECHANICAL UNITS AND
 SUPPORTS SHALL BE SECURED TO THE STRUCTURE IN
 ACCORDANCE WITH FBCM 301.13. PROVIDE DOCUMENTATION
 SHOWING ALL APPLIANCES AND EQUIPMENT IS DESIGNED AND
 CONSTRUCTED TO WITHSTAND EXPECTED WIND PRESSURES BY THE
 EQUIPMENT AND APPLIANCE MANUFACTURER. ALSO PROVIDE
 DETAILS WITH ACCOMPANYING WIND LOAD CALCULATIONS
 SHOWING HOW APPLIANCES AND EQUIPMENT ARE TO BE ATTACHED
 TO THE BUILDING STRUCTURE FOR BUILDING PLAN REVIEW IN
 ACCORDANCE WITH THIS SECTION.
  
 57. GENERAL: HOISTWAYS OF ELEVATORS PENETRATING MORE
 THAN THREE STORIES SHALL BE PROVIDED WITH A MEANS FOR
 VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE IN ACCORDANCE WITH FBCB 3004.1. HOISTWAY VENTS
 SHALL BE INSTALLED IN ACCORDANCE WITH FBCB 3004.2
 THROUGH 3004.4. ALSO, STAIR AND ELEVATOR SHAFT VENTS
 SHALL BE EQUIPPED WITH MOTORIZED DAMPERS THAT ARE
 CAPABLE OF BEING AUTOMATICALLY CLOSED DURING NORMAL
 BUILDING OPERATION AND ARE INTERLOCKED TO OPEN AS
 REQUIRED BY FIRE AND SMOKE DETECTION SYSTEMS IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.3.1.
  
 58. ENERGY CALCULATIONS: THE INPUT DATA SHOWS 99 HEAT
 PUMPS GROUPED INTO ONE ENTRY. AN EFFICIENCY RATING OF
 12.8 IS ASSIGNED TO ALL 99 HEAT PUMPS BUT THE EQUIPMENT
 SCHEDULE ON AC-28 INDICATES THAT THE HEAT PUMPS ARE OF
 VARYING EFFICIENCIES. DEMONSTRATE EFFICIENCIES IN THE
 CALCULATIONS WHICH ACCURATELY REFLECT THOSE OF THE
 EQUIPMENT BEING SPECIFIED ON THE PLANS IN ACCORDANCE
 WITH FBCB 13-103.2.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING. ALSO
 PLEASE RETURN ONE SET OF OLD/VOIDED PLANS, PREFERABLY
 THE SET WHICH WAS MARKED UP DURING THIS REVIEW, IN
 ORDER TO ASSIST IN A TIMELY REVIEW OF THE RESUBMITTED
 PLANS.
  