Plan Review Notes
Plan Review Notes For Permit 07120262
Permit Number 07120262
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-03 11:23:021. ON PAGE A-1.00 FIRST INFORMATION BOX OF EGRESS
 CAPACITY SHOULD READ 102 NOT 112.
  
 2. WRONG LIFE SAFETY CODE LISTED ON G-0.03. IT SHOULD
 READ THE FLORIDA FIRE PREVENTION CODE, 2003 LIFE SAFETY
 CODE AND NFPA 1, 2003 EDITION.
  
 3. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND
 AFTER CONSTRUCTION.
  
 4. STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 5. SUITABLE ACCESS SHALL BE PROVIDED FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 6. TEMPORARY STANDPIPE SYSTEM REQUIRED WHEN THE
 BUILDING REACHED THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 7. STAIRWELL IDENTIFICATION SIGNS REQUIRED IDENTIFYING
 FLOOR LEVEL, STAIR IDENTITY, AND TERMINUS TOP AND
 BOTTOM.
  
 8. SITE PLAN A-0.01 DOES NOT ILLUSTRATE ANY EXISTING OR
 NEW FIRE HYDRANTS.
  
 9. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6"
 HIGH WITH AT LEAST 1" WIDE NUMBERS SHALL BE PROVIDED.
  
 10. KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING.
  
 11. PLEASE INDICATE HOW THE PARKING CONTROL LIFT GATES
 COULD IMPACT EXISTING FROM THE GARAGE ON PAGE A-1.00.
  
 12. ELEVATOR WARNING SIGNS "IN CASE OF FIRE, DO NOT USE
 THE ELEVATORS"ARE REQUIRED.
  
 13. ALL TRASH CHUTES ARE TO COMPLY WITH NFPA 82.
  
 14. SEVERAL AREAS NOT IDENTIFIED ON PAGE A-2.10.
  
 15. ALL REQUIRED STAIRS ARE TO BE EQUIPPED WITH
 STANDPIPES.
  
 16. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 COMPLETE AUTOMATIC FIRE SPRINKLER SYSTEM.
  
 17. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE COMPLETE AUTOMATIC FIRE ALARM
 SYSTEM. THE AUTOMATIC FIRE SPRINKLER AND FIRE ALARM
 SYSTEM ARE TO BE MONITORED BY A UL LISTED CENTRAL
 STATION APPROVED FOR CENTRAL STATION SERVICE.
  
 18. ELECTRIC POWERED SMOKE DETECTORS ARE REQUIRED ON
 EVERY LEVEL OF THE RESIDENTIAL UNITS.
  
 19. HOW WILL THE PRIVATE ELEVATOR LOBBIES BE ACCESSED
 BY FIRE RESCUE.
  
 20. PLEASE INDICATE WHICH ELEVATORS WILL BE STRETCHER
 ACCESSIBLE.
  
 21. WHAT IS ANY TYPES OF POOL CHEMICALS WILL BE STORED
 IN THE POOL EQUIPMENT ROOM ON PAGE A-2.5.3.
  
 22. DOOR NOTES INFORMATION BOX ON PAGE A-3.10 AND OTHER
 SHEETS, NOTE # 2 IS INCORRECT. SHOULD READ SECTION 7
 NOT 5.
  
 23. DOORS APPEAR TO SWING OVER THE PROPERTY LINE ON
 PAGE A-3.16.
  
 24. DOOR SCHEDULE ON PAGE A-3.16 CONTAINS NO
 INFORMATION.
  
 25. WHAT TYPE OF FIREWALL SEPARATION EXISTS BETWEEN THE
 ONE CAR GARAGES AND OTHER PORTIONS OF THE BUILDING.
  
 26. SOME AIR CONDITIONER DOORS LOCATED IN CORRIDORS DO
 NOT APPEAR ON THE DOOR SCHEDULE.
  
 27. DETAILS REQUIRED ON EIFS MATERIAL DISPLAYED ON THE
 PLANS. EIFS NOTED ON EXTERIOR INSULATION AND FINISH
 SYSTEM AND MISCELLANEOUS DETAILS.
  
 28. ELECTRONIC SWITCHES, CHAIN AND LOCK REQUIRED ON
 FIRE LINE BACKFLOW DEVICE.
  
 29. WHAT METHODS ARE TO BE EMPLOYED ON THE EXTERIOR
 STAIRS FOR SLIP RESISTANT METHODS.
  
 30. PLEASE PROVIDE MANUFACTURERS DETAILS FOR THE CARBON
 MONOXIDE DETECTORS.
  
 31. ALL FIRE AND SMOKE DAMPERS AFTER INSTALLATION SHALL
 BE DROP TESTED TO ENSURE PROPER OPERATION.
  
 32. ON SEVERAL ELECTRICAL SHEETS, GAS GRILLS ARE NOTED.
 THESE TYPES OF GRILLS ARE NOT PERMITTED.
  
 33. ON SP-1 ONLY A SIX INCH WATER MAIN ENTERS THE
 BUILDING. PLEASE EXPLAIN HOW THIS IS ENOUGH WATER.WHAT
 SIZE IS THE FIRE PUMP.
  
 34. KNOX-BOX LOCKING CAPS ARE TO BE PROVIDED FOR THE
 FIRE DEPARTMENT CONNECTIONS.
  
 35. PLEASE EXPLAIN WHY THE OPEN AREA IS NOT CONSIDERED
 AN ATRIUM.
  
 36. THE FLOOR PLANS APPEAR TO BE VERY CONFUSING. PLEASE
 CORRECT THE PLANS AS NECESSARY TO MAKE THEM NOT AS
 CONFUSING.
  
 37. PLEASE DECLARE IF THE BUILDING WILL BE CONSIDERED A
 HIGH-RISE STRUCTURE.
  
 38. ALL RATED FIRE WALLS NEED TO BE IDENTIFIED ON THE
 PLANS.
  
 39. WHERE WILL THE STANDPIPE HOSE VALVES BE INSTALLED
 WHEN DOUBLE DOORS OPEN INTO THE STAIRWELLS.
  
 40. PRESCRIPTIVE STRENGTH REQUIREMENTS SHALL BE NOTED
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 41. PLEASE ILLUSTRATE ALL PORTABLE FIRE EXTINGUISHER
 LOCATIONS.
  
 42. PLEASE DECLARE OCCUPANCY TYPE AND USE OF THE
 BUILDING. APARTMENTS OR CONDOMINIUM AND WHAT CODE
 OCCUPANCY TYPE IS BEING ADHERED TO.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX