Plan Review Notes
Plan Review Notes For Permit 07120262
Permit Number 07120262
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-01 12:07:382008-01-01 12:07:38
  
 *** DENIED REVIEW ***
  
 ** IMPORTANT**
 THIS HAS ONLY BEEN SUBMITTED FOR *PLAN REVIEW* AND HAS
 NOT BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 AND REFLECTED ON PLANS INCLUDING ON ELECTRICAL PLANS.
 PLEASE SEE SOME ARE ALREADY SHOWN AND SOME CODES WHICH
 ARE SHOWN ARE NOT YET ADOPTED BY THE STATE OF FLORIDA.
 PLEASE BE SURE THE FOLLOWING ARE LISTED.
 2004 FBC W/2007 SUPPLEMENTS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2002 NFPA-110
 2003 NFPA-20
  
 PLEASE SEE COMMENTS FROM OTHERTRADES WHICH MAY ALSO
 REQUIRE SOME CODES TO BE LISTED.
 ** PLEASE SEE SOME SHEETS FOR EXAMPLE INDICATE THE 2006
 NFPA-101. ( NOT YET ADOPTED)
 ** PLEASE SEE CODE SECTIONS REFERENCED ON THE
 ELECTRICAL PLANS ARE NOT FROM THE CURRENT NEC IN
 EFFECT. PLEASE SEE LOAD CALCULATIONS FOR EXAMPLE WHICH
 INDICATES 220.30, YET 220.30 DOES NOT EXIST UNDER THE
 2005 NEC.
  
 2) NOTE: PLEASE SEE COMMENTS FROM THE ADDRESSING
 REVIEWER ALONG WITH ANY ADDRESSING COMMENTS FROM THE
 FIRE MARSHAL OFFICE. PLEASE BE SURE TO PLACE THE
 ADJUSTED DETERMINED ADDRESS ON TITLE BLOCKS ONCE
 FINALIZED.
 FAC 61G15-23.002, 61G1-16.004
 FBC ADMIN 106.5
  
 3) NOTE: PLEASE BE SURE ALL TITLE BLOCKS ON ALL SHEETS
 CONTAIN THE PRINTED NAME OF THE DESIGNER OF RECORD.
 PLEASE SEE FOR EXAMPLE SOME SHEETS CONTAIN WHITE-OUT
 OVER WHAT USED TO BE THE PRINTED NAME OF A DIFFERENT
 ENGINEER WORKING FOR THE SAME FIRM. THIS CAN BE SEEN ON
 SHEET E-20.
 FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE LANDSCAPE PLANS IN SETS SUBMITTED
 CONTAIN A *RUBBER-STAMP* FOR THE REQUIRED ORIGINAL
 SIGNATURE OF SAID DESIGNER. THIS IS STRICTLY PROHIBITED
 UNDER THE FLORIDA STATUTES AND REQUIRES AN
 *ORIGINAL/WET* SIGNATURE.
 PLEASE KNOW THIS COMMENT IS REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY ANY OTHER TRADE.
 FS 481.221
  
 5) NOTE: PLEASE SEE NO LIGHTING CONTROLS FOR FBC
 CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND .1.3 WAS
 SUBMITTED OR SHOWN ON PLANS.
 AS NO SYSTEMS, DEVICES, OVER RIDES ETC WAS SHOWN IN
 DESIGN, NO REVIEW OF SAID ITEMS COULD BE DONE AT THIS
 TIME.
 PLEASE SEE ALL INFORMATION FOR MAXIMUM TIMES, ANY
 SCHEDULING ETC NEEDS TO BE SUBMITTED.
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS THE
 INPUT DATA REPORT NEEDS TO COORDINATE WITH *ALL*
 LIGHTING ON PLANS, ALL, METHOD OF CONTROLS, TYPE OF
 FIXTURES AND WATTAGES.
 PLEASE SEE ONE EXAMPLE IS: THE EXTERIOR LIGHTING
 FIXTURES ON THE INPUT DATA REPORT ONLY SHOWS A TOTAL OF
 57 FIXTURES WHICH IS NOT POSSIBLE WHEN THE PLANS SHOW
 SUBSTANTIALLY MORE FIXTURES.
 PLEASE SEE FOR EXAMPLE: THE METHOD OF CONTROLS FOR
 INTERIOR LIGHTS IS ALL SHOWN AS MANUAL ON/OFF WHICH IS
 NOT POSSIBLE FOR ALL WHEN THE FBC CHAPTER 13 SECTIONS
 AS NOTED ABOVE REQUIRE AUTOMATED CONTROLS FOR THE
 BUILDING AND MOST LOCATIONS.
 ** PLEASE KNOW THESE ARE ONLY A COUPLE OF EXAMPLES,
 PLEASE BE SURE TO GO THROUGH ALL LIGHTING ON PLANS AND
 COORDINATE WITH THE INPUT DATA REPORT FOR *ALL*
 LIGHTING.
 13-415.1.A, 13-415.2, 13-415.2.ABC.1.2,
 13-415.2.ABC.1.3
  
 ** IMPORTANT** THIS OFFICE CAN NOT EXPRESS ENOUGH TO
 PLEASE SURE ALL LIGHTING ON PLANS MATCHES WITH THE
 INPUT DATA REPORT. THIS IS ONE ITEM WHICH IS TYPICAL OF
 HOLDING UP NUMEROUS PROJECTS FOR PERMIT ISSUANCE.
  
 ** THE LIGHTING CONTROLS FOR FBC WENT INTO EFFECT IN
 OCT 2005 UNDER THE 2004 FBC CODE CHANGE. THE FEDERAL
 REQUIREMENT WAS ADOPTED IN JULY 04.
  
 7) NOTE: PLEASE SEE HOUSE BILL 7121 AND POSSIBLE
 REQUIREMENTS FOR BUILDING.
  
 8) NOTE: PLEASE PROVIDE INFORMATION ON FAIL SAFE
 OPERATION OF ALL EGRESS DOORS WHICH ARE SHOWING ACCESS
 CONTROLS AND ALSO PARKING GATES.
 PLEASE SEE NFPA-101 7.2.1.5, 7.2.1.6.2.
 ** PLEASE ALSO SEE DOORS AT LOBBY ETC FOR EXAMPLES.
 SHEET E-1.4, AND NOTE #1.
  
 9) NOTE: PLEASE SEE THE PLANS INDICATE WHAT IS BEING A
 NATURAL GAS GENERATOR IN THE DESIGN OF THE BUILDING.
 PLEASE SEE 700.12B3, 701.11B3 AS ON-SITE FUEL WILL BE
 REQUIRED.
 PLEASE SEE COMMENTS FROM OTHER REVIEWS WITH RESPECT TO
 ANY ON-SITE FUEL TANKS FOR LP.
 PLEASE KNOW THE TRANSFER OF FUEL MUST BE BY AN
 AUTOMATIC MEANS AND SHALL NOT BE MANUAL.
 ** PLEASE KNOW THERE IS QUESTIONS OVER WHAT TYPE OF
 GENERATOR SYSTEM IS BEING PROPOSED. PLEASE IDENTIFY IF
 THIS IS INDEED A SYSTEM UNDER 700, 701 OR 702.
 IF PROPOSING A 702 SYSTEM THIS CHANGES COMMENTS AND
 WILL INDEED REQUIRE OTHER ADDITIONAL ITEMS/COMMENTS
 WHICH CAN NOT BE MADE AT THIS TIME.
 PLEASE ALSO SEE NFPA-110 AND CLASS OF SYSTEM.
  
 10) NOTE: PLEASE SEE THE MINIMUM CLEARANCE OF THE
 TRANSFER SWITCH HAS NOT BEEN MET PER NFPA-110 7.2.2.1
 AND NEC 110.26.
 ** REQUIRES TWICE THE DISTANCE.
  
 11) NOTE: PLEASE PROVIDE THE ELEVATION OF THE ANY EPSS
 EQUIPMENT PER 7.2.3.
 PLEASE BE SURE THE LEVELS MEET EITHER THE 100YR STORM
 LEVELS OR LEVELS BASED ON CAT 4, *SLOSH* CHARTS. ( SEA,
 LAKE, OVERLAND, SURGES BY HURRICANES).
  
 12) NOTE: PLEASE SEE NO INFORMATION WAS SUBMITTED FOR
 FIRE PUMP CONTROLLER, SIZE, LOCKED ROTOR CURRENTS ETC.
 PLEASE SEE NEC 695.3, 695.4 AND SEE NFPA-20 CHAPTERS 9
 AND 10. THE ENTIRE CHAPTERS ARE BEING REFLECTED AS NO
 INFORMATION WAS SUBMITTED.
  
 13) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT
 SHEETS FOR THE GENERATOR, ATS, FIRE PUMP, FIRE PUMP
 CONTROLLER ETC.
 PLEASE SUBMIT ALSO ANY SPECS/CUT SHEETS FOR ON-SITE
 FUEL TANKS.(REVIEWED BY OTHERS).
 NEC 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 14) NOTE: PLEASE SUBMIT COMPLETED LIGHTING
 PHOTO-METRICS FOR ALL DESIGNATED EGRESS PATH UNDER
 NORMAL AND UNDER EMERGENCY CONDITIONS.
 PLEASE SEE FOR EXAMPLE THERE ARE MANY LOCATIONS WHERE
 THERE IS NO BATTERY BACK UP FIXTURES ARE BEING SHOWN.
 FOR EXAMPLE: PLEASE SEE THE STAIRS WHICH EGRESS INTO
 COURTYARD AREA, THE HALLWAYS DO NOT CONTAIN ANY BATTERY
 BACK UP FIXTURES. PLEASE SEE STAIRS 1A, 2A, 3A, 4A, 5A
 ETC.
 FOR EXAMPLE: PLEASE SEE THE STAIRS LEADING FROM THE
 UNDERGROUND PARKING TO GROUND LEVELS OUTSIDE WHICH DO
 NOT CONTAIN ANY BACK UP FIXTURES.
 FOR EXAMPLE: PLEASE SEE EGRESS AREAS ON CABANA LEVELS.
 ** PLEASE KNOW THE LEVELS FOR ALL EGRESS STAIR AREAS IS
 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED DOWN TO 1FT
 CANDLE UNDER EMERGENCY CONDITIONS PER 7.9.2.2
 ** PLEASE KNOW AT THIS TIME AS NO LIGHTING LEVELS WERE
 SUBMITTED, ALL AREAS CAN NOT BE REVIEWED AT THIS TIME.
 THERE IS CONCERN OVER SOME OF THE EXAMPLES GIVEN AS
 THESE AREAS DO NOT APPEAR TO CONTAIN MINIMUM LIGHTING
 LEVELS UNDER NORMAL (OUTSIDE STAIRS).
 ** PLEASE SEE NFPA-101 7.8 AND 7.9
 ** PLEASE SEE FAC 61G15-33.004
 ** PLEASE KNOW THE FEW EXAMPLES GIVEN ABOVE ARE IN NO
 WAY ALL LOCATIONS IN WHICH CONCERN OF THE LIGHTING
 LEVELS ARE GIVEN.
  
 15) NOTE: PLEASE SEE THE FOLLOWING AREAS SHALL CONTAIN
 BATTERY BACK UP FIXTURES OF SOME KIND.
 THE MAIN ELECTRICAL ROOM, FIRE PUMP ROOM, GENERATOR
 ROOM.
 SOME OF THESE ROOMS MAY ALREADY CONTAIN FIXTURES LIKE
 THE FIRE PUMP ROOMS BUT NOT ALL.
 NFPA-101 7.9, NEC 700.16, 700.12F.
  
 16) NOTE: PLEASE ALSO PROVIDE PHOTO-METRICS FOR
 GENERATOR ROOM.THE LOCATION OF THE ROOM IS NOT YET
 FINAL HOWEVER THE LIGHTING LEVELS ARE STILL THE SAME.
 PLEASE SEE NFPA-110 7.3.3
  
 17) NOTE: PLEASE SEE NEC 620.23B FOR MINIMUM LIGHTING
 LEVELS IN ELEVATOR PIT. PLEASE SEE REFERENCE TO ASME
 A17.1-2004 AS THIS REQUIRES 5FT CANDLES MINIMUM.
  
 18) NOTE: PLEASE BE SURE TO COMPLETE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS ALONG WITH ALL CIRCUITING. PLEASE
 BE SURE TO COORDINATE ALL CIRCUITING WITH THE PANEL
 SCHEDULES.
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 PLEASE SEE FOR EXAMPLE SOME UNITS ALSO ARE MISSING
 CIRCUITING ( UNIT TH, GARAGE)
 ** ONLY SOME EXAMPLES ARE GIVEN HOWEVER THERE ARE
 NUMEROUS DEVICES ON PLANS WHICH DO NOT CONTAIN A
 CIRCUIT OR NOT FOR CIRCUITING.
  
 19) NOTE: PLEASE CLARIFY HEADROOM AND ELEVATION
 CLEARANCES FOR ALL ELECTRICAL ROOMS AND ELECTRICAL
 CLOSETS. FOR EXAMPLE: PLEASE SEE MC4,5,6,7,8 AND 9 AS
 THERE APPEAR TO BE STAIRS SHOWN ABOVE THIS ROOM FOR
 NEXT LEVEL AND MAY NOT MEET 110.26.
 PLEASE PROVIDE ELEVATION OF ROOM/AREAS OF CONCERN. MAY
 BE ONE DETAIL TYPICAL OF ALL.
  
 20) NOTE: PLEASE SEE NO MORE THAN 8FT OF UNPROTECTED
 CONDUCTORS, BUS-DUCT ETC MAY BE INSTALLED INSIDE
 BUILDING. THIS INCLUDES THE BUS-DUCT SHOWN ACROSS
 CEILING IN MAIN ELECTRICAL ROOM.
 230.70, 230.71.
 90.4.
  
 21) NOTE: PLEASE SEE NFPA-72 DEFINITIONS OF SMOKE
 DETECTION TYPE DEVICES. PLEASE SEE SMOKE DETECTORS ARE
 SHOWN ON PLANS FOR UNITS ARE DEVICES WHICH ONLY
 *DETECT* AND DO NOT SOUND AN ALARM. THE PLANS HOWEVER
 SEEM TO DESCRIBE THESE AS * SMOKE ALARMS* WHICH ARE
 DEVICES THAT *DETECT AND SOUND*. PLEASE BE SURE TO
 ADJUST THE DEVICE DESIGNATIONS AND SYMBOL LEGEND ALONG
 WITH ALL NOTES.
 PLEASE SEE THE LOCATIONS OF MANY OF THESE DEVICES DO
 NOT APPEAR TO MEET 11.8.3.
 PLEASE SEE FOR EXAMPLE ANY UNITS WHICH CONTAIN AN
 ELEVATED CEILING SUCH AS A TRAY CEILING WITH A
 DIFFERENCE OF 12INCHES OR MORE WILL REQUIRE THE DEVICE
 TO BE RE-LOCATED TO THE UPPER LEVEL (HIGHEST POINT)
 SOME UNITS ALREADY HAVE THESE DEVICES IN UPPER AREA
 HOWEVER MOST DO NOT.
 PLEASE SEE NFPA-72 11.5.1.1.1, 11.8.3
  
 22) NOTE: PLEASE SEE ANY GROUND LEVEL UNITS WHICH
 CONTAIN MEANS OF EGRESS FROM UNIT WILL REQUIRE A
 LIGHTING CONTROLLED DEVICE, OUTLET AND LIGHTING FIXTURE
 OF SOME TYPE.
 PLEASE SEE UNIT *C* FOR EXAMPLE WHICH HAS DIRECT
 ACCESS.
 210.70
 LS 101 7.8
  
 23) NOTE: PLEASE SEE 240.12 AND PROVIDE SELECTIVE
 COORDINATION OF EMERGENCY SYSTEMS, EQUIPMENT, OVER
 CURRENT PROTECTION ETC.
 PLEASE ALSO SEE NFPA-110 6.5.1
  
 24) NOTE: PLEASE LABEL ALL MAINS. PLEASE SEE FOR
 EXAMPLE EM MAIN WHICH DOES NOT CONTAIN NOTE OR
 INFORMATION FOR LABELING.
 230.2E, 700.8, 701.9 ETC
  
 25) NOTE: PLEASE SEE MISSING INFORMATION FOR CDP ON
 RISER EQUIPMENT NOTES. THIS IS SHOWN AS MAIN #3,
 HOWEVER NO INFORMATION COULD BE LOCATED FOR THIS MAIN.
 PLEASE ALSO SEE THERE ARE SEVERAL OTHER METER CENTERS
 WHICH ARE NOTED TO THIS CDP YET NO SCHEDULE WAS SHOWN
 ON SHEET. THE ADP DOES HAVE THE SCHEDULE, LOAD
 CALCULATIONS AND SIZING OF EQUIPMENT ETC.?? 230.70,
 230.70, 240.4, 310.16 ETC ETC.
  
 26) NOTE: PLEASE SEE SHEET E-1.5 WHICH TITLE OF SHEET
 INDICATES POOL LEVEL, YET NO POOL SHOWN.??
 PLEASE COORDINATE ALL SHEETS AND ITEMS ON SHEETS.
 PLEASE INDICATE AND COMPLETE ANY LANDSCAPE LIGHTING.
 PLEASE KNOW ANY LANDSCAPE LIGHTING SHALL ALSO
 COORDINATE WITH THE NOTES ABOVE FOR ENERGY
 CALCULATIONS, CIRCUITING ETC.
 PLEASE SEE ALSO FOR EXAMPLE THIS SET BEING REVIEWED
 CONTAINS SHEETS E -8 AND E-9 AT THE END OF ALL
 ELECTRICAL SHEETS.
 PLEASE SEE ONLY TWO SETS SUBMITTED FOR REVIEW. PLEASE
 KNOW WHEN SUBMITTING FOR PERMIT THREE COMPLETE SETS OF
 ALL DOCUMENTS WILL BE REQUIRED.
 PLEASE BE SURE TO COORDINATE ALL SHEETS, SETS ETC. FBC
 106.1.2, 106.3.1, 106.3, 106.5 ETC
  
 27) NOTE: PLEASE SEE NOTE FOR ARC FAULT REFERENCE
 PROTECTION FOR RECEPTACLES ONLY. PLEASE SEE NEC 2005 AS
 THIS REQUIRES PROTECTION FOR ALL OUTLETS INCLUSIVE OF
 RECEPTACLES, LIGHTS, FANS, SMOKE ALARMS ETC. PLEASE SEE
 SOME UNITS DO NOT HAVE PROTECTION FOR SOME SLEEPING
 ROOMS. PLEASE SEE POSSIBLE ADAPTABLE SLEEPING ROOMS
 (UNIT *C*)?
 210.12
 PLEAS ADJUST NOTE(S).
  
 28) NOTE: PLEASE SEE CIRCUITING FOR DINING ROOMS AND
 AREAS OF THE LIKE SHALL BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS.
 PLEASE SEE FOR EXAMPLE: UNIT DINING RECEPTACLES ON
 LIGHTING CIRCUIT.
 ** ONLY NOTED ONE EXAMPLE, HOWEVER PLEASE SEE OTHER
 AREAS AND AREAS OF THE *LIKE* SUCH AS BAR AREAS OFF
 KITCHENS.
  
 29) NOTE: PLEASE SEE 210.52C1 AND 210.8A6 AS THERE ARE
 SOME COUNTER SPACE RECEPTACLES MISSING.
 PLEASE SEE UNITS CH, CH MOD, CH MOD 2 ETC.
 THESE ARE A COUPLE OF UNITS GIVEN AS EXAMPLE.
  
 30) NOTE: PLEASE SEE POSSIBLE COUNTER SPACE AS
 PENINSULAR DESIGNATED IN UNIT *B*.
 PLEASE VERIFY 12INCHES OR MORE OF COUNTER SPACE WITH A
 SINK WHICH SEPARATES SPACE WILL REQUIRE AN ADDITIONAL
 GFI.
 PLEASE SEE 210.52C1-C5.
  
 31) NOTE: PLEASE SEE NOTES IN SQUARE BOXES ON E-10
 NOTED AS NOTE #1 AND NOTE #2.
 PLEASE SEE THESE BOXES ARE NOTED FOR UNDER CABINET
 LIGHTING WHICH WILL BE REQUIRED TO BE INCLUDED IF
 INSTALLED.
 PLEASE CLARIFY NOTE #2 AS THIS NOTES A WINE COOLER YET
 AS THE SIZE OF THIS EQUIPMENT IS NOTKNOWN, THIS MAY
 BE REQUIRED TO NOT ONLY BE A DEDICATE CIRCUIT HOWEVER
 IT WILL ALSO REQUIRE A SINGLE DEDICATE RECEPTACLE.
 PLEASE SEE PANELSCHEDULE ALREADY SHOWS DEDICATE
 CIRCUIT, THEREFORE A DEDICATED SINGLE POINT OF USE
 RECEPTACLE WILL BE REQUIRED.
 210.3, 210.20, 21, 23 ETC
  
 32) NOTE: PLEASE SEE THE GENERATOR IS BEING SHOWN AS A
 SEPARATELY DERIVED UNIT, YET NO GROUNDING ELECTRODE
 RISER AND SYSTEM IS BEING SHOWN??
 PLEASE SEE 250.50, 250.20, 250.58 ETC
 PLEASE PROVIDE CONNECTIONS AND RISER.
  
 33) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR POOL AREA
 LIGHTING TO MEET 680.22 AND 411.4AND ACTUAL DISTANCES
 DEPENDING ON THE FIXTURES BEING LOW VOLTAGE OR HIGH
 VOLTAGE.
 PLEASE SEE FOUNTAIN AREAS ALSO.
  
 34) NOTE: PLEASE PLACE NOTE ON PLANS FOR ANY PROPOSED
 LIGHTNING PROTECTION SYSTEM TO MEET NFPA-780. *WORDS TO
 THAT AFFECT*
  
 35) NOTE: PLEASE SEE SOME UNITS FOR HALLWAY/GALLERY
 AREAS FOR 10FT OR MORE OF WALL SPACE.
 PLEASE SEE 210.52H.
 PLEASE SEE FOR EXAMPLE UNIT E, AS THE LOCATION OF THE
 RECEPTACLE AS SHOWN WOULD LEAVE MORE THAN 10FT OF WALL
 SPACE WITH NO DEVICE.
 PLEASE SEE UNITS TH, TH-MOD ETC AS THE AREAS NEAR
 STAIRS ARE CONSIDERED HALLWAYS AND DO CONTAIN WALLS
 10FT OR MORE.
  
 36) NOTE: PLEASE SEE AS NOTED ABOVE THE FOR UNITS TH,
 TH_MOD ETC THE RAIL AREAS OFF STAIRS ARE CONSIDERED
 WALL SPACE PER 210.52.
 PLEASE SEE FOR EXAMPLES SOME OTHER AREAS IN WHICH WALL
 RECEPTACLES FOR TWO FEET OR MORE OF WALL ARE MISSING
 DEVICES.
 PLEASE SEE UNIT *F* BEDROOM #3, 2FT OF WALL. PLEASE SEE
 UNIT *P* 2FT OF WALL IN FAMILY ROOM. PLEASE SEE UNIT
 *B* KITCHEN WALL 2FT OR MORE.
 ** THESE ARE A FEW EXAMPLES, PLEASE GO THROUGH ALL
 UNITS.
  
 37) NOTE: PLEASE SEE UNITS WHICH SHOWS WHAT APPEARS TO
 BE A LOW VOLTAGE CONTROL PANEL IN MANY OF THE CLOSETS.
 PLEASE KNOW THAT IF THESE PANELS/UNITS CONTAIN OVER
 CURRENT PROTECTION DEVICES AND/OR TRANSFORMERS WHICH
 GENERATE A HAZARDOUS HEAT SOURCE FOR STORAGE OF
 COMBUSTIBLES THESE WILL BE REQUIRED TO BE RE-LOCATED.
 MANY OF THESE ARE NOT SHOWN NEAR SHELVING AREAS AND
 SOME ARE IN LAUNDRY ROOMS/AREAS HOWEVER NOT ALL. PLEASE
 SEE FOR EXAMPLE UNIT *J* SHOWN RIGHT ABOVE SHELF , AND
 UNIT *K* WHICH SHOWS TWO PANELS IN THE SAME UNIT.
 PLEASE SEE 240.24, 408.17, 90.4
 THIS AHJ HAS SEEN FIRST HAND FIRE HAZARDS CAUSED BY
 SOME OF THESE TYPES OF UNITS. PLEASE VERIFY UNIT,
 LISTING ETC.
  
 38) NOTE: PLEASE SEE MISSING CIRCUITING IN GARAGE UNITS
 AS NOTED ABOVE FOR COMPLETING CIRCUITING ON PLANS.
 PLEASE SEE FOR EXAMPLE: UNITS TH ETC WHICH CONTAIN WHAT
 APPEAR TO BE GDO (GARAGE DOOR OPENERS) HOWEVER NO
 DEDICATE CIRCUITS WERE SHOWN.
 PLEASE SEE 430.148 AND 210 AS THESE MAY NOT BE ON WITH
 ANY OTHER RECEPTACLES NOR CAN THEY BE ON THE LIGHTING
 CIRCUIT.
  
 39) NOTE: PLEASE SUBMIT AND COMPLETE LOAD CALCULATIONS
 FOR ALL UNITS ON SHEETS AND PANELS.
 PLEASE SEE FOR EXAMPLE: THE MISSING CALCULATIONS FOR
 PANEL/UNIT *P* ON E-19.
  
 40) NOTE: PLEASE SHOW WHERE THE SPA EQUIPMENT/MOTOR
 ACCESS IS LOCATED FOR UNITS TH-TH-MOD ETC.430.74,
 680.73, 680.44 ETC
  
 41) NOTE: PLEASE CLARIFY THE SPA ACTUAL *WATERS EDGE*.
 DETERMINATION FOR CLEARANCES FOR EQUIPMENT, LIGHTING
 CAN NOT BE DONE AT THIS TIME.
 680.42, 43
  
 42) NOTE: PLEASE SEE SHEET E-26 MAKES REFERENCE FOR
 CANDELA LEVELS TO BE ACCORDING TO NFPA-72 HOWEVER
 PLEASE SEE THE MINIMUM LEVELS FOR ADA COMPLIANCE IS
 SUBSTANTIALLY MORE RESTRICTIVE UNDER THE FLORIDA
 BUILDING CODE 11-4.
 PLEASE BE SURE TO INDICATE LEVELS PER 11-4.28.1, .2 AND
 .3(4).
 PLEASE KNOW THE MINIMUM LEVEL IN NFPA-72 IS 15CD
 WHEREAS THE MINIMUM ADA LEVEL IS 75CD IN THE FBC.
 PLEASE ADJUST DEVICES, LOCATIONS AND LEVELS PER FBC.
  
 43) NOTE: PLEASE THE CHANGES IN THE 2005 NEC FOR ALL
 RECEPTACLES WITHIN 6FT OF ANY LAUNDRY TUB WHICH
 REQUIRES ALL RECEPTACLES TO BE GFI OR GFI PROTECTED TO
 15, 20AMP AND 120V. THIS WOULD INCLUDE WASHERS AND
 OTHER RECEPTACLES LOCATED IN THE LAUNDRY ROOM.
 THE PREVIOUS CODE STILL REQUIRED NONE DEDICATE DEVICES
 IN LAUNDRY ROOMS WITHIN 6FT OF LAUNDRY TUB AND THE NEW
 CODE REQUIRES EVEN THAT OF WASHERS AND OTHER DEDICATED
 EQUIPMENT WITH THAT SAME 6FT.
 PLEASE SEE UNIT *A* FOR ONE EXAMPLE.
 PLEASE SEE NEC 210.8A7
  
 ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET
 DESIGNED OR SUBMITTED FOR REVIEW THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-30 17:04:302007-12-30 17:04:30
  
 REVIEW TO CONTINUE 12/31
2007-12-30 12:57:502007-12-30 12:57:50
  
 REVIEW CONTINUED
2007-12-25 14:23:402007-12-25 14:23:40
  
 ONE SET IN ELECTRIC FOR REVIEW.