Date |
Text |
2008-01-01 12:07:38 | 2008-01-01 12:07:38 |
| |
| *** DENIED REVIEW *** |
| |
| ** IMPORTANT** |
| THIS HAS ONLY BEEN SUBMITTED FOR *PLAN REVIEW* AND HAS |
| NOT BEEN SUBMITTED FOR PERMIT. |
| |
| 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| AND REFLECTED ON PLANS INCLUDING ON ELECTRICAL PLANS. |
| PLEASE SEE SOME ARE ALREADY SHOWN AND SOME CODES WHICH |
| ARE SHOWN ARE NOT YET ADOPTED BY THE STATE OF FLORIDA. |
| PLEASE BE SURE THE FOLLOWING ARE LISTED. |
| 2004 FBC W/2007 SUPPLEMENTS |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| 2002 NFPA-110 |
| 2003 NFPA-20 |
| |
| PLEASE SEE COMMENTS FROM OTHERTRADES WHICH MAY ALSO |
| REQUIRE SOME CODES TO BE LISTED. |
| ** PLEASE SEE SOME SHEETS FOR EXAMPLE INDICATE THE 2006 |
| NFPA-101. ( NOT YET ADOPTED) |
| ** PLEASE SEE CODE SECTIONS REFERENCED ON THE |
| ELECTRICAL PLANS ARE NOT FROM THE CURRENT NEC IN |
| EFFECT. PLEASE SEE LOAD CALCULATIONS FOR EXAMPLE WHICH |
| INDICATES 220.30, YET 220.30 DOES NOT EXIST UNDER THE |
| 2005 NEC. |
| |
| 2) NOTE: PLEASE SEE COMMENTS FROM THE ADDRESSING |
| REVIEWER ALONG WITH ANY ADDRESSING COMMENTS FROM THE |
| FIRE MARSHAL OFFICE. PLEASE BE SURE TO PLACE THE |
| ADJUSTED DETERMINED ADDRESS ON TITLE BLOCKS ONCE |
| FINALIZED. |
| FAC 61G15-23.002, 61G1-16.004 |
| FBC ADMIN 106.5 |
| |
| 3) NOTE: PLEASE BE SURE ALL TITLE BLOCKS ON ALL SHEETS |
| CONTAIN THE PRINTED NAME OF THE DESIGNER OF RECORD. |
| PLEASE SEE FOR EXAMPLE SOME SHEETS CONTAIN WHITE-OUT |
| OVER WHAT USED TO BE THE PRINTED NAME OF A DIFFERENT |
| ENGINEER WORKING FOR THE SAME FIRM. THIS CAN BE SEEN ON |
| SHEET E-20. |
| FAC 61G15-23.002 |
| |
| 4) NOTE: PLEASE SEE LANDSCAPE PLANS IN SETS SUBMITTED |
| CONTAIN A *RUBBER-STAMP* FOR THE REQUIRED ORIGINAL |
| SIGNATURE OF SAID DESIGNER. THIS IS STRICTLY PROHIBITED |
| UNDER THE FLORIDA STATUTES AND REQUIRES AN |
| *ORIGINAL/WET* SIGNATURE. |
| PLEASE KNOW THIS COMMENT IS REQUIRED WHETHER OR NOT |
| COMMENT IS MADE BY ANY OTHER TRADE. |
| FS 481.221 |
| |
| 5) NOTE: PLEASE SEE NO LIGHTING CONTROLS FOR FBC |
| CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND .1.3 WAS |
| SUBMITTED OR SHOWN ON PLANS. |
| AS NO SYSTEMS, DEVICES, OVER RIDES ETC WAS SHOWN IN |
| DESIGN, NO REVIEW OF SAID ITEMS COULD BE DONE AT THIS |
| TIME. |
| PLEASE SEE ALL INFORMATION FOR MAXIMUM TIMES, ANY |
| SCHEDULING ETC NEEDS TO BE SUBMITTED. |
| |
| 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS THE |
| INPUT DATA REPORT NEEDS TO COORDINATE WITH *ALL* |
| LIGHTING ON PLANS, ALL, METHOD OF CONTROLS, TYPE OF |
| FIXTURES AND WATTAGES. |
| PLEASE SEE ONE EXAMPLE IS: THE EXTERIOR LIGHTING |
| FIXTURES ON THE INPUT DATA REPORT ONLY SHOWS A TOTAL OF |
| 57 FIXTURES WHICH IS NOT POSSIBLE WHEN THE PLANS SHOW |
| SUBSTANTIALLY MORE FIXTURES. |
| PLEASE SEE FOR EXAMPLE: THE METHOD OF CONTROLS FOR |
| INTERIOR LIGHTS IS ALL SHOWN AS MANUAL ON/OFF WHICH IS |
| NOT POSSIBLE FOR ALL WHEN THE FBC CHAPTER 13 SECTIONS |
| AS NOTED ABOVE REQUIRE AUTOMATED CONTROLS FOR THE |
| BUILDING AND MOST LOCATIONS. |
| ** PLEASE KNOW THESE ARE ONLY A COUPLE OF EXAMPLES, |
| PLEASE BE SURE TO GO THROUGH ALL LIGHTING ON PLANS AND |
| COORDINATE WITH THE INPUT DATA REPORT FOR *ALL* |
| LIGHTING. |
| 13-415.1.A, 13-415.2, 13-415.2.ABC.1.2, |
| 13-415.2.ABC.1.3 |
| |
| ** IMPORTANT** THIS OFFICE CAN NOT EXPRESS ENOUGH TO |
| PLEASE SURE ALL LIGHTING ON PLANS MATCHES WITH THE |
| INPUT DATA REPORT. THIS IS ONE ITEM WHICH IS TYPICAL OF |
| HOLDING UP NUMEROUS PROJECTS FOR PERMIT ISSUANCE. |
| |
| ** THE LIGHTING CONTROLS FOR FBC WENT INTO EFFECT IN |
| OCT 2005 UNDER THE 2004 FBC CODE CHANGE. THE FEDERAL |
| REQUIREMENT WAS ADOPTED IN JULY 04. |
| |
| 7) NOTE: PLEASE SEE HOUSE BILL 7121 AND POSSIBLE |
| REQUIREMENTS FOR BUILDING. |
| |
| 8) NOTE: PLEASE PROVIDE INFORMATION ON FAIL SAFE |
| OPERATION OF ALL EGRESS DOORS WHICH ARE SHOWING ACCESS |
| CONTROLS AND ALSO PARKING GATES. |
| PLEASE SEE NFPA-101 7.2.1.5, 7.2.1.6.2. |
| ** PLEASE ALSO SEE DOORS AT LOBBY ETC FOR EXAMPLES. |
| SHEET E-1.4, AND NOTE #1. |
| |
| 9) NOTE: PLEASE SEE THE PLANS INDICATE WHAT IS BEING A |
| NATURAL GAS GENERATOR IN THE DESIGN OF THE BUILDING. |
| PLEASE SEE 700.12B3, 701.11B3 AS ON-SITE FUEL WILL BE |
| REQUIRED. |
| PLEASE SEE COMMENTS FROM OTHER REVIEWS WITH RESPECT TO |
| ANY ON-SITE FUEL TANKS FOR LP. |
| PLEASE KNOW THE TRANSFER OF FUEL MUST BE BY AN |
| AUTOMATIC MEANS AND SHALL NOT BE MANUAL. |
| ** PLEASE KNOW THERE IS QUESTIONS OVER WHAT TYPE OF |
| GENERATOR SYSTEM IS BEING PROPOSED. PLEASE IDENTIFY IF |
| THIS IS INDEED A SYSTEM UNDER 700, 701 OR 702. |
| IF PROPOSING A 702 SYSTEM THIS CHANGES COMMENTS AND |
| WILL INDEED REQUIRE OTHER ADDITIONAL ITEMS/COMMENTS |
| WHICH CAN NOT BE MADE AT THIS TIME. |
| PLEASE ALSO SEE NFPA-110 AND CLASS OF SYSTEM. |
| |
| 10) NOTE: PLEASE SEE THE MINIMUM CLEARANCE OF THE |
| TRANSFER SWITCH HAS NOT BEEN MET PER NFPA-110 7.2.2.1 |
| AND NEC 110.26. |
| ** REQUIRES TWICE THE DISTANCE. |
| |
| 11) NOTE: PLEASE PROVIDE THE ELEVATION OF THE ANY EPSS |
| EQUIPMENT PER 7.2.3. |
| PLEASE BE SURE THE LEVELS MEET EITHER THE 100YR STORM |
| LEVELS OR LEVELS BASED ON CAT 4, *SLOSH* CHARTS. ( SEA, |
| LAKE, OVERLAND, SURGES BY HURRICANES). |
| |
| 12) NOTE: PLEASE SEE NO INFORMATION WAS SUBMITTED FOR |
| FIRE PUMP CONTROLLER, SIZE, LOCKED ROTOR CURRENTS ETC. |
| PLEASE SEE NEC 695.3, 695.4 AND SEE NFPA-20 CHAPTERS 9 |
| AND 10. THE ENTIRE CHAPTERS ARE BEING REFLECTED AS NO |
| INFORMATION WAS SUBMITTED. |
| |
| 13) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT |
| SHEETS FOR THE GENERATOR, ATS, FIRE PUMP, FIRE PUMP |
| CONTROLLER ETC. |
| PLEASE SUBMIT ALSO ANY SPECS/CUT SHEETS FOR ON-SITE |
| FUEL TANKS.(REVIEWED BY OTHERS). |
| NEC 110.3, 90.7 |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 14) NOTE: PLEASE SUBMIT COMPLETED LIGHTING |
| PHOTO-METRICS FOR ALL DESIGNATED EGRESS PATH UNDER |
| NORMAL AND UNDER EMERGENCY CONDITIONS. |
| PLEASE SEE FOR EXAMPLE THERE ARE MANY LOCATIONS WHERE |
| THERE IS NO BATTERY BACK UP FIXTURES ARE BEING SHOWN. |
| FOR EXAMPLE: PLEASE SEE THE STAIRS WHICH EGRESS INTO |
| COURTYARD AREA, THE HALLWAYS DO NOT CONTAIN ANY BATTERY |
| BACK UP FIXTURES. PLEASE SEE STAIRS 1A, 2A, 3A, 4A, 5A |
| ETC. |
| FOR EXAMPLE: PLEASE SEE THE STAIRS LEADING FROM THE |
| UNDERGROUND PARKING TO GROUND LEVELS OUTSIDE WHICH DO |
| NOT CONTAIN ANY BACK UP FIXTURES. |
| FOR EXAMPLE: PLEASE SEE EGRESS AREAS ON CABANA LEVELS. |
| ** PLEASE KNOW THE LEVELS FOR ALL EGRESS STAIR AREAS IS |
| 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED DOWN TO 1FT |
| CANDLE UNDER EMERGENCY CONDITIONS PER 7.9.2.2 |
| ** PLEASE KNOW AT THIS TIME AS NO LIGHTING LEVELS WERE |
| SUBMITTED, ALL AREAS CAN NOT BE REVIEWED AT THIS TIME. |
| THERE IS CONCERN OVER SOME OF THE EXAMPLES GIVEN AS |
| THESE AREAS DO NOT APPEAR TO CONTAIN MINIMUM LIGHTING |
| LEVELS UNDER NORMAL (OUTSIDE STAIRS). |
| ** PLEASE SEE NFPA-101 7.8 AND 7.9 |
| ** PLEASE SEE FAC 61G15-33.004 |
| ** PLEASE KNOW THE FEW EXAMPLES GIVEN ABOVE ARE IN NO |
| WAY ALL LOCATIONS IN WHICH CONCERN OF THE LIGHTING |
| LEVELS ARE GIVEN. |
| |
| 15) NOTE: PLEASE SEE THE FOLLOWING AREAS SHALL CONTAIN |
| BATTERY BACK UP FIXTURES OF SOME KIND. |
| THE MAIN ELECTRICAL ROOM, FIRE PUMP ROOM, GENERATOR |
| ROOM. |
| SOME OF THESE ROOMS MAY ALREADY CONTAIN FIXTURES LIKE |
| THE FIRE PUMP ROOMS BUT NOT ALL. |
| NFPA-101 7.9, NEC 700.16, 700.12F. |
| |
| 16) NOTE: PLEASE ALSO PROVIDE PHOTO-METRICS FOR |
| GENERATOR ROOM.THE LOCATION OF THE ROOM IS NOT YET |
| FINAL HOWEVER THE LIGHTING LEVELS ARE STILL THE SAME. |
| PLEASE SEE NFPA-110 7.3.3 |
| |
| 17) NOTE: PLEASE SEE NEC 620.23B FOR MINIMUM LIGHTING |
| LEVELS IN ELEVATOR PIT. PLEASE SEE REFERENCE TO ASME |
| A17.1-2004 AS THIS REQUIRES 5FT CANDLES MINIMUM. |
| |
| 18) NOTE: PLEASE BE SURE TO COMPLETE ALL ROOM AND AREA |
| DESIGNATIONS ON PLANS ALONG WITH ALL CIRCUITING. PLEASE |
| BE SURE TO COORDINATE ALL CIRCUITING WITH THE PANEL |
| SCHEDULES. |
| PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT |
| LIGHTS. |
| PLEASE SEE FOR EXAMPLE SOME UNITS ALSO ARE MISSING |
| CIRCUITING ( UNIT TH, GARAGE) |
| ** ONLY SOME EXAMPLES ARE GIVEN HOWEVER THERE ARE |
| NUMEROUS DEVICES ON PLANS WHICH DO NOT CONTAIN A |
| CIRCUIT OR NOT FOR CIRCUITING. |
| |
| 19) NOTE: PLEASE CLARIFY HEADROOM AND ELEVATION |
| CLEARANCES FOR ALL ELECTRICAL ROOMS AND ELECTRICAL |
| CLOSETS. FOR EXAMPLE: PLEASE SEE MC4,5,6,7,8 AND 9 AS |
| THERE APPEAR TO BE STAIRS SHOWN ABOVE THIS ROOM FOR |
| NEXT LEVEL AND MAY NOT MEET 110.26. |
| PLEASE PROVIDE ELEVATION OF ROOM/AREAS OF CONCERN. MAY |
| BE ONE DETAIL TYPICAL OF ALL. |
| |
| 20) NOTE: PLEASE SEE NO MORE THAN 8FT OF UNPROTECTED |
| CONDUCTORS, BUS-DUCT ETC MAY BE INSTALLED INSIDE |
| BUILDING. THIS INCLUDES THE BUS-DUCT SHOWN ACROSS |
| CEILING IN MAIN ELECTRICAL ROOM. |
| 230.70, 230.71. |
| 90.4. |
| |
| 21) NOTE: PLEASE SEE NFPA-72 DEFINITIONS OF SMOKE |
| DETECTION TYPE DEVICES. PLEASE SEE SMOKE DETECTORS ARE |
| SHOWN ON PLANS FOR UNITS ARE DEVICES WHICH ONLY |
| *DETECT* AND DO NOT SOUND AN ALARM. THE PLANS HOWEVER |
| SEEM TO DESCRIBE THESE AS * SMOKE ALARMS* WHICH ARE |
| DEVICES THAT *DETECT AND SOUND*. PLEASE BE SURE TO |
| ADJUST THE DEVICE DESIGNATIONS AND SYMBOL LEGEND ALONG |
| WITH ALL NOTES. |
| PLEASE SEE THE LOCATIONS OF MANY OF THESE DEVICES DO |
| NOT APPEAR TO MEET 11.8.3. |
| PLEASE SEE FOR EXAMPLE ANY UNITS WHICH CONTAIN AN |
| ELEVATED CEILING SUCH AS A TRAY CEILING WITH A |
| DIFFERENCE OF 12INCHES OR MORE WILL REQUIRE THE DEVICE |
| TO BE RE-LOCATED TO THE UPPER LEVEL (HIGHEST POINT) |
| SOME UNITS ALREADY HAVE THESE DEVICES IN UPPER AREA |
| HOWEVER MOST DO NOT. |
| PLEASE SEE NFPA-72 11.5.1.1.1, 11.8.3 |
| |
| 22) NOTE: PLEASE SEE ANY GROUND LEVEL UNITS WHICH |
| CONTAIN MEANS OF EGRESS FROM UNIT WILL REQUIRE A |
| LIGHTING CONTROLLED DEVICE, OUTLET AND LIGHTING FIXTURE |
| OF SOME TYPE. |
| PLEASE SEE UNIT *C* FOR EXAMPLE WHICH HAS DIRECT |
| ACCESS. |
| 210.70 |
| LS 101 7.8 |
| |
| 23) NOTE: PLEASE SEE 240.12 AND PROVIDE SELECTIVE |
| COORDINATION OF EMERGENCY SYSTEMS, EQUIPMENT, OVER |
| CURRENT PROTECTION ETC. |
| PLEASE ALSO SEE NFPA-110 6.5.1 |
| |
| 24) NOTE: PLEASE LABEL ALL MAINS. PLEASE SEE FOR |
| EXAMPLE EM MAIN WHICH DOES NOT CONTAIN NOTE OR |
| INFORMATION FOR LABELING. |
| 230.2E, 700.8, 701.9 ETC |
| |
| 25) NOTE: PLEASE SEE MISSING INFORMATION FOR CDP ON |
| RISER EQUIPMENT NOTES. THIS IS SHOWN AS MAIN #3, |
| HOWEVER NO INFORMATION COULD BE LOCATED FOR THIS MAIN. |
| PLEASE ALSO SEE THERE ARE SEVERAL OTHER METER CENTERS |
| WHICH ARE NOTED TO THIS CDP YET NO SCHEDULE WAS SHOWN |
| ON SHEET. THE ADP DOES HAVE THE SCHEDULE, LOAD |
| CALCULATIONS AND SIZING OF EQUIPMENT ETC.?? 230.70, |
| 230.70, 240.4, 310.16 ETC ETC. |
| |
| 26) NOTE: PLEASE SEE SHEET E-1.5 WHICH TITLE OF SHEET |
| INDICATES POOL LEVEL, YET NO POOL SHOWN.?? |
| PLEASE COORDINATE ALL SHEETS AND ITEMS ON SHEETS. |
| PLEASE INDICATE AND COMPLETE ANY LANDSCAPE LIGHTING. |
| PLEASE KNOW ANY LANDSCAPE LIGHTING SHALL ALSO |
| COORDINATE WITH THE NOTES ABOVE FOR ENERGY |
| CALCULATIONS, CIRCUITING ETC. |
| PLEASE SEE ALSO FOR EXAMPLE THIS SET BEING REVIEWED |
| CONTAINS SHEETS E -8 AND E-9 AT THE END OF ALL |
| ELECTRICAL SHEETS. |
| PLEASE SEE ONLY TWO SETS SUBMITTED FOR REVIEW. PLEASE |
| KNOW WHEN SUBMITTING FOR PERMIT THREE COMPLETE SETS OF |
| ALL DOCUMENTS WILL BE REQUIRED. |
| PLEASE BE SURE TO COORDINATE ALL SHEETS, SETS ETC. FBC |
| 106.1.2, 106.3.1, 106.3, 106.5 ETC |
| |
| 27) NOTE: PLEASE SEE NOTE FOR ARC FAULT REFERENCE |
| PROTECTION FOR RECEPTACLES ONLY. PLEASE SEE NEC 2005 AS |
| THIS REQUIRES PROTECTION FOR ALL OUTLETS INCLUSIVE OF |
| RECEPTACLES, LIGHTS, FANS, SMOKE ALARMS ETC. PLEASE SEE |
| SOME UNITS DO NOT HAVE PROTECTION FOR SOME SLEEPING |
| ROOMS. PLEASE SEE POSSIBLE ADAPTABLE SLEEPING ROOMS |
| (UNIT *C*)? |
| 210.12 |
| PLEAS ADJUST NOTE(S). |
| |
| 28) NOTE: PLEASE SEE CIRCUITING FOR DINING ROOMS AND |
| AREAS OF THE LIKE SHALL BE ON ONE OR MORE OF THE SMALL |
| APPLIANCE CIRCUITS. |
| PLEASE SEE FOR EXAMPLE: UNIT DINING RECEPTACLES ON |
| LIGHTING CIRCUIT. |
| ** ONLY NOTED ONE EXAMPLE, HOWEVER PLEASE SEE OTHER |
| AREAS AND AREAS OF THE *LIKE* SUCH AS BAR AREAS OFF |
| KITCHENS. |
| |
| 29) NOTE: PLEASE SEE 210.52C1 AND 210.8A6 AS THERE ARE |
| SOME COUNTER SPACE RECEPTACLES MISSING. |
| PLEASE SEE UNITS CH, CH MOD, CH MOD 2 ETC. |
| THESE ARE A COUPLE OF UNITS GIVEN AS EXAMPLE. |
| |
| 30) NOTE: PLEASE SEE POSSIBLE COUNTER SPACE AS |
| PENINSULAR DESIGNATED IN UNIT *B*. |
| PLEASE VERIFY 12INCHES OR MORE OF COUNTER SPACE WITH A |
| SINK WHICH SEPARATES SPACE WILL REQUIRE AN ADDITIONAL |
| GFI. |
| PLEASE SEE 210.52C1-C5. |
| |
| 31) NOTE: PLEASE SEE NOTES IN SQUARE BOXES ON E-10 |
| NOTED AS NOTE #1 AND NOTE #2. |
| PLEASE SEE THESE BOXES ARE NOTED FOR UNDER CABINET |
| LIGHTING WHICH WILL BE REQUIRED TO BE INCLUDED IF |
| INSTALLED. |
| PLEASE CLARIFY NOTE #2 AS THIS NOTES A WINE COOLER YET |
| AS THE SIZE OF THIS EQUIPMENT IS NOTKNOWN, THIS MAY |
| BE REQUIRED TO NOT ONLY BE A DEDICATE CIRCUIT HOWEVER |
| IT WILL ALSO REQUIRE A SINGLE DEDICATE RECEPTACLE. |
| PLEASE SEE PANELSCHEDULE ALREADY SHOWS DEDICATE |
| CIRCUIT, THEREFORE A DEDICATED SINGLE POINT OF USE |
| RECEPTACLE WILL BE REQUIRED. |
| 210.3, 210.20, 21, 23 ETC |
| |
| 32) NOTE: PLEASE SEE THE GENERATOR IS BEING SHOWN AS A |
| SEPARATELY DERIVED UNIT, YET NO GROUNDING ELECTRODE |
| RISER AND SYSTEM IS BEING SHOWN?? |
| PLEASE SEE 250.50, 250.20, 250.58 ETC |
| PLEASE PROVIDE CONNECTIONS AND RISER. |
| |
| 33) NOTE: PLEASE PROVIDE A NOTE ON PLANS FOR POOL AREA |
| LIGHTING TO MEET 680.22 AND 411.4AND ACTUAL DISTANCES |
| DEPENDING ON THE FIXTURES BEING LOW VOLTAGE OR HIGH |
| VOLTAGE. |
| PLEASE SEE FOUNTAIN AREAS ALSO. |
| |
| 34) NOTE: PLEASE PLACE NOTE ON PLANS FOR ANY PROPOSED |
| LIGHTNING PROTECTION SYSTEM TO MEET NFPA-780. *WORDS TO |
| THAT AFFECT* |
| |
| 35) NOTE: PLEASE SEE SOME UNITS FOR HALLWAY/GALLERY |
| AREAS FOR 10FT OR MORE OF WALL SPACE. |
| PLEASE SEE 210.52H. |
| PLEASE SEE FOR EXAMPLE UNIT E, AS THE LOCATION OF THE |
| RECEPTACLE AS SHOWN WOULD LEAVE MORE THAN 10FT OF WALL |
| SPACE WITH NO DEVICE. |
| PLEASE SEE UNITS TH, TH-MOD ETC AS THE AREAS NEAR |
| STAIRS ARE CONSIDERED HALLWAYS AND DO CONTAIN WALLS |
| 10FT OR MORE. |
| |
| 36) NOTE: PLEASE SEE AS NOTED ABOVE THE FOR UNITS TH, |
| TH_MOD ETC THE RAIL AREAS OFF STAIRS ARE CONSIDERED |
| WALL SPACE PER 210.52. |
| PLEASE SEE FOR EXAMPLES SOME OTHER AREAS IN WHICH WALL |
| RECEPTACLES FOR TWO FEET OR MORE OF WALL ARE MISSING |
| DEVICES. |
| PLEASE SEE UNIT *F* BEDROOM #3, 2FT OF WALL. PLEASE SEE |
| UNIT *P* 2FT OF WALL IN FAMILY ROOM. PLEASE SEE UNIT |
| *B* KITCHEN WALL 2FT OR MORE. |
| ** THESE ARE A FEW EXAMPLES, PLEASE GO THROUGH ALL |
| UNITS. |
| |
| 37) NOTE: PLEASE SEE UNITS WHICH SHOWS WHAT APPEARS TO |
| BE A LOW VOLTAGE CONTROL PANEL IN MANY OF THE CLOSETS. |
| PLEASE KNOW THAT IF THESE PANELS/UNITS CONTAIN OVER |
| CURRENT PROTECTION DEVICES AND/OR TRANSFORMERS WHICH |
| GENERATE A HAZARDOUS HEAT SOURCE FOR STORAGE OF |
| COMBUSTIBLES THESE WILL BE REQUIRED TO BE RE-LOCATED. |
| MANY OF THESE ARE NOT SHOWN NEAR SHELVING AREAS AND |
| SOME ARE IN LAUNDRY ROOMS/AREAS HOWEVER NOT ALL. PLEASE |
| SEE FOR EXAMPLE UNIT *J* SHOWN RIGHT ABOVE SHELF , AND |
| UNIT *K* WHICH SHOWS TWO PANELS IN THE SAME UNIT. |
| PLEASE SEE 240.24, 408.17, 90.4 |
| THIS AHJ HAS SEEN FIRST HAND FIRE HAZARDS CAUSED BY |
| SOME OF THESE TYPES OF UNITS. PLEASE VERIFY UNIT, |
| LISTING ETC. |
| |
| 38) NOTE: PLEASE SEE MISSING CIRCUITING IN GARAGE UNITS |
| AS NOTED ABOVE FOR COMPLETING CIRCUITING ON PLANS. |
| PLEASE SEE FOR EXAMPLE: UNITS TH ETC WHICH CONTAIN WHAT |
| APPEAR TO BE GDO (GARAGE DOOR OPENERS) HOWEVER NO |
| DEDICATE CIRCUITS WERE SHOWN. |
| PLEASE SEE 430.148 AND 210 AS THESE MAY NOT BE ON WITH |
| ANY OTHER RECEPTACLES NOR CAN THEY BE ON THE LIGHTING |
| CIRCUIT. |
| |
| 39) NOTE: PLEASE SUBMIT AND COMPLETE LOAD CALCULATIONS |
| FOR ALL UNITS ON SHEETS AND PANELS. |
| PLEASE SEE FOR EXAMPLE: THE MISSING CALCULATIONS FOR |
| PANEL/UNIT *P* ON E-19. |
| |
| 40) NOTE: PLEASE SHOW WHERE THE SPA EQUIPMENT/MOTOR |
| ACCESS IS LOCATED FOR UNITS TH-TH-MOD ETC.430.74, |
| 680.73, 680.44 ETC |
| |
| 41) NOTE: PLEASE CLARIFY THE SPA ACTUAL *WATERS EDGE*. |
| DETERMINATION FOR CLEARANCES FOR EQUIPMENT, LIGHTING |
| CAN NOT BE DONE AT THIS TIME. |
| 680.42, 43 |
| |
| 42) NOTE: PLEASE SEE SHEET E-26 MAKES REFERENCE FOR |
| CANDELA LEVELS TO BE ACCORDING TO NFPA-72 HOWEVER |
| PLEASE SEE THE MINIMUM LEVELS FOR ADA COMPLIANCE IS |
| SUBSTANTIALLY MORE RESTRICTIVE UNDER THE FLORIDA |
| BUILDING CODE 11-4. |
| PLEASE BE SURE TO INDICATE LEVELS PER 11-4.28.1, .2 AND |
| .3(4). |
| PLEASE KNOW THE MINIMUM LEVEL IN NFPA-72 IS 15CD |
| WHEREAS THE MINIMUM ADA LEVEL IS 75CD IN THE FBC. |
| PLEASE ADJUST DEVICES, LOCATIONS AND LEVELS PER FBC. |
| |
| 43) NOTE: PLEASE THE CHANGES IN THE 2005 NEC FOR ALL |
| RECEPTACLES WITHIN 6FT OF ANY LAUNDRY TUB WHICH |
| REQUIRES ALL RECEPTACLES TO BE GFI OR GFI PROTECTED TO |
| 15, 20AMP AND 120V. THIS WOULD INCLUDE WASHERS AND |
| OTHER RECEPTACLES LOCATED IN THE LAUNDRY ROOM. |
| THE PREVIOUS CODE STILL REQUIRED NONE DEDICATE DEVICES |
| IN LAUNDRY ROOMS WITHIN 6FT OF LAUNDRY TUB AND THE NEW |
| CODE REQUIRES EVEN THAT OF WASHERS AND OTHER DEDICATED |
| EQUIPMENT WITH THAT SAME 6FT. |
| PLEASE SEE UNIT *A* FOR ONE EXAMPLE. |
| PLEASE SEE NEC 210.8A7 |
| |
| ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET |
| DESIGNED OR SUBMITTED FOR REVIEW THERE MAY VERY WELL BE |
| NEW COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE |
| AT THIS TIME. |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-12-30 17:04:30 | 2007-12-30 17:04:30 |
| |
| REVIEW TO CONTINUE 12/31 |
2007-12-30 12:57:50 | 2007-12-30 12:57:50 |
| |
| REVIEW CONTINUED |
2007-12-25 14:23:40 | 2007-12-25 14:23:40 |
| |
| ONE SET IN ELECTRIC FOR REVIEW. |