Plan Review Notes
Plan Review Notes For Permit 07120223
Permit Number 07120223
Review Stop E
Sequence Number 3
Notes
Date Text
2008-11-21 09:29:09 
  
  
 ** FAILED REVISION **
  
  
  
 1) NOTE: PLEASE SEE ITEM REDLINED ON ISSUED PLANS FROM
 1/28/08 THE 2005 NEC WAS REVISED TO REQUIRE ALL
 RECEPTACLES IN LAUNDRY ROOMS TO BE GFI/GFI PROTECTED
 WITHIN 6FT OF THE LAUNDRY SINK EVEN IF THESE ARE
 DEDICATED RECEPTACLES.
 THE PLANS WERE REDLINED FOR THE IRONING BOARD
 RECEPTACLE TO MEET 210.8A7
  
 2) NOTE: PLEASE LIST/IDENTIFY THE ARC FAULT BREAKERS ON
 PANEL SCHEDULES.
 210.12,408.4
  
 3) NOTE: PLEASE VERIFY THE CONDUITS FROM METER TO
 MAINS. ARE THESE OVERHEAD AS SHOWN ON RISER OR
 UNDERGROUND?
 IF OVER HEAD THEN OCP IS REQUIRED ON THE OUTSIDE.
 IF IN SLAB PLEASE SHOW.
 230.70
  
 4) NOTE: PLEASE SEE 210.11C2, 220.52
  
 5) NOTE: PLEASE SEE THE INCORRECT NFPA-72 IS STATED ON
 PLANS. SHOWS 2005 AND NEEDS TO 2002. THIS WAS REDLINED
 ON ORIGINAL PLANS.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  