2008-11-21 09:29:09 | |
| |
| |
| ** FAILED REVISION ** |
| |
| |
| |
| 1) NOTE: PLEASE SEE ITEM REDLINED ON ISSUED PLANS FROM |
| 1/28/08 THE 2005 NEC WAS REVISED TO REQUIRE ALL |
| RECEPTACLES IN LAUNDRY ROOMS TO BE GFI/GFI PROTECTED |
| WITHIN 6FT OF THE LAUNDRY SINK EVEN IF THESE ARE |
| DEDICATED RECEPTACLES. |
| THE PLANS WERE REDLINED FOR THE IRONING BOARD |
| RECEPTACLE TO MEET 210.8A7 |
| |
| 2) NOTE: PLEASE LIST/IDENTIFY THE ARC FAULT BREAKERS ON |
| PANEL SCHEDULES. |
| 210.12,408.4 |
| |
| 3) NOTE: PLEASE VERIFY THE CONDUITS FROM METER TO |
| MAINS. ARE THESE OVERHEAD AS SHOWN ON RISER OR |
| UNDERGROUND? |
| IF OVER HEAD THEN OCP IS REQUIRED ON THE OUTSIDE. |
| IF IN SLAB PLEASE SHOW. |
| 230.70 |
| |
| 4) NOTE: PLEASE SEE 210.11C2, 220.52 |
| |
| 5) NOTE: PLEASE SEE THE INCORRECT NFPA-72 IS STATED ON |
| PLANS. SHOWS 2005 AND NEEDS TO 2002. THIS WAS REDLINED |
| ON ORIGINAL PLANS. |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |