2008-06-09 10:00:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS.
 *** DENIED ***
 1) COOLING LOAD CALCULATION ON FILE ARE CALLING FOR
 51,426 TOTAL COOLING BTU'S FOR SYSTEM 1, REVISED
 MECHANICAL PLAN IS SHOWING MODEL NUMBERS FOR A 3 TON
 SYSTEM AROUND 33,800 TOTAL COOLING BTU'S. (SEE ARI
 CERTIFICATE ATTACHED). PLEASE CORRECT PLANS OR REVISE
 COOLING LOAD CAL'S PER 2004 FBC 13-607.1.ABC.1.1.
  
 2) THE SUPPLY AIR DUCT FROM AIR HANDLER #2 TO THE
 MIXING BOX OVER THE MASTER BATHROOM NEEDS TO BE SIZED,
 PER WPB AMEND. 106.3.5.4 (10).
  
 3) PLEASE SHOW THE JOB ADDRESS ON THE PLAN, PER WPB
 AMEND.106.1.3.
  
 MECHANICAL PLAN REVIEW BY;