2008-06-09 10:00:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECHANICAL PLANS. | | *** DENIED *** | | 1) COOLING LOAD CALCULATION ON FILE ARE CALLING FOR | | 51,426 TOTAL COOLING BTU'S FOR SYSTEM 1, REVISED | | MECHANICAL PLAN IS SHOWING MODEL NUMBERS FOR A 3 TON | | SYSTEM AROUND 33,800 TOTAL COOLING BTU'S. (SEE ARI | | CERTIFICATE ATTACHED). PLEASE CORRECT PLANS OR REVISE | | COOLING LOAD CAL'S PER 2004 FBC 13-607.1.ABC.1.1. | | | | 2) THE SUPPLY AIR DUCT FROM AIR HANDLER #2 TO THE | | MIXING BOX OVER THE MASTER BATHROOM NEEDS TO BE SIZED, | | PER WPB AMEND. 106.3.5.4 (10). | | | | 3) PLEASE SHOW THE JOB ADDRESS ON THE PLAN, PER WPB | | AMEND.106.1.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|