2007-12-23 13:16:23 | ** DENIEDREVIEW ** |
| |
| |
| 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE |
| NEEDED AS FOLLOWS: |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE 2005 NEC AS ALL RECEPTACLES IN A |
| LAUNDRY ROOM WITHIN 6FT OF LAUNDRY SINK ARE TO BE GFI. |
| THIS INCLUDES WASHING MACHINE. BASED ON THE SCALE OF |
| ELECTRICAL PLANS, THE SINK EDGE IS AT 6FT OR LESS. |
| PLEASE SEE 210.8A7 |
| |
| 3) NOTE: PLEASE SEE BEDROOM #3 AS ALL OUTLETS WHICH ARE |
| 15AMP OR 20AMP SHALL BE AFCI PROTECTED PER 210.12. THIS |
| INCLUDES THE GFI AND OTHER DEDICATED RECEPTACLES SHOWN |
| IN THIS ROOM. |
| |
| 4) NOTE: PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS |
| ARE STILL SHOWING 3-#6 CONDUCTORS FOR AH UNITS AND C |
| UNITS. THESE ARE TWO POLE UNITS AND IT IS PERMITTED TO |
| INSTALLED #6 FOR THE EQUIPMENT GROUNDING CONDUCTORS |
| HOWEVER NOT REQUIRED. IF SHOWN ON PLANS, THIS IS WHAT |
| WILL BE REQUIRED TO BE INSTALLED. |
| NO CHANGE IS NEEDED FOR EQUIPMENT GROUNDING IF #6 |
| CONDUCTORS WILL BE INSTALLED. THIS IS NOTED FOR |
| INFORMATION ONLY. |
| |
| 5) NOTE: PLEASE SEE MISSING LIVING ROOM RECEPTACLE |
| ALONG MORE THAN 2FT OF WALL SPACE. (REDLINED ON ONE |
| SET) (WALL NEAR KITCHEN DOORWAY ENTERING FROM BRKFST |
| RM. |
| 210.52 |
| |
| 6) NOTE: PLEASE SEE NFPA-72 11.8.3. IF THE TRAY CEILING |
| IN OFFICE WHICH IS ALSO CONSIDERED AN ADAPTABLE BEDROOM |
| IS 12INCHES OR HIGHER, THE SA IS REQUIRED AT THE HIGH |
| POINT OF ELEVATION. (ONLY IF TRY IS 12 INCHES OR |
| GREATER). BASED ON PLANS AND ELEVATIONS SHOWN THIS IS |
| THE CASE. PLEASE ADJUST LOCATION. |
| |
| 7) NOTE: PLEASE CORRELATE ELECTRICAL PLANS AND |
| MECHANICAL PLANS FOR NUMBER OF A/C UNITS AND SIZE OF |
| HEAT STRIPS. |
| PLEASE SEE MECHANICAL PLANS CALL FOR 1-5KW, 1-10KW AND |
| 1-7.5KW WHEREAS THE ELECTRICAL PANEL SCHEDULE/LOAD |
| CALCULATIONS ONLY INDICATE TWO SYSTEMS AND BOTH AT 10KW |
| EACH FOR HEAT. |
| THIS WILL AFFECT CIRCUITING, LOADS, OVER CURRENT |
| PROTECTION ETC. |
| 408.4, 240.4, 310.16, 220, ETC |
| FBC 106.3.5.4 |
| |
| 8) NOTE: PLEASE COORDINATE PLANS AND RISER AS PLANS |
| SHOW TWO MAIN DISCONNECTS OUTSIDE AND RISER ONLY SHOWS |
| TWO PANELS INSIDE.? |
| PLEASE COORDINATE. |
| FBC 106.1.2, 106.3.5.4 |
| NEC 230.70, 230.71, 230.72 |
| |
| 9) NOTE: PLEASE VERIFY IF THE LOAD ON POOL PANEL ARE |
| ALREADY FIGURED AT 125%. |
| 215.3, 230.42 ETC |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |