2007-12-23 13:16:23** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS:
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE 2005 NEC AS ALL RECEPTACLES IN A
 LAUNDRY ROOM WITHIN 6FT OF LAUNDRY SINK ARE TO BE GFI.
 THIS INCLUDES WASHING MACHINE. BASED ON THE SCALE OF
 ELECTRICAL PLANS, THE SINK EDGE IS AT 6FT OR LESS.
 PLEASE SEE 210.8A7
  
 3) NOTE: PLEASE SEE BEDROOM #3 AS ALL OUTLETS WHICH ARE
 15AMP OR 20AMP SHALL BE AFCI PROTECTED PER 210.12. THIS
 INCLUDES THE GFI AND OTHER DEDICATED RECEPTACLES SHOWN
 IN THIS ROOM.
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS
 ARE STILL SHOWING 3-#6 CONDUCTORS FOR AH UNITS AND C
 UNITS. THESE ARE TWO POLE UNITS AND IT IS PERMITTED TO
 INSTALLED #6 FOR THE EQUIPMENT GROUNDING CONDUCTORS
 HOWEVER NOT REQUIRED. IF SHOWN ON PLANS, THIS IS WHAT
 WILL BE REQUIRED TO BE INSTALLED.
 NO CHANGE IS NEEDED FOR EQUIPMENT GROUNDING IF #6
 CONDUCTORS WILL BE INSTALLED. THIS IS NOTED FOR
 INFORMATION ONLY.
  
 5) NOTE: PLEASE SEE MISSING LIVING ROOM RECEPTACLE
 ALONG MORE THAN 2FT OF WALL SPACE. (REDLINED ON ONE
 SET) (WALL NEAR KITCHEN DOORWAY ENTERING FROM BRKFST
 RM.
 210.52
  
 6) NOTE: PLEASE SEE NFPA-72 11.8.3. IF THE TRAY CEILING
 IN OFFICE WHICH IS ALSO CONSIDERED AN ADAPTABLE BEDROOM
 IS 12INCHES OR HIGHER, THE SA IS REQUIRED AT THE HIGH
 POINT OF ELEVATION. (ONLY IF TRY IS 12 INCHES OR
 GREATER). BASED ON PLANS AND ELEVATIONS SHOWN THIS IS
 THE CASE. PLEASE ADJUST LOCATION.
  
 7) NOTE: PLEASE CORRELATE ELECTRICAL PLANS AND
 MECHANICAL PLANS FOR NUMBER OF A/C UNITS AND SIZE OF
 HEAT STRIPS.
 PLEASE SEE MECHANICAL PLANS CALL FOR 1-5KW, 1-10KW AND
 1-7.5KW WHEREAS THE ELECTRICAL PANEL SCHEDULE/LOAD
 CALCULATIONS ONLY INDICATE TWO SYSTEMS AND BOTH AT 10KW
 EACH FOR HEAT.
 THIS WILL AFFECT CIRCUITING, LOADS, OVER CURRENT
 PROTECTION ETC.
 408.4, 240.4, 310.16, 220, ETC
 FBC 106.3.5.4
  
 8) NOTE: PLEASE COORDINATE PLANS AND RISER AS PLANS
 SHOW TWO MAIN DISCONNECTS OUTSIDE AND RISER ONLY SHOWS
 TWO PANELS INSIDE.?
 PLEASE COORDINATE.
 FBC 106.1.2, 106.3.5.4
 NEC 230.70, 230.71, 230.72
  
 9) NOTE: PLEASE VERIFY IF THE LOAD ON POOL PANEL ARE
 ALREADY FIGURED AT 125%.
 215.3, 230.42 ETC
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved