Plan Review Notes For Permit 07120179 |
Permit Number |
07120179 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-12-10 11:32:59 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLANS MAY NOT BE IN PEN OR PENCIL AFTER DRAWING PLAN | | MAKE COPIES AND SUBMIT TWO COPIES. | | | | 2) THE MECHANICAL PLANS NEED THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND | | CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE | | W.P.B. AMEND. 106.1.3. | | | | 3) SHOW THE SIZE OF THE DUCT (FLEX) TO EACH SUPPLY | | CAN. | | | | 4) PROVIDE FOR RETURN AIR TO BEDROOMS, SEE 2004 FBC/R | | M1602.4 . | | | | 5) SHOW THE SIZE OF THE MAIN TRUNK LINES. | | | | 6) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | LAWS, SEE F.B.C. 106.1.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|