Date |
Text |
2008-02-21 11:59:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED 2ND TIME: |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| THE PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW COMMENTS |
| WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| COMMENTS. |
| |
| 1. **RESPONSE NOTED, HOWEVER WATER COOLERS ARE NOT |
| COMPLIANT** |
| SHEET A-3.0 PER TABLE 403.1.2 DRINKING FOUNTAINS ARE |
| REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING |
| FOUNTAIN. SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| SECTION 11-4.15 AND ALL SUBSECTIONS. |
| |
| **PER FBC PLUMBING TABLE 403.1.2 WITH AN OCCUPANCY |
| LOAD OF 146 PERSONS BEING INDICATED ON SHEET A-1.0, A |
| MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED AND |
| SHALL BE COMPLIANT WITH CHAPTER 11 FLORIDA |
| ACCESSIBILITY CODE SECTION 11-4.15 AND ALL |
| SUBSECTIONS. |
| |
| |
| **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| INFORMATION) |
| 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| MAXIMUM. |
| 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| OF THE FRONT OF FOUNTAIN. |
| 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| MOUNTED NEAR FRONT EDGE. |
| 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| SPACE. |
| 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| |
| 2. **RESPONSE NOTED, HOWEVER SEE NOTE: BELOW PREVIOUS |
| COMMENT** |
| SHEET A-3.0 THE KITCHEN SINK SHALL BE ACCESSIBLE, |
| PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| 11-4.24 AND ALL SUB SECTIONS. |
| |
| **NOTE: SHEET A-3.2 DETAIL 2, KITCHEN: PER CHAPTER 11 |
| FLORIDA ACCESSIBILITY CODE PLEASE SHOW COMPLIANCE TO |
| 11-4.24 SUBSECTIONS. |
| |
| **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE |
| FOLLOWING INFORMATION) |
| 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. |
| 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| SINK.**CLEARLY INDICATE THAT CLEAR FLOOR SPACE SHALL |
| EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK. 11-4.24.7 |
| FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR ELECTRONICALLY |
| CONTROLLED ARE ACCEPTABLE DESIGNS.**CLEARLY INDICATE |
| FAUCET TYPE. |
| |
| 3. **OK** COMMENT ADDRESSED. |
| |
| 4. **OK** COMMENT ADDRESSED. |
| |
| 5. **COMMENT RESPONSE NOTED, HOWEVER SEE NOT: BELOW |
| PREVIOUS COMMENT** |
| SHEET P-1 SHOW THE LOCATION OF THE SANITARY BUILDING |
| DRAIN AND THE WATER MAIN THAT THE KITCHEN SINK WILL BE |
| CONNECTED TO. SECTION 106.1.2 ADDITIONAL DATA. |
| |
| **NOTE: SHEET P-1 IS INDICATING THE SANITARY WASTE, |
| VENT AND POTABLE WATER TO THE SINK AS EXISTING (REMOVED |
| SINK) HOWEVER THERE IS NO INDICATION ON THE DEMO PLAN |
| SHEET A-2.0 THAT THERE WAS AN EXISTING SINK LOCATED IN |
| THIS AREA. PLEASE CLARIFY THIS. PER CITY OF WPB |
| AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS AND SECTION 106.1.2 ADDITIONAL |
| DATA. |
| |
| **THE FOLLOWING IS A NEW COMMENT** |
| |
| 6. SHEETS A-1.0, A-3.0, A-3.1, A-3.2, A-4.0 AND A-5.0 |
| ARE MISSING A DATE AT THE ARCHITECTS SIGNATURE AND SEAL |
| AS WELL AS THE PRINTED NAME AND LICENSE NUMBER OF THE |
| PERSON SIGNING AND SEALING EACH SHEET, ALSO SHEETS |
| A-2.0 AND A-6.0 ARE MISSING THE PRINTED NAME OF THE |
| PERSON RESPONSIBLE OF SIGNING AND SEALING SHEETS. PER |
| FS 481 AND FAC61G16-23. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |