Plan Review Notes
Plan Review Notes For Permit 07120174
Permit Number 07120174
Review Stop M
Sequence Number 2
Notes
Date Text
2008-02-11 18:17:32REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS APPEARS TO BE A LEVEL 3 ALTERATION IN
 ACCORDANCE WITH FBC, EB 305.1. SEE BUILDING PLAN REVIEW
 COMMENTS.
  
 2. OK
  
 3. THERE IS NO INDICATION THAT THE DUCT SMOKE DETECTORS
 WILL BE TIED INTO THE BUILDING FIRE ALARM SYSTEM AS
 REQUIRED BY FBC, M 606.4.1. THERE IS NO REQUIREMENT FOR
 THE DETECTORS TO BE INTERCONNECTED OR FOR ALL DETECTORS
 TO SHUT DOWN AT ONCE, BUT THIS CONFIGURATION IS
 ACCEPTABLE AS A DESIGN CHOICE.
  
 4. OK
  
 5. NOTE #28: THIS NOTE IS NOT SUFFICIENT TO DEMONSTRATE
 CODE COMPLIANCE. IF THERE IS A SPRAY FOAM PLASTIC
 INSULATION WHICH IS TESTED AND LISTED FOR USE IN A
 PLENUM, PLEASE SUBMIT THE DOCUMENTATION FOR REVIEW
 PRIOR TO PERMIT ISSUANCE. FBC, M 60.2.1.5 AND FBC
 2603.4.
  
 6. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]