Plan Review Notes For Permit 07120174 |
Permit Number |
07120174 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-02-11 18:17:32 | REVIEW #: 2ND | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | 1. THIS APPEARS TO BE A LEVEL 3 ALTERATION IN | | ACCORDANCE WITH FBC, EB 305.1. SEE BUILDING PLAN REVIEW | | COMMENTS. | | | | 2. OK | | | | 3. THERE IS NO INDICATION THAT THE DUCT SMOKE DETECTORS | | WILL BE TIED INTO THE BUILDING FIRE ALARM SYSTEM AS | | REQUIRED BY FBC, M 606.4.1. THERE IS NO REQUIREMENT FOR | | THE DETECTORS TO BE INTERCONNECTED OR FOR ALL DETECTORS | | TO SHUT DOWN AT ONCE, BUT THIS CONFIGURATION IS | | ACCEPTABLE AS A DESIGN CHOICE. | | | | 4. OK | | | | 5. NOTE #28: THIS NOTE IS NOT SUFFICIENT TO DEMONSTRATE | | CODE COMPLIANCE. IF THERE IS A SPRAY FOAM PLASTIC | | INSULATION WHICH IS TESTED AND LISTED FOR USE IN A | | PLENUM, PLEASE SUBMIT THE DOCUMENTATION FOR REVIEW | | PRIOR TO PERMIT ISSUANCE. FBC, M 60.2.1.5 AND FBC | | 2603.4. | | | | 6. OK | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|